1. What are the factory recovery parameters of Reynolds inverter?
N600 = 100 (often press the WR button for 3-5 seconds), it is necessary to be in the shutdown state to be effective.
2. In the parameters of the N308 motor of the inverter, is the [motor leakage inductance reactance] specified sub-leakage inductance or rotor leakage inductance react?
Stator leakage reactance = rotor leakage reactance = motor leakage reactance
3. Can the inverter check the previous fault information?
Yes, for example RNB6000 it is possible to check the last 8 faulty code information via parameter N603.
4. RNB6000 the N701-N712 parameter specification, but I can't see it in the inverter?
N701-N712 is a tacit hiding group parameter, and N700=7 can be set
5. RNB6000 the parameters of the motor should be entered correctly before starting?
Because the RNB6000-type inverter completes the better control of the motor inside the motor, and a special algorithm is added to achieve better control, so it is necessary to correctly input the parameters on the motor signage. Otherwise, there will be a phenomenon such as starting skipping current or frequency failure.
6. How to set the external analog input of RNB6000 inverter 0-20MA and 4-20MA?
RNB6000 type can be imported externally from 0-20MA and 4-20MA, and the internal parameter N222=0% is 0-20MA input, and N222=25% is 4-20MA input.
7. Can the RNB6000 inverter complete the given switching between the main frequency and the auxiliary frequency source?
The RNB6000 type inverter is possible through the external terminal X1(12). X2 (13) terminals. The X3 (14) terminal completes the frequency switching by binary combination method (such as parameter N203=15.N204=16.N205=17).
8. What is the difference between the RNB6000's motor tuning N311=1 (static self-learning) and N311=2 (dynamic self-learning)?
RNB6000's N311=1 static self-learning learns the resistance and resistance leakage inductance of the motor, and rewrites the internal parameters N306.N308.N309. values, and N311=2 dynamic learning is self-learning of the no-load current and motor mutual inductance of the motor, and rewrites N307.N310.N403, and the parameters of dynamic learning are more comprehensive (it is recommended to use the method of dynamic learning).
9. How to set the analog output of RNB6000 inverter 0-10VDC, 0-20MA and 4-20MA?
THE RNB6000 CAN OUTPUT 0-10VDC AND 0-20MA/4-20MA OUTPUT SIGNALS EXTERNALLY, AND THE HARDWARE PART IS SELECTED BY TWO DIP SWITCHES ON AM1 AND AM2 ON THE MOTHERBOARD (CURRENT/VOLTAGE IS SELECTED), AND THEN THE 0-20MA OUTPUT IS SET TO 0% BY PARAMETER N226 (AM1 CHANNEL) N228 (AM2 CHANNEL). 4-20MA OUTPUT: 25%.
10. How to complete heavy-duty control (vector control) of RNB6000-type inverter.
To complete the vector control, you need to correctly input the parameters on the motor (motor current, speed, number of pole pairs), and then put N311=2 (dynamic self-learning) after input, and then take the empty motor, start (inverter start learning) to identify the motor parameters, after learning, and then N008=4 can be.
11. How many relay dry contact outputs are supplied to the RNB6000 inverter?
The RNB6000 type is supplied with two relay dry contact outputs, which are 11.21 (NO point), 01.02.03 (normally open, normally closed) outputs, and one transistor output.
|
More on that
|
Germany core control appeared at the China International Industry Fair
It is human beings who have always been committed to making human-computer interaction safer, easier to use, and more efficient, which has made collaborative robots gradually become the main stream of shopping malls.
It is precisely because of the vigorous development of the collaborative robot industry that Synapticon Gmb ...
|
|
Indicator of Reynolds inverter cabinet wiring
Voltage level: The voltage level should match the voltage level of the power supply and motor to ensure electrical safety and normal operation of the equipment.
Current level: The current level should match the rated current of the motor to ensure electrical safety and normal operation of the equipment.
Cable Specification: Cable ...
|
|
Reynolds inverter E.oC3 constant speed operation overcurrent fault solution
Reynolds inverter RNB1000 series E.oC3 constant speed operation overcurrent fault solution
Reynolds inverter fault codes:
E.oC3
Reynolds inverter fault phenomenon/type:
Constant speed operation overcurrent
Possible causes of Reynolds inverter failure:
...
|
|
Classification of Reynolds inverter types
1. Classified according to the input voltage level
According to the input voltage level, the inverter can be divided into low-voltage inverter and high-voltage inverter, and the low-voltage inverter is common in China with single-phase 220 V inverter, three-phase 220 V inverter, and i-phase 380 V inverter. High-voltage inverters are commonly used in 6 kV, 10 kV transformers.
|
|
The frequency of the frequency converter is given in a given way
The first way to use the inverter is to change the output frequency to achieve the controllability of the motor speed, so do you know what steps to complete the output frequency controllability? One of the first and foremost key points is how to complete the change of the frequency signal supplied by the inverter equipment.
|
|
Water pump inverter pressure adjustment method - Reynolds
Water pump inverter pressure conditioning steps: 1. Open PID closed-loop control; 2. Close the pressure circuit; 3. Set the pressure feedback and set the given pressure; When the pump speed is changed, the outlet pressure can be changed. Adjust the operating frequency of the VFD. The higher the frequency, the higher the pump speed and the higher the pressure. About ...
|
|
Rated current analysis of inverter leakage circuit breaker
The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will occur, if you want to install a general leakage disconnect switch on the primary side of the inverter, it is recommended to select a sensitivity current of more than 200mA for each inverter and the action time is 0.1 seconds ...
|
|
Inverter control loop wiring taboo - Reynolds
1. The wires laid out in the inverter control circuit should be separated from the main circuit cable (power line), so as to avoid the harmonic disturbance components on the side of the main circuit of the inverter from polluting the inverter control circuit;
2. Due to the faulty signal of the inverter and ...
|
|
Advantages of the inverter vector control system - Reynolds
Dynamic "fast response" DC motors are rectified constrained and excessively high di/dt is not allowed. The asynchronous motor is only constrained by the capacity of the inverter, and the multiple of the forced current can be very high, so the speed echoes quickly, generally reaching the millisecond level, which has surpassed the DC motor in terms of speed.
At low frequencies ...
|
|
The Reynolds SVG series was successfully completed
More than 40 sets of RNSVG series low-voltage power generator sets and RNZB series high-voltage reactive power automatic compensation devices designed and produced by Reynolds have been successfully completed and will be delivered in the near future.
This product is owned by Shanghai Reynolds ...
|
|
The difference between frequency converter and power saver - Reynolds
Many people don't have a clear idea of the detailed differences and uses of AC converters and power savers. Power savers are generally divided into lighting appliances and power savers. Using high-voltage filtering and energy absorption skills, it automatically absorbs the energy of the reverse potential of high-voltage power equipment, and continuously feeds back ...
|
|
Reynolds soft starter features:
The Reynolds soft engine is a new type of software launcher that can assist users in quickly launching and closing the computer system. It was developed by Reynolds and its main function is to provide a fast, safe and reliable software launcher that can assist users in quickly launching and closing ...
|
|
Inverter maintenance power-on test instructions - Reynolds
First, the inverter is not repaired and the power test is tested
(1) Inverter repair test rectifier circuit
At the two ends of the inverter to detect the internal DC power supply, P and N ends, adjust the multimeter to the resistance RX10 gear, the red watch pen is connected to the P end, and the black watch pen is connected to R, S, T, and there are tens of ohms under normal conditions.
|
|
Inverter dust handling – Reynolds inverters
1. Plan a special inverter room: When the power of the inverter used is large or the number is large, a special inverter room can be planned. The doors, windows and cable holes in the room should be sealed to prevent dust from entering; It is necessary to plan air filtration equipment and circulation channels to adhere to the normal circulation of indoor air ...
|
|
Reynolds inverter overhaul process
1) Query and query fault phenomena. The fault phenomenon of the inverter is varied, for example, the same type of problem may have different problem phenomena, and different types of problems may have the same kind of problem, which brings difficulties to find the problem. However, the problem phenomenon is the fundamental basis for repairing the inverter ...
|
|
Inverter starts the overload adjustment parameter - Reynolds
Motor overload: There is no need to set overload maintenance parameters in frequency conversion.
The inverter generally acquiesces to the motor overload maintenance based on the motor power. Generally, it is 1.2 times and 60 seconds will report an overload failure. The overload factor is not the same for different frequency converters.
...
|
|
Reynolds inverter power selection
The system power is equal to the product of the power of a general-purpose inverter and the power of the motor. As long as both work efficiently, the system power will be higher. From the perspective of power, when choosing VFD power, you should pay attention to the following points:
VFD ...
|
|
Precautions for multiple motors in one inverter - Reynolds
Equipment selection
1. Inverter selection. When it comes to sizing, the first thing to consider is the operating conditions – whether one or more motors should be started or stopped at any time during the operation of the inverter.
If the motor does not need to be started at any time during the operation of the inverter, it may only be stopped or ...
|
|
Misunderstanding of inverter control loop wiring - Reynolds
1. The wires of the inverter control circuit should be strictly distinguished from the main circuit cable (power line) and placed separately. This effectively prevents the inverter's control circuit from being disturbed by harmonics in the inverter's main circuit.
2. To separate the connection of the inverter from the terminals or contacts of other control circuits, ...
|
|
Methods and steps of frequency conversion speed regulation - Reynolds
Frequency conversion speed regulation is to change the power supply frequency through the frequency converter, and then adjust the motor speed to improve the operation efficiency of the electric drive system. Depending on the current, VFDs can be divided into AC-DC-AC type and AC-AC type. At present, the most widely used in China is the AC-DC-AC type.
...
|
|