Busway installation method - Wiener

Create Date: 2024-8-30 12:03:23|Source: Woehner/Wiehner

1. Busway horizontal device, the interval between the two brackets is ≯2500mm, and the interval between straight devices is ≯3600mm;

2. When the device bracket is straight, it should be drilled with the channel side plate and fastened with M6-M8 bolts.

3. In the process of installation construction, priority should be given to the construction plan from the power supply system, bus trunk to branch trunk line;

4. The basic sequence of closing the bus duct device: select the wiring direction→ fix the bracket→ fix the slot hole with four bolts→ add the bus bar adapter plate and insulating pad→ single head bolt penetrate the insulating sleeve→ bolt into the bus preset hole→ fasten at both ends→ install the upper and lower half covers→ fix the channel on the bracket.

                               Busway installation method - Wiener

5. When installing the channel bus, the start, middle, end and channel shell should be reliably connected to the grounding network of the electrical equipment. The channel shell coated with insulating material should be connected with flat copper tape or yellow-green cable on the grounding bolt between the two channels to ensure that the entire channel is connected to form a grounding system.

6. After the installation project is completed, before power transmission, use a vibration meter to test the insulation resistance of the channel bus interphase and ground insulation: (1) The low-voltage bus channel is not less than 20MΩ; (2) About 6-10KV high-voltage bus channel insulation resistance is not less than 1200MΩ. 35KV insulation resistance is not less than 3000MΩ.

7. Before transmission, the 6-35KV bus channel should be subjected to 50HZ power frequency withstand voltage test and DC leakage test, and it can be put into operation only after it is qualified;

8. The bus duct is put into operation, tighten the bus joint bolts within 3 months, and check the contact status of the bus joint;

9. Check the following items of the bus duct in operation at least once a year:

1) Tighten the fixing bolts, especially the bus joints, observe whether the joints have poor contact or burnout caused by overcurrent, and deal with them;

2) Test the degree of insulation of the swing meter and check whether the insulation material is aging;

3) The connection between the bus channel and the grounding grid;

4) Pay attention to the internal and external absorption of dust and condensate;

More on that
The main components of the Wiener bus system in the distribution cabinet are composed The main components of the Wiener bus system in the distribution cabinet are composed

(1) Busbar It is the basic element of the bus system, and there are a variety of standards, which can be installed with 5mm or 10mm thick rectangular busbar, double T type and triple T type busbar. The busbar is divided into 1-4 wires, 1 wire can be used with N or PE, 2 wires can be used together with N and PE, 3 wires are two-phase, and 4 wires can be used for three-phase ...

Phase of the busway in the low-voltage incoming line – Wiener Phase of the busway in the low-voltage incoming line – Wiener

According to the requirements of the relevant specifications, the placement of the three-phase busbar can be roughly divided into two kinds according to the model of the low-voltage distribution cabinet and the different manufacturers: horizontal placement and placement of the down wire, according to the order of placement.

Standard parameters of busway specification - Wiener Standard parameters of busway specification - Wiener

1. The standard scale of the bus duct This specification regulates the terminology, skill requirements and test methods of the insulated bus trunk system (bus duct) and its plug-in feed box (hereinafter referred to as the feed box). This specification specification applies to additional voltage AC to 660V...

Applications in the power of busbar systems – Vernal Applications in the power of busbar systems – Vernal

The bus refers to the connection of voltage transformers and other voltage distribution devices at all levels in the substation, as well as the connection of electrical equipment such as transformers and corresponding distribution devices, and most of the bare wires or stranded wires with rectangular or circular cross-sections are selected. Follow the lines ...

The difference between air-type busway and dense busway - Vernal The difference between air-type busway and dense busway - Vernal

1. The insulating medium is different: there is a certain open space between the copper bars of the air bus duct, that is to say, the insulation between the copper bars mainly depends on air, and the insulation medium between the copper bars of the dense bus duct (many people call it a closed bus duct) is an organic insulating material. 2. Copper bar placement ...

What are the modules of the Wiener bus system? What are the modules of the Wiener bus system?

The modulus of the bus system is 40mm, 60ram, 100/185mm; The bus cross-section is rectangular, double "T" (i.e., "H" shape) and three "T" (i.e., 'state') shapes; The bus system can be three-wire, four-wire or five-wire, or even seven-wire, of course, it should be determined according to the needs ...

220V DC Hazard of Bus System – Wiener 220V DC Hazard of Bus System – Wiener

The grounding of the DC system should include two situations: the one-point grounding of the DC system and the two-point grounding of the DC system. In the DC system, the positive and negative poles of the DC are insulated from the ground, and when the ground of one pole is generated, there is no grounding current due to the fact that there is no grounding current.

Low-voltage dense busway uses and applications Low-voltage dense busway uses and applications

Densely insulated bus duct (hereinafter referred to as bus duct) can be communication three-phase three-wire, three-phase four-wire, three-phase five-wire system, frequency 50-60Hz, voltage to 400V, rated operating current of 250-5000A, mainly as a new type of power supply and distribution equipment in industrial and mining, enterprises and high-rise buildings. Mother with insertion day ...

Calculation method of bus system and distribution cabinet bus - Wiener Calculation method of bus system and distribution cabinet bus - Wiener

The bus system divides the bus into hard bus and soft bus. The 60mm bus system refers to the three-wire or four-wire bus with a distance of 60mm. 1. In the 60mm bus system, the different cross-sectional areas of rectangular copper bars or special-shaped copper busbars such as 2T and 3T can be used to achieve the best classification of current intensity grades.

Advantages of a shared DC bus system – Wienal Advantages of a shared DC bus system – Wienal

The shared DC bus system is the future development direction in the application of multi-drive motors, which makes reasonable use of the regenerative energy of the system together with better dynamic and static functions and speed regulation accuracy, eliminating a lot of braking units and braking resistors, and the energy efficiency ratio of the system has been greatly improved.

Wiener bus differential protection switching operation Wiener bus differential protection switching operation

1. Whether the scale of bus differential maintenance is determined, and whether the maintenance goal is unchanged Generally, differential maintenance includes bus differential maintenance, transformer differential maintenance, generator differential maintenance and line differential maintenance. The basic principle of achieving differential maintenance is common, i.e. on all sides or on each side...

The application of Wiener bus system wiring technology in box transformer The application of Wiener bus system wiring technology in box transformer

The bus system is to directly connect the components to the bus, the bus does not need to be perforated, at this time, the bus is not only the conductor of the component, but also the support of the component, the current can reach 2500A, so that the box transformer function has the following progress: 1 ...

What is tubular busbar and dense busbar - Wiener What is tubular busbar and dense busbar - Wiener

What is a tubular busbar Tubular bus bar is a kind of bus bar product with copper tube or aluminum alloy tube as conductor and external insulation. The tubular bus has the characteristics of high current (12000A), high mechanical strength, good insulation, wide application range, etc., ...

Bus load forecasting method and characteristics - Wiener Bus load forecasting method and characteristics - Wiener

Bus load guessing is a kind of power system load guessing, and the bus system load can be defined as the sum of the terminal load supplied by the main transformer of the substation to a relatively small power supply area, which is the refinement of the system load. Bus load guessing generally only carries out short-term load guessing, and the result is ...

Difference Between Fuse and Circuit Breaker – Vernal Difference Between Fuse and Circuit Breaker – Vernal

The principle of the fuse is to use the current to flow through the conductor to heat the conductor, and the conductor is ablated after reaching the melting point of the conductor, so the electrical appliances and circuits used for circuit maintenance are not burned out. It is an accumulation of heat, so it is also able to complete overload maintenance. Once...

Features of the use of closed busway - Wiener Features of the use of closed busway - Wiener

Compared with other air-type busway, Wiener closed busway has many similarities in appearance, and its difference lies mainly in the shell, the structure of the closed busway is more distinctive, which also makes its use have certain advantages. As long as it is in contrast ...

Mesh tray reduces the cost of replacing cables – Wiener Mesh tray reduces the cost of replacing cables – Wiener

(1) Simple maintenance and repair operations Equipment is often added or removed or changed in the computer room, and cables are removed or added at the same time, and the grid bridge with open structure can observe the cables to the maximum extent, so it is easy to distinguish the cables that need to be replaced, so that maintenance and repair ...

What are the hazards of 220V DC in the bus system - Wiener What are the hazards of 220V DC in the bus system - Wiener

The grounding of the DC system should include two situations: the one-point grounding of the DC system and the two-point grounding of the DC system. In the DC system, the positive and negative poles of DC are insulated from the ground, and there is no grounding current when generating a ground current when one pole is grounded.

Introduction to the Wiener data center bus system Introduction to the Wiener data center bus system

Although the service life cost of the bus system is usually lower than that of the traditional wiring method, the bus system still bears a considerable cost compared with other structural elements of the water supply and drainage or HVAC system. In addition, customized busbar equipment allows the busbar system to be routed around obstacles ...

Low-voltage enclosed busway function - Wiener Low-voltage enclosed busway function - Wiener

Phase-off bus is a kind of high-current transmission equipment widely used in the outgoing circuit of generators of 50MW and above and the branch circuit of the factory The phase-off busbar, conductor and shell are made of aluminum plate coil and welding, with the following characteristics: ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top