Megmeet inverter - high-voltage inverter selection considerations

Create Date: 2024-8-30 12:03:23|Source: MEGMEET

First, the disadvantages

Choosing too high a voltage level results in too high an investment and a long payback period. With the increase of the voltage level, the insulation of the motor must be improved, so that the price of the motor increases. The increase of voltage level increases the number of series connections of power semiconductor devices in the inverter, and the cost rises.

It can be seen that it is extremely uneconomical and unreasonable to use 6kV and 10kV voltage levels for 200-2000kW motor systems.

Second, the relationship between the number of phases

The inverter device put into the 6kV power grid must comply with the national regulations on harmonic suppression. This is related to the capacity of the grid and the power rating of the device.

The short-circuit capacity is within 1000MVA, and the 1000kW device can be 12 phases (transformer secondary side double winding), if the 24-phase power can reach 2000kW, the 12-phase basically eliminates the 5th and 7th harmonics with large amplitudes.

After the number of rectifier phases exceeds 36 phases, the harmonic current amplitude decreases insignificantly, and the manufacturing cost is too high. If the grid short-circuit capacity is 2000MVA, the allowable capacity of the installation is larger.

3. Save investment

Considering the necessity of voltage level from the characteristics and safety factor of power electronic devices, limited by the voltage of power electronic devices and the allowable dv/dt of the motor, the 6kV inverter must be connected in series with multiple levels or multiple devices, resulting in complex lines, expensive and poor reliability. For the 6kV inverter, if 1700VIGBT is used, take the PERFECTHARMONY series of 6kV high-voltage inverter of United States Robin Kang as an example, each phase is connected in series by 5 power units with a rated voltage of 690V, and a total of 60 devices in three phases. If 3300V devices are used, a total of 30 devices in 3 strings are also required, which is a huge number. On the other hand, the device current is small, the current capacity of the device is not fully utilized, taking 560kW as an example, the current of the 6kV motor is only about 60A, and the IGBT current of 1700V has reached 2400A, and the current of the 3300V device is 1600A. Even with a motor power of 2,000 kW, the current is only about 140 A, which is still very small.

Foreign medium voltage inverters have multiple voltage levels: 1.1kV, 2.3kV, 3kV, 4.2kV, 6kV, which are mainly determined by the voltage level of power electronic devices.

For an inverter with the same output, the cost of using a higher voltage or more units in series is greater than the cost of using a lower voltage, a smaller number of units with a larger current, that is to say, the lowest voltage level should be selected as much as possible under the allowable condition of the device current.

Fourth, the issue of isolation

In order to isolate, improve the input current and reduce harmonics, all medium-voltage "direct inverters" are not true direct inverters, and their input side is equipped with an input transformer, which will not change for a short time. Since there is a transformer on the input side, the voltage of the inverter and the motor is not necessary to be the same as the power grid, 10kV and 6kV must be used, and the voltage below the power of 2500kW can not exceed 3kV, so there is a reasonable voltage level of the inverter and the motor.

——380V or 660V voltage level should be selected for frequency conversion speed regulation below 800kW. It has simple lines, mature technology, high reliability, small DV/DT and low price. Taking 560kW motors as an example, there are about 350,000 low-voltage inverters with 630kW and 660V low-voltage inverters, and about 900,000 medium-voltage inverters with the same capacity of 6000V. There are several forms of low-low, low-high, high-low, and high-low-high. Because of the motor, the price of the transformer is much lower than that of the inverter, and even if the motor and transformer are replaced, it is reasonable.

Fifth, how to match

How to match the original 6kV high-voltage motor with the 3.5kV inverter voltage

Since the founding of the People's Republic of China, the traditional 6kV high-voltage motor is the main product that has been put into production, in order to promote the 3.5kV inverter can no longer spend money to replace the motor, the author proposes a simple scheme for reference.

The original 6kV motor in the manufacturer is generally star-wired, and the actual voltage of the phase winding is 3468V, so as long as the winding is reconnected to a triangle, the others remain unchanged. With a 3.5kV inverter, the inverter voltage is reduced from 6kV to 3.5kV, and it can be seen from Table 3 that the 4.5kV device can withstand 3kV withstand voltage without being connected in series. If you use a 1.7kV device for 3 strings, you can do it. Manufacturing costs will drop by 30%. At present, the maximum motor of 30MW unit in China is 2500kW, and the voltage of 3.5kV is completely reasonable.

6. Harmonic pollution

From a practical point of view, the rectifier bridge is composed of 12-phase rectification, which can eliminate the 5th and 7th harmonics, which basically meets the harmonic requirements of the power grid. Therefore, 400kW-800kW can be rectified with 12 phases, and 1000kW-2500kW with 24 phases can also meet the requirements.
Megmeet inverter - high-voltage inverter selection considerations

More on that
Megmeet inverter - precautions for inverters at high temperatures Megmeet inverter - precautions for inverters at high temperatures

1. Carefully monitor and record the display parameters on the man-machine interface of the inverter, and reflect the abnormality immediately; 2. Carefully monitor and record the ambient temperature of the frequency conversion room, and the ambient temperature should be between -5 °C and 40 °C. The temperature rise of the phase-shifting transformer should not exceed 130°C; 3. Summer ...

Megmeet PLC - an introduction to the classification of PLC Megmeet PLC - an introduction to the classification of PLC

There are many types of PLC products, and their specifications and performance also vary. PLCs are usually classified according to their different structural forms, differences in functions, and the number of I/O points. 2.1 Classification by structural form According to the structural form of PLC, PLC can be divided into whole ...

Common faults of Megmeet drives and how to deal with them Common faults of Megmeet drives and how to deal with them

1. When the oscilloscope looks at the current monitoring output of the driver, it finds that it is all noisy and cannot be read Cause: The current monitoring output is not blocked from the AC power supply (transformer). Solution: You can use a DC voltmeter to detect and investigate. 2. Servo motor high speed ...

Common faults and solutions of Megmeet PLC Common faults and solutions of Megmeet PLC

1. Do not execute the program: The input check is identified by the input LED indicator or the input monitor composed of a writer. When the input LED is not lit, it can be preliminarily determined that the external input system is faulty, and then check with the multimeter. If the output voltage is not normal, it can be determined that ...

Megmeet drives – a common fault in low-voltage drives Megmeet drives – a common fault in low-voltage drives

External electromagnetic interference can easily cause malfunctions If there are interference sources around the inverter, they will invade the inside of the inverter through radiation or power lines, causing the control loop to malfunction, causing abnormal operation or shutdown, and even damage to the inverter in severe cases. Noise suppression on the outside ...

Megmeet inverter - inverter braking mode and advantages and disadvantages introduction Megmeet inverter - inverter braking mode and advantages and disadvantages introduction

What are the braking methods of the inverter? Generally speaking, braking refers to the technical measures taken during the operation of the motor due to fault protection or man-made active shutdown, and the commonly used inverter braking methods include energy consumption braking, feedback braking, DC braking and DC feedback braking. ...

Megmeet drives – what are the basic requirements for regular replacement of drive components? Megmeet drives – what are the basic requirements for regular replacement of drive components?

1. It is necessary to figure out the basic parameters and shape of the device that needs to be replaced. The basic parameters include the rated operating current, the capacitance of the capacitor, the resistance value of the resistor, the value of the GTR Darlington device (current amplification factor), the switching characteristics of the IGBT (including IPM) device, and the saturation voltage ...

Megmeet drives – what are the components of a drive? Megmeet drives – what are the components of a drive?

The inverter is composed of a main circuit, a rectifier, a flat wave circuit, and an inverter. 1) Main circuit: The main circuit is the power conversion part that provides voltage regulation and frequency regulation power supply for the asynchronous motor, and the main circuit of the inverter can be roughly divided into two categories: the voltage type is the DC ...

Megmeet inverter - maintenance precautions and items for high-voltage inverters Megmeet inverter - maintenance precautions and items for high-voltage inverters

Precautions for maintenance of high-voltage inverters 1. Carefully monitor and record the display parameters on the man-machine interface of the inverter, and reflect the abnormality immediately 2. Carefully monitor and record the ambient temperature of the inverter room, and the ambient temperature should be between -5 °C and 40 °C. Phase-shifting transformers ...

Hollysys edge intelligent controller and edge intelligent all-in-one machine launched new products Hollysys edge intelligent controller and edge intelligent all-in-one machine launched new products

Transportation power, urban rail responsibility. With the vigorous development of emerging technologies such as 5G, cloud computing, big data, and artificial intelligence, more innovative technologies are accelerating the empowerment of urban rail transit, and smart urban rail is ushering in a "golden age" of development. As a deep cultivator in the field of smart urban rail, Hollysys adheres to technological innovation.

Megmeet inverter - heating noise harmonic problems in inverter applications and countermeasures Megmeet inverter - heating noise harmonic problems in inverter applications and countermeasures

First, some problems in the application of frequency converter 1.1 Harmonic problems The devices that play a switching role in the main circuit of the inverter must generate harmonics in the process of turning on and off the circuit. The lower harmonics usually have a greater impact on the motor load, causing torque ripple; And the higher ...

Solutions to common faults of Megmeet inverter (2) Solutions to common faults of Megmeet inverter (2)

Fault three Fault phenomenon: There is a rebound phenomenon when the rotation starts Solution: 1. Set the start frequency P08.02 and start frequency time P08.03 appropriately (such as P08.02=P08.03=0.5) 2. Appropriately reduce the stator resistance (P03.07) and no-load current value (P03.11 ...

Megmeet drives – how should high-voltage drives be maintained after they are shut down? Megmeet drives – how should high-voltage drives be maintained after they are shut down?

1. Check the surrounding situation - carefully check the ventilation and lighting of the inverter and the surrounding environment. It is necessary to ensure that the ventilation equipment is functioning properly and that the lighting equipment is in working order. 2. Check the internal cable - open the inverter cabinet door and check whether the internal cable is damaged, the cable ...

Megmeet PLC - What are the features of the PLC program? Megmeet PLC - What are the features of the PLC program?

1. Correctness (low debugging cost) First of all, the PLC program must be able to work correctly to meet the requirements of the actual control process. This is the essence of the PLC program, and if you don't do that, nothing else makes sense. 2. Reliability (low maintenance cost) Not only to ...

Megmeet drives – safety precautions for the installation of drives Megmeet drives – safety precautions for the installation of drives

When the inverter is installed and wired; Note: When more than two inverters are installed in the same cabinet, please pay attention to the installation position and spacing to ensure the heat dissipation effect. Dangerous: 1. It should be operated by professional electrical engineering personnel, otherwise there is a risk of electric shock. 2. Please make sure before wiring...

Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (1-10) Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (1-10)

1。 How do you distinguish between heavy and light failures? When the fault is light, the system sends out an alarm signal, and the fault indicator flashes. When a major fault occurs, the system issues a fault indication, and the fault indicator is always on. At the same time, a command is issued to break the high voltage and close the prohibition, and the fault information and high voltage are instructed.

Megmeet PLC - Comparison of the advantages of PLC and DDC in building automation systems Megmeet PLC - Comparison of the advantages of PLC and DDC in building automation systems

1. Application field: The initial design goal of PLC is only to replace complex relay circuits, and DDC is originally only used in industrial automation instruments: PLC emphasizes versatility, DDC emphasizes specificity: PLC is used in the field of industrial control, and DDC is used in professional building systems. 2. Structural differences ...

Megmeet drives – routine and regular maintenance of drives Megmeet drives – routine and regular maintenance of drives

1. Maintenance items and scope: Daily maintenance and maintenance of inverter Due to the influence of environmental temperature, humidity, dust and vibration, it will lead to the aging of the internal components of the inverter, resulting in the potential failure of the inverter or reducing the service life of the inverter. Therefore, there is a must ...

Megmeet PLC - the installation method and functional requirements of the PLC Megmeet PLC - the installation method and functional requirements of the PLC

Installation: The installation mode of PLC system is divided into centralized, remote I/O and distributed with multiple PLC networking. Centralized does not need to set up the drive remote I/O hardware, the system response is fast, and the cost is low; Remote I/O is suitable for large systems with a range of ...

Megmeet PLC - What are the steps to complete PLC commissioning? Megmeet PLC - What are the steps to complete PLC commissioning?

1. Check the circuit according to the drawing (without power transmission) The drawings of the general PLC system include two parts: the drawings in the cabinet and the drawings outside the cabinet; The drawing in the cabinet refers to the wiring diagram inside the cabinet; The out-of-cabinet drawings are the wiring diagrams of all electrical cabinets. This part needs to be checked for; ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top