1. The pressure of Delixi inverter system is unstable and simple vibration?
Answer: The pressure of the system is unstable, which may be due to the following reasons:
A. There is a problem with the direction of the pressure of the pressure sensor collection system, and the pressure collection point is too close to the water outlet of the water pump, and the pressure of the pipeline is too affected by the water outlet speed. The pressure value fed back to the controller then rises and falls, forming the vibration of the system.
B. In addition, assuming that the system adopts the method of a pressure tank, and the pressure collection point is selected on the pressure tank, the vibration of the system may also be formed. Because the air itself has a certain elasticity, and the solubility pressure of the gas in the water changes, there is a certain time difference between the water pumped out and the pressure transmitted through the gas, and then the system vibrates.
C. The acceleration and deceleration time of the controller and the inverter do not match the power of the pump motor. In general, the higher the power, the longer the acceleration and deceleration time. For this parameter, the user can select several more data for experimentation. For example, 15KW is generally between 10 and 20 seconds.
2. Delixi inverter small pump starts and stops too frequently?
Answer: In the system, the 11th parameter in the parameters of the controller, that is, the abort pressure error of the small pump is too small. After all the main pumps have been switched off, the small pump starts when the operating pressure of the system falls below the set pressure. As the system pressure rises, the practical pressure of the system is higher than the sum of the set pressure and the abort pressure error of the small pump, and the small pump is shut down by the system. Therefore, the solution to the problem is to increase this parameter to a certain value.
3. The analog output of Delixi inverter is abnormal, and the operating frequency of the inverter is inconsistent with the output of the controller?
A: First and foremost, you should determine what hardware is going wrong. Make the controller enter the manual debugging state, and use a multimeter to measure the analog output values corresponding to the 0Hz and 50Hz output of the controller. Assuming that the analog output value of the manipulator is greater than 30mV at 0Hz, or less than the voltage value calibrated by parameter 5 of the manipulator at 50Hz, it is clear that there is a problem with the output of the manipulator. There are several situations here:
A. Assuming that the output remains unchanged as the frequency of the controller changes, the analog output circuit of the controller is damaged. B. Assuming that the analog output value is also changed, but cannot reach the * large value, it can be solved by the VR3 potentiometer in the small window of the conditioning controller.
Secondly, assuming that the output value of the controller is normal, when the output of the controller reaches the maximum value, the inverter cannot reach 50Hz, which clarifies that there is a problem with the set value of the inverter, and the frequency gain of the inverter can be adjusted.
4. When the pump of Delixi inverter is switched, the output of the inverter is not zero, why?
Answer: The user should make sure that the controller connects all the control lines to the inverter, and when the pump switches the action, the controller will give the inverter a gliding stop signal, that is, the EMG signal. Some users did not connect the EMG signal line, which directly led to the above situation. This kind of phenomenon should be stopped, otherwise, the inverter will be simply damaged. Assuming that there is an EMG signal line, please double-check that the wiring is secure. After making sure that there is no line fault, use a multimeter to check whether the EMG of the controller has output. Assuming that there is no output of the EMG signal when the controller is switching, it is clarified that the controller is the problem.
5. How to connect the anti-disturbance wiring of Delixi inverter controller and inverter?
Answer: In order to prevent the control signal lines of the controller and frequency converter from being disturbed by the space electromagnetic field, the outer layer of these control signal lines can be connected with shielded wires to improve the anti-interference ability of the system. This kind of wiring must be noted, and only one point can be selected for the grounding point of the shield. Whether it's on the side of the controller or on the side of the inverter. In this way, the anti-disturbance capacity of the progressive system is ensured. Assuming that the shield wire is grounded at both ends, the potential difference will be generated on the shield wire, which will not only not improve the anti-interference ability of the system, but will aggravate the disturbance of the outside world to the controller.
6. How to solve the problem of data running away from the inverter controller of Delixi, or the data is occasionally incorrect?
A: This condition is caused by severe disturbance of the manipulator. Often, the operating environment of the controller is relatively harsh, and the disturbing signals come from many sources. After correcting the condition or parameters of the controller, the user must turn the black keyboard in the small window of the controller to determine the direction of the switch to LOCK. In this way, not only does it prevent others from inadvertently correcting the parameters, but it also ensures that the system data does not run away. Assuming that the data is occasionally abnormal, the manipulator can actively run without stopping, and the system stability pressure has not changed, the manipulator can take the initiative to read the original data back at this moment. Assuming that the controller is no longer working normally, the user can disconnect the power supply of the controller, and then turn on the machine from the beginning after a while, and the system will resume normal operation. Suppose the user forgets to make sure that the keyboard determines the switch and sets the data to be overwritten, then the user needs to set the system parameters from scratch. After the setting is complete, pay attention to the switch.
7. The contactor of the Delixi inverter control motor has no action, and the motor does not start?
Answer: First of all, check the output status of the controller reflected by the controller panel, and you can compare the setting and operation indication status of the 7 pumps on the panel described in the controller clarification book. Assuming that there is an output of the pump indication status on the panel corresponding to the non-action motor, the user should first check whether the external contactor wiring and the relay logic of the contactor are correct. Assuming that there is no problem, then use a multimeter to measure the output of the corresponding relay of the controller, and assume that the relay does not output a closed switching signal, and clarify that there is a problem with the relay output of the controller. Assuming that the corresponding pump indicated on the panel does not have an output indication, please check the parameter settings of the controller and check whether the corresponding pump is set to the ON state.
|
More on that
|
Switching power supply FAQ - Delixi
1. The safety wire is blown off
In a general environment, a blown safety wire indicates that there is a problem with the internal wiring of the power supply. Because the power supply is operated in the shape of high voltage and high current, the fluctuation of the grid voltage and the surge city cause the current in the power supply to increase suddenly and cause the safety wire to be blown off. The focus should be on checking the power ...
|
|
The difference between Delixi voltage regulator SBW and SJW
What is the difference between Delixi voltage regulator SBW and SJW, which is better?
Customer Question:
I maintain an uninterruptible power supply and a computer server, and the whole community shares a transformer, so the voltage fluctuation may be greater during the day and at night.
|
|
How to select Delixi voltage regulator
1. For pure resistive loads such as incandescent lamps, resistance wires, electric furnaces and other equipment, the power of the voltage regulator should be 1.5 times the power of the load equipment - 2 times, for example, if your electric furnace is about 250W, you can choose a voltage regulator with a power of 500W.
2. Rational, ...
|
|
Why use optocouplers in circuits - Delixi
Requirements for electrical barriers. Between A and B circuits, signal transmission is required, but because of the disparity between the power supply levels of the two circuits, one is hundreds of volts, and the other is only a few volts; Two very different power supply systems, unable to share the power supply;
...
|
|
Delixi inverter selection
1. According to the load type, confirm the type of inverter: different load types, speed requirements and power size, and the need to choose different types of Delixi inverters. Therefore, it is necessary to understand in detail the type of motor load to be controlled to find the most suitable type.
...
|
|
Delixi contactor selection considerations
Electrical safety is not a trivial matter in modern society. Delixi communication contactors are used in homes, public places or commercial buildings. As a power device, its importance is self-evident. If you buy an unsuitable communication contactor, it will appear briefly in the future application process ...
|
|
Delixi CDI-EM60 inverter technical characteristics
Delixi CDI-EM60 inverter has optimized open-loop vector control, V/F control, stable function, optimized function, standard configuration of common users, but also expand multi-channel I/O interface and communication function, is a delicate type of small power type.
...
|
|
Analysis of common problems of inverter - Delixi
1. Why does the maintenance function of the inverter operate when the clutch is connected to the load?
When the load is connected with a clutch, at the moment of connection, the motor changes sharply from the no-load condition to the area with a large slip rate, and the large current flowing through causes the inverter to trip over the current and cannot work.
...
|
|
Delixi low-voltage inverter selection method
The selection of inverter is indeed very important, because if the selection is not suitable, it will cause a waste of time and money, and at worst it will cause production incidents and personnel damage.
First of all, according to the classification and selection of the inverter
1. Inverters can be divided into general-purpose inverters and special inverters.
...
|
|
Delixi takes you to understand the knowledge of resistance and resistivity
1. Resistance
Indicates the magnitude of the conductor's resistance to the current.
Conversion between units of resistance: 1KΩ=1000Ω
R indicates the resistance, and the unit of resistance is: ohms (Ω)
R=U/I
U--- voltage (unit: volts V)
I--- current (in ...
|
|
Delixi inverter constant pressure variable frequency water supply system control problem
1. The pressure of Delixi inverter system is unstable and easy to vibrate?
Answer: The pressure of the system is unstable, which may be due to the following reasons:
A. There is a problem with the direction of the pressure of the pressure sensor acquisition system, and the pressure collection point is too close to the water outlet of the water pump, and the pressure of the pipeline is affected by the water outlet ...
|
|
The difference between Delixi LDO and DC-DC
The so-called DC-DC is actually DC to DC voltage, of course, LDO is also a kind of DC-DC, and only LDO can only achieve step-down.
The general DC-DC is mainly converted from DC to AC communication through the self-excited vibration circuit inside, so the external inductance and capacitor are required to achieve LC vibration (and LDO is only ...
|
|
LDO low dropout linear regulator features - Delixi
Since it is used as a low dropout voltage regulator, the first feature is the extremely low input and output voltage difference, and secondly, it also has stable voltage output, low noise, small ripple, small size, and simple peripheral circuits. If an LDO regulator is used when planning the circuit, the general requirement is at least ...
|
|
The reason for the existence of Delixi voltage regulator
In general, every electrical device or device is designed for a wide range of input voltages. Depending on the sensitivity, the operating scale of the device is limited to a specific value, for example, some devices can tolerate ±10% of the rated voltage, while others can tolerate ±5% or less.
...
|
|
Servo motor failure and analysis - Delixi
1. Motor encoder alarm
1. The cause of the failure
(1) Wrong wiring;
(2) electromagnetic disturbance;
(3) Encoder hardware damage caused by mechanical vibration;
(4) Pollution caused by the on-site environment.
2 ...
|
|
What are the advantages and disadvantages of dry and oil regulators? - Delixi
Oil Regulator: Also known as non-contact inductive regulator or intelligent non-contact regulator (only the name of the company's own selling point).
Forte:
1. No contact, no protection, impact resistance (especially instantaneous impact, 2 times of normal.) The reason for this is the slow response, which ...
|
|
Delixi bearing rust causes
1. The instantaneous high temperature in the grinding process will make the surface of the workpiece reach a molten state, and the steel surface will react with the oxygen in the air chemically, which will form a very thin (20-30nm) iron oxide film.
|
|
Delixi circuit breaker P number selection points
As far as miniature circuit breakers are concerned, 1P+N, 1P, and 2P are generally used as the on-off control of single-phase electrical appliances, but the functions are different. In order to facilitate the user's selection and difference, the difference of the P number of circuit breakers and the selection method are briefly analyzed.
...
|
|
Delixi CDI-EM60 series inverter application
Delixi CDI-EM60 series inverter is a high-performance communication motor drive, suitable for a variety of industrial use. This kind of inverter has a variety of advantages, such as ** rate, low harmonic distortion, low noise, low oscillation, etc.
Delixi CDI-EM60 series inverter can be used in a variety of ...
|
|
Delixi voltage regulator fault performance and elimination
Regulator problem 1: The regulator cannot be started
Reason: Whether the phase sequence of the input power cord has been changed, and the air switch in the machine is not turned on or broken.
Repair methods: 1. Swap the two power supply wires arbitrarily or check whether the power supply line is correct; 2. Close or replace the switch.
Voltage Regulator ...
|
|