RKC thermostat - how to keep the line when installing the thermostat?

Create Date: 2024-8-30 12:03:23|Source: RKC

First, the selection of the orientation of the thermostat device

1. Easy to operate locally;

2. It can include the average temperature of the local area;

3. Localities with more human activities;

4. It can avoid cold and heat sources;

That is to say, the orientation of the device should be far away from the radiator, away from the doors and windows, otherwise the heating will be just hot, the wall-hung boiler will stop, and the wall-hung boiler will start as soon as the doors and windows are opened.

The height of the device is about 1.4 meters (on the same level as the switch of the light) and the distance from the door and window is more than 0.8 meters.

5. Embed the square wire box (general power supply 86 junction box) in the selected direction, and lead out the wire pipe from here to the direction of the wall-hung boiler.

Second, the wiring direction of the wall-hung boiler

1. On the left and right sides of the bottom of the wall-hung furnace, arbitrarily select the wiring port;

2. Pre-embedded square wire box with a box cover with a round hole in the middle;

3. Use 2×0.75 and above multi-strand twisted pair flexible wire (telephone line and lamp head line can be used, but two), 0.5 meters are reserved in the threading room, and 1 meter is reserved for the wall-hung boiler.

4. Wrap the reserved wire into a ball and put it into the box, and then seal the wire box with hard foam of the same size (so as not to be pulled)

3. The easiest way to stay in line

1. After opening a small groove downward in the direction of the thermostat of the device (to the depth of the thread) to the ground, place the line along the wall until the bottom of the wall-hung furnace;

2. Open a small groove under the wall-hung furnace wall to the direction of the line to be out, and bury the line in;

3. The wire in the wall groove should be nailed with a small wire clip;

4. Smooth the groove;

5. The wire diameter is 2×1.0, and it can be used continuously as long as it is continued.
RKC thermostat - how to keep the line when installing the thermostat?

More on that
RKC Thermostats – How to Choose a Thermocouple? RKC Thermostats – How to Choose a Thermocouple?

The selection of thermocouples should be based on comprehensive considerations such as the operating temperature range, the required accuracy, the operating atmosphere, the performance of the measured object, the response time and the economic benefits. 1. Selection of measurement accuracy and temperature measurement range 1) The operating temperature is 1300-1800°C, and the accuracy is required to be more accurate than ...

RKC Temperature Control Meter - How to set the temperature control meter RKC Temperature Control Meter - How to set the temperature control meter

1. Turn on the power supply of the smart thermostat, and the temperature displayed on the screen is the temperature at that time. Because the sensor is not in contact with other devices, but is directly exposed to the air clock, this is the current temperature: 31 degrees Celsius, which is not too hot. 2. At the bottom right of the display screen is the "starting temperature" setting ...

Common faults and analysis of thermostats Common faults and analysis of thermostats

Common faults of thermostats 1. There is no display when the power is on. This type of problem first determines whether the power supply is available and whether the power supply matches the power supply required by the thermostat, and then checks whether the wiring is secure. The problem is still there, then it is the problem of the thermostat itself. 2. There is a display, and the control is wrong. This...

RDC converters – a classification of power converters RDC converters – a classification of power converters

Motors are divided into two categories: DC motors and AC motors, and AC motors are divided into asynchronous motors and synchronous motors, and their respective speed regulation principles are also different. According to the speed regulation requirements of the motor, it can be divided into two categories: DC power converter and AC power converter: ...

RK Level Gauge - Four common types of faults and solutions for float level gauges RK Level Gauge - Four common types of faults and solutions for float level gauges

1. The indicated value is large (or out of range). According to the investigation of our staff, this kind of problem often appears in the atmospheric pressure workshop. When we find that the counterweight of the float in the float level gauge is at a low point, the liquid level must be very high at this time, and the glass plate is inconsistent with the indication of the instrument.

RLC thermostat - a detailed explanation of dry-type transformer thermostats RLC thermostat - a detailed explanation of dry-type transformer thermostats

The working principle of dry-type transformer thermostats The dry-type transformer temperature controller is a new generation of controller designed for the safe operation of dry-type transformers. The controller adopts single-chip microcomputer technology, and uses three platinum thermal resistors embedded in the three-phase winding of the dry-type transformer to detect and display the transformer.

Common faults and failure analysis of RTC thermostats Common faults and failure analysis of RTC thermostats

1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which leads to the breakpoint of the solder joint, and sometimes it is caused by the phenomenon of virtual soldering at the factory, and the main re-soldering can be done. 2. Temperature controller ...

A few things to note about the installation of the RKC thermostat A few things to note about the installation of the RKC thermostat

1) For RTD input, 3 wires with low resistance and no difference should be used. 2) The input signal line should be far away from the power line of the instrument, the power supply line and the load line to avoid noise and annoyance. 3) The power cord of the instrument is generally annoyed by the power supply. 4) Instrument complement ...

For some considerations in the RKG thermostat setup For some considerations in the RKG thermostat setup

RKC Thermostat Operation Note: 1. Clean the instrument only after the power is off; 2. To remove the stains on the monitor, please use a soft cloth or cotton paper; 3. The display is easy to be scratched, and it is forbidden to use hard objects to operate the panel buttons, otherwise the buttons will be damaged or scratched. RLC thermostat ...

Introduction to the types of alarms for RKC thermostats Introduction to the types of alarms for RKC thermostats

* Alarm table {ALM1} (standard built-in) A: Upper limit deviation alarm G: Standby upper and lower limit deviation alarm attached B: Lower limit deviation alarm H: Upper limit input value alarm C: Upper and lower limit deviation alarm J: Lower limit input value alarm D: Alarm in the range K: Attached standby ...

Introduction and wiring method of Japan physical and chemical RKC thermostat Introduction and wiring method of Japan physical and chemical RKC thermostat

  The core control algorithm of the temperature regulator is PID control, P (Proportional) ratio + I (Integral) point + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, custom parameter control, adaptive parameter control and other algorithms, ...

Technical characteristics of the RKC thermostat Technical characteristics of the RKC thermostat

The core control algorithm of the thermostat is PID control, P (Proportional) + I (Integral) integral + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, self-tuning parameter control, adaptive parameter control and other algorithms, temperature control ...

RLC thermostat - common faults of temperature controllers and solutions RLC thermostat - common faults of temperature controllers and solutions

Fault 1: The device does not display after powering on Solution(s): First of all, check whether the terminals of the device have been connected to the neutral live wire, and make sure that the neutral live power supply can work normally. Then start to check whether the cable between the LCD motherboard and the device drive power supply is ...

RLC thermostat - common faults and treatment methods of dry-type transformer thermostats RLC thermostat - common faults and treatment methods of dry-type transformer thermostats

1. There is no display of dry-type transformer thermostat Cause of failure: (1) The power supply of the thermostat is not connected; (2) The fuse is blown out. Solution: (1) Turn on the power supply; (2) Replace the fuse. 2. The dry-type transformer thermostat shows that one or three phases are flashing and displays "-OP-" ...

RKC Level Gauge - Preservation and storage of float level gauges in daily use RKC Level Gauge - Preservation and storage of float level gauges in daily use

1. To avoid damage to the instrument, pay attention to the correct protection method: in order to ensure the accuracy of the instrument and avoid damage to the instrument, try not to use the protection instrument of isolator or other isolation devices. If you have to do it, you should also pay attention to the careful selection, determine the isolation solution, and wash the isolation film correctly, ...

RLC Level Gauge - Classification and construction of pontoon level gauges RLC Level Gauge - Classification and construction of pontoon level gauges

1. Classification of pontoon level gauges The pontoon level gauge is also divided into two types: inner pontoon and outer pontoon, the so-called internal and external division refers to the place where the pontoon is installed, in the container of the liquid to be measured is the inner pontoon, and the outer pontoon is called the outer pontoon outside the liquid container to be measured.

RKC thermostat operation attention and its main features RKC thermostat operation attention and its main features

RKC thermostat operation attention · Clean the instrument only after the power is off; · Please use a soft cloth or cotton paper to remove stains on the monitor; · The display is easy to be scratched, it is forbidden to use hard object to operate the panel buttons, otherwise the keys will be damaged or scratched.   Key features: ...

RHK thermostat - 5 common problems and solutions for stand-alone thermostats RHK thermostat - 5 common problems and solutions for stand-alone thermostats

Fault 1: The thermostat does not turn on (does not light up) Analyze the causes 1. Wrong wiring 2. The voltage of the input terminal is not enough or the input terminal is damaged by empty opening and leakage 3. Whether the cable between the panel and the power board is broken or plugged incorrectly 4. Load short circuit or open circuit, probe ...

RKC Thermostat How to properly select and use a pressure sensor RKC Thermostat How to properly select and use a pressure sensor

 High-temperature melt pressure sensors, transmitters, and high-temperature melt pressure gauges are special equipment in extrusion processing. On the production line, melt pressure sensors play an important role in improving melt quality, increasing production safety and protecting production equipment. Use...

Wiring method of the RKG thermostat Wiring method of the RKG thermostat

Take CD901 as an example, L(1) pin to 220 volt live wire, N(2) pin 220 volt neutral wire, 3,4 pins for the first output, 5,6 pins for the second output, 7, 8, 9 pins are alarm output, Finally, the three pins are connected to thermocouples or PT100 ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top