Common causes and solutions of PLC failures in Omron operation

Create Date: 2024-8-30 12:03:23|Source: Omron/Omron

Fault phenomenon: The analog module CJ1W-DA041 outputs 4-20mA current for 4 channels, of which channels 2 and 3 are normal, and channels 1 and 4 have no current output.

Analyzing the circuit, the 4 current outputs use 4 integrated blocks LT1490 for D/A conversion, first measure the external components on the integrated block LT1490 on channels 1 and 4, and no problems are found with the triode and resistor.

It is suspected that the integrated block LT1490 on the 1st and 4th channels is damaged, because there are no spare parts in hand, try to use the method of reversal to judge, change the integrated block LT1490 on the 1st channel to 2 channels, and change the integrated block LT1490 on the 2nd channel to 1 channel.

As a result, the current output of channel 1 is normal, and the current output of channel 2 is not current, so it is judged that channel 1 is the fault of the integrated block LT1490, and the same method is used to judge that the 4 channel is also damaged by LT1490, and 2 new LT1490 are purchased, replaced, and troubleshooting.

(1) Failure of peripheral circuit components

This kind of failure is more common in PLC maintenance, and it is generally a frequent occurrence in failures after a certain period of work. In the PLC control loop, if there is a component damage fault, the PLC control system will immediately and automatically stop working.

The input circuit is the port of the PLC to accept the input signals such as switching quantity and analog quantity, and the quality of its components, wiring mode and whether it is reliable are also important factors affecting the reliability of the control system.

For the switching output, the output of the PLC has three forms: relay output, thyristor output and transistor output, and the specific choice of which form of output should be decided according to the load requirements, and the improper selection will reduce the reliability of the system

Low When it is severe, the system cannot work properly.

In addition, the load capacity of the output terminal of the PLC is limited. If the stated maximum limit is exceeded. An external relay or contactor must be connected. to work properly.

The quality of actuators such as external relays, contactors, and solenoid valves is an important factor affecting the reliability of the system. Common faults include short circuits in the coil, mechanical failures that cause immobility of the contacts or poor contact.

(2) Poor terminal wiring contact

This kind of fault occurs after the PLC has been working for a certain period of time with the increase in the frequency of equipment action. Due to the defects in the wiring of the control cabinet or the intensification of vibration in use and the mechanical life, etc.,

The terminal blocks or component binding posts are prone to loosening and cause poor contact.

The method of troubleshooting this kind of fault is to use a multimeter, with the help of the control system schematic diagram or PLC logic ladder diagram for fault diagnosis and maintenance.

For the wiring of some important peripheral terminals, in order to ensure reliable connection, the method of soldering cold-pressed sheets or cold-pressed pins is generally used.

(3) Functional failure caused by interference of Omron PLC

The various types of PLCs used in automation systems are control devices specially designed for industrial production environments. In the design and manufacturing process, multi-level anti-interference and selected component measures are adopted, so it has a strong ability to adapt to harsh industrial environments, operational stability and high reliability. Therefore, it can generally be used directly in an industrial environment without any special measures.

The interference experienced by the PLC can be divided into internal interference and external interference. In the actual production environment, external interference is random, independent of the system structure, and the source of interference cannot be eliminated and can only be limited on a case-by-case basis.

Internal interference is related to the structure of the system. It is mainly caused by the AC main circuit and analog input signal in the system, and the internal interference can be suppressed to the greatest extent through careful design of system circuits or system software filtering.
Common causes and solutions of PLC failures in Omron operation

More on that
Analysis of the location and cause of Omron PLC failure Analysis of the location and cause of Omron PLC failure

1. External equipment failure. Such faults come from external devices such as various sensors, switches, actuators, and loads. The failure of this part of the equipment will directly affect the control function of the system. This type of failure is usually caused by the quality and longevity of the equipment itself. 2. System failure ...

Routine maintenance methods of Omron relays Routine maintenance methods of Omron relays

1. In the operation of Omron relay, if there is an abnormal sound or other abnormal conditions, the operation should be terminated first, and the skilled and professional repair staff should be notified to repair, and the operation can be resumed after the common fault is cleared. 2. In the whole process of maintenance, check the spring ...

What are the maintenance precautions for Omron relays? What are the maintenance precautions for Omron relays?

1. In the operation of Omron relay, if there is any abnormal sound or other abnormal phenomena, the operation should be stopped immediately, and the professional maintenance personnel should be notified to come for maintenance, and the normal operation can only be put into normal operation after troubleshooting. 2. During the maintenance process, check whether the spring is deformed, old...

Omron brought a variety of new blood pressure monitors to the Expo Omron brought a variety of new blood pressure monitors to the Expo

Hypertension is the main risk factor for cardiovascular and cerebrovascular diseases, and is known as the "invisible killer of human health". The Lancet study shows that the number of hypertensive adults aged 30-79 has increased from 650 million to 1.28 billion in the past 30 years. In China, hypertension is also a cardiovascular disease.

What should Omron PLC pay attention to when selecting a model What should Omron PLC pay attention to when selecting a model

Omron PLC is a compact PLC with perfect functions, which can provide high value-added machine control for industry-leading conveying and decentralized control; It also has the ability to upgrade through a variety of advanced built-in boards, large program capacity and memory units for efficient software development in the Windows environment ...

How to input Omron PLC timer command? How to input Omron PLC timer command?

1. After opening Omron PLC, you need to set LD X0 through ladder input and confirm. 2. After getting X000 in the next step, use the ladder diagram input to determine the timer instruction of out T0 K30. 3. At this time, the relevant settings will be completed, and you can directly ...

Omron switch - 9 tests and methods for switching power supplies Omron switch - 9 tests and methods for switching power supplies

1. Repeated short-circuit test ◆ Test instructions The output of the module is short-circuited in various input and output states, the module should be able to achieve protection or retraction, repeated short-circuits, and after troubleshooting, the module should be able to automatically resume normal operation. ◆ Test Method a ...

What are the advantages of Omron MOS FET relays? What are the advantages of Omron MOS FET relays?

1. The relay is small and still weldable. The relays in SSOP/USOP packages feature directly exposed terminals for excellent visibility and easy installation. 2. Ultra-small and lightweight: In addition to SSOP and USOP, ultra-small packages contribute to the miniaturization of devices. ...

Introduction to the classification of Omron relay switch contacts Introduction to the classification of Omron relay switch contacts

1.A contacts A contact is a contact in which the two contact terminals are separated (OFF) when the switch is not operated, and closed (ON) when the switch is operated. If you want to start the load by operating the switch, you can use the A contact. A circuit is a circuit that uses a contact without operating the switch (pressing ...

How to add SMC module to Omron plc How to add SMC module to Omron plc

After adding the I/O module, you need to set it in the CX-PROGRAMMER program. Find the IO table and unit settings, double-click to find the mainframe [0000], dot + sign, and then double-click 00 (if not set), 00 represents the module number closest to the CPU.

Omron PLC's maintenance procedures and equipment cleaning regulations Omron PLC's maintenance procedures and equipment cleaning regulations

1. Maintenance procedures, regular testing and adjustment of equipment (1) Check the connection of the terminal blocks in the PLC cabinet every six months or quarters, and reconnect the loose places in time if they are found; (2) Re-measure the working voltage of the power supply to the main engine in the cabinet every month ...

Wiring method of Omron relays Wiring method of Omron relays

Step 1: 13 and 14 of the contactor are the contacts of the contactor coil. Step 2: When the voltage is added to 13 and 14, the intermediate relay acts. Step 3: 9, 5 normally open, 9, 1 normally closed, after adding voltage, relay action, 9, 5 normally closed, 9, 1 normally open. Clause...

Omron PLC troubleshooting Omron PLC troubleshooting

1. Power check: The first thing to analyze is the reliability of the power supply and ground of the Omron PLC. Visually inspect power and ground cables for damaged, corroded, or other suspicious links. Power supplies can also be electrically tested. If there is AC power in the PLC processor, test ...

Instructions for the use of Omron relays Instructions for the use of Omron relays

One. Omron relays should be installed in a well-ventilated environment with room temperature and humidity, and there are no flammable gases, dusts and other dangerous factors in the installation environment to ensure that Omron relays can be used normally after being put into operation. Two. The selection of Omron relays should be in line with the actual needs.

How to modify the program online of Omron PLC? How to modify the program online of Omron PLC?

1. After determining the object in Omron PLC, click Write Mode in the edit window. 2. Next, directly select the relevant software components and double-click. 3. At this time, you need to change the number through the ladder diagram input and select OK. 4. Such a ...

Fault maintenance methods commonly encountered in the operation of Omron PLC Fault maintenance methods commonly encountered in the operation of Omron PLC

(1) Failure of peripheral circuit components This kind of failure is relatively common in PLC maintenance and usually occurs frequently after a certain period of work. If there is a component damage fault in the PLC control loop, the PLC control system will stop working immediately and automatically. The input circuit is a PLC receiving switching quantity ...

【Omron industry case】Predictive maintenance of smoke machine in automobile welding workshop 【Omron industry case】Predictive maintenance of smoke machine in automobile welding workshop

Process introduction Automobile welding is the second of the four major processes in vehicle production, which mainly assembles stamped body components into a complete body. In the welding process, spot welding and arc welding of robots are the mainstay, and there will be a station for visual inspection of the welding status in the middle.   Make...

Common problems and solutions in the maintenance process of Omron PLC Common problems and solutions in the maintenance process of Omron PLC

1. CPU abnormality: When the CPU is abnormally alarmed, check all the devices connected to the internal bus of the CPU unit. The specific method is to replace the units that may have problems in turn, find out the problem units, and deal with them accordingly 2. Memory abnormality: Memory anomaly ...

The disassembly sequence and method of Omron PLC equipment The disassembly sequence and method of Omron PLC equipment

(1) Shutdown for maintenance, more than two people must supervise the operation; (2) Change the mode selector switch on the front panel of the CPU from "Run" to "Stop" position; (3) Turn off the main power supply of PLC power supply, and then turn off other power supplies to the mold saka; (4) ...

Omron announces the opening of its California Robotics Headquarters Omron announces the opening of its California Robotics Headquarters

March 12, 2020 - Omron Corporation announces the opening of its Robotics and Safety Automation business headquarters in Pleasanton, California. The company has invested $10 million in its 128,000-square-foot facility to design, develop, test and manufacture robots and safe self-propelled robots.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top