When switching on and off components, you should pay attention to the following:
–In accordance with VDE-0105-100, only operation (non-energized operation, closing, disconnecting, and replacing fuses) is allowed by electrical professionals or persons with electrical knowledge.
– The handle on the fuse cover should be operated quickly.
– Before closing, it is important to note that the fuse cover should be in the precise opening position.
–When the cover is partially opened, the fuse may be electrified, so only the cover handle can be operated.
Wire connection
The depiction of wire mating terminals (clips) applies only to copper wires. The unprotected anti-aging properties of the listed joints have been proven by testing.
Test proof for aluminium wires is only available if specifically mentioned.
Before connecting the aluminium conductors, the oxide layer should be removed from the surface and measures should be taken to avoid oxidation.
After the oxide layer has been removed, no debris or abrasives are present that affect the contact surface. Multi-core conductors should be able to reach the exposed metal conductor part exactly, and an insulating sleeve should be installed. To avoid re-oxidation, the contact points should be sealed (e.g. with acid-free contact grease).
The terminal blocks must be inspected accordingly according to the operating conditions. Under normal environmental conditions and load conditions, it is advisable to check every 6 months. In the case of unfortunate operating conditions, or frequent changes in the temperature of the terminal block, it may be necessary to shorten the inspection period. A temperature measuring strip that can store the maximum value can be installed near the terminal block for objective evaluation when performing a timed view.
Unless otherwise specified, all joints are suitable for connecting a single wire. The dual-function adapter terminal has 2 adapters. In principle, the torque value given in the installation instructions on the equipment or on the company's website shall prevail.
The error of the torque Md of the screw and terminal connection should be within +/- 20% of the rated value if no limit is given. If the size of the terminal cross-sectional area is not given, the size should be limited to two levels below the rated value.
|
More on that
|
Several faults of the Wiener bus system can be avoided
Cause of bus failure
1. The inner network of the bus insulator and the breaker sleeve caused by the dirty appearance
2. The voltage transformer installed on the bus and the current transformer between the bus and the circuit breaker fail
3. Reverse gate ...
|
|
The operation procedure of the dual power supply automatic transfer switch
The dual-supply ACT is a new generation of products. Beautiful appearance, good quality, long life, simple It is composed of two three-pole or four-pole shell graders and their parts/mechanical interlocking transmission arrangements, intelligent controllers, etc., which are divided into two structures: integral and split.
|
|
Introduction to the Wiener busbar system
The 60mm bus system refers to the three- or four-wire bus spacing of 60mm.
In the 60mm bus system, the different cross-sectional areas of rectangular copper bars or special-shaped copper busbars such as 2T and 3T can be used to achieve the optimal distribution of current intensity levels, ...
|
|
Characteristics of the common box closed busbar - Wiener
The common box closed bus includes the non-phase isolated, common box closed bus, phase isolated common box closed bus and AC and DC excitation common box bus, which are used for current transmission between the generator lead wire below 100MW and the low-voltage side of the main transformer or between the low-voltage side of the transformer and the high-voltage distribution device of the unit of 75MW and above.
|
|
Phase of the busway in the low-voltage incoming line – Wiener
According to the requirements of the relevant specifications, the placement of the three-phase busbar can be roughly divided into two kinds according to the model of the low-voltage distribution cabinet and the different manufacturers: horizontal placement and placement of the down wire, according to the order of placement.
|
|
Scenarios for the use of various types of busbars - Vernal
1. The bus bar is divided into hard bus bar and soft bus bar.
2. According to different shapes, hard busbars can be divided into: rectangular busbars, tubular busbars, trough busbars, diamond busbars, etc.
3. Rectangular busbar is a commonly used busbar. According to its material ...
|
|
The advantages of busway are used in cable tray installations
At the time of the cable tray installation, the wiring is not very convenient. This phenomenon can be avoided by using busway. The 5 advantages of using busway in the cable tray device are as follows:
1. Convenient connection of bus duct: the so-called plug-in bus...
|
|
The difference between metal busbar and closed busbar - EVOC
The nature is different
Busbar: It is a common path on which multiple devices are connected in the form of side-by-side branches.
Busway: It is a closed metal equipment composed of copper and aluminum busbars.
Different uses
Mother...
|
|
Introduction to the Wiener data center bus system
Although the service life cost of the bus system is usually lower than that of the traditional wiring method, the bus system still bears a considerable cost compared with other structural elements of the water supply and drainage or HVAC system.
In addition, customized busbar equipment allows the busbar system to be routed around obstacles ...
|
|
Dense busbar installation – Wiener
1. Requirements for civil engineering before installation
1) The foundation, structure, reserved holes and embedded parts all meet the design requirements of electrical equipment.
2) After the construction of the roof and floor slab is completed, there shall be no leakage.
3) After the indoor ground construction is completed, mark the ground leveling line on the well wall.
...
|
|
Distribution cabinet bus calculation method - Vilna
1. The main bus at the upper end of the low-voltage distribution cabinet is calculated according to the material and cross-section in the extension meter. The bus bar connected to the main bus at the upper end of the switch is not accounted for and is included in the low-voltage distribution cabinet.
2. The transformer mainly depends on how large the load is, according to your switchgear can be calculated to match the transformer, but not the same...
|
|
Introduction to several power supply systems – Wienal
At present, China has five power supply systems: IT, TT, TN-c, TN-c-s and TN-S. They have their own advantages and disadvantages, and we should choose sensitively according to the actual situation in life.
Five power supply systems
1.IT power supply system
In a ...
|
|
Considerations for purchasing a busbar system – Wiener
The bus system plays a very important role in the practice of construction, and for products such as the bus system, the relevant items can not be ignored, so that we can better use the practical value of this type of product. Generally speaking, when we are purchasing a bus system ...
|
|
Wiener bus adapter features:
Functional aspects
The bus bar is made of copper or aluminum, which has high current density, small resistance and small skin effect, and does not need to be used for capacity reduction. The small voltage drop also means that the energy loss is small, which ultimately saves the user's capital. As far as the cable is concerned, because the cable core is a multi-strand thin copper wire, its root surface ...
|
|
Difference Between Busbar and Cable – Vernal
When the busway has not been developed and introduced, the cable is still an indispensable figure in the low-voltage distribution system, when the busway system is introduced and widely used. Whether to choose the cable or the bus duct has become a topic of endless debate. So it's hard to say which of the two is better ...
|
|
Busway Installation Specification – Wiener
1: The basic requirements for the bus duct:
1) Conductor data: high-purity electrical copper drawn from national standard T2 electrolytic copper, with a purity of more than 99.9% and a full-length tinned copper conductor. 2) Shell: Select high-quality aluminum-magnesium alloy profiles that meet the strength, with heat dissipation ribs, and the appearance should be oxygen-proof.
|
|
Busbar system in detail – Vernal
1. In the 60mm bus system, the square fuse type blocking switch can be directly hooked.
2. The 60mm bus system refers to the three-wire or four-wire bus spacing of 60mm.
3. Strip NH-fuse type load barrier switch with scale 00 ...
|
|
What are the modules of the Wiener bus system?
The modulus of the bus system is 40mm, 60ram, 100/185mm; The bus cross-section is rectangular, double "T" (i.e., "H" shape) and three "T" (i.e., 'state') shapes; The bus system can be three-wire, four-wire or five-wire, or even seven-wire, of course, it should be determined according to the needs ...
|
|
The Wiener bus is a Siemens 3 VA1 and 3 VA2 adapter
Wiener has developed a new series of 3 VA1 circuit breakers equipped with ® busbar adapters from Siemens in the 160 system with a compact range of 30.
The safety articulation of the circuit breaker is the internal right of the tension spring device base and high-performance rails.
...
|
|
Advantages of cable tray installed in busway
At the time of the cable tray installation, the wiring is not very convenient. This phenomenon can be avoided by using busway. The 5 advantages of using busway in the cable tray device are as follows:
1. Convenient connection of bus duct: the so-called plugging ...
|
|