1. Omron PLC cannot be connected to the computer
There are two reasons why the PLC and the computer cannot be connected: hardware and software.
The hardware reasons are: the interface type does not match (such as USB, RS232, RS422, RS485, CAN, etc., both sides should be the same.) If it is different, the corresponding converter should be used), and the connection line is open, short, or wrong.
The reasons for the software are: inconsistent communication settings (including baud rate, data bits, check bits, stop bits, etc., both sides must be consistent), communication protocol mismatch (just like Chinese speaking Chinese to foreigners who do not understand Chinese).
2. The Omron PLC network cable cannot be connected
Assume that the IP address of the computer network card: 192.168.59.54. (1) Set the NODE number of the CJ1W/CS1W-ETN21 module: NODE=0×161 +3 ×160=3 (2) Set the module parameters: CX-Programmer software is connected to the PLC through the serial port, the PLC switches to the programming mode, double-clicks the IO table and unit settings, and selects Create in the options drop-down menu, prompting the initialization bus, and then the CJ1W-ETN21 module appears in the rack. Double-click the CJ1W-ETN21 module, and the unit settings appear. Set the IP address of the module to 192.168.59.03 and the subnet mask to 255.255.255.0. Note: The last segment of the IP of the CJ1W-ETN21 module is the same as the NODE number by default. Click Transfer (PC to Unit).
(3) Create a new project in CX-Programmer software, select Ethernet as network type, and click Settings after network type.
In the network, the FINS source network and destination network number are defaulted to 00, and the node number is set to 3. In the driver, the IP address is set to 192.168.59.03, and the port number is 9600 by default.
(4) CX-Programmer software clicks online, and the communication is completed.
3. Omron PLC cannot be connected to the computer
Answer: If you don't have MODEN installed on the motherboard, the main reason is that your motherboard drivers are not installed properly or the drivers are not installed in order.
Install the motherboard driver first, then the graphics card driver, and then the sound card and network card.
If not, install it in the order above, if it is already installed, you have to reinstall the system and install it again in the order above.
If there is a moden installed on the motherboard, this is it. In the early days, the transmission rate of hardware devices used for Internet access was about 56K per minute. Now it's less useful. This situation may occur when there is a modem in the computer case. Since you don't have a driver installed, the computer recognizes the modem as a PCI Simple Communication Controller.
4. Omron PLC USB cannot be connected to PLC
Reasons and solutions for Omron's PLC not connecting online:
There are two reasons why the PLC and the computer cannot be connected: hardware and software.
The hardware reasons are: the interface type does not match (such as USB, RS232, RS422, RS485, CAN, etc., both sides should be the same.) If it is different, the corresponding converter should be used), and the connection line is open, short, or wrong.
Software reasons are: inconsistent communication settings (including baud rate, data bits, check bits, stop bits, etc., both sides must be consistent), communication protocol mismatch (just like Chinese speaking Chinese to foreigners who do not understand Chinese)
5. Omron PLC can't connect to the computer solution
Configuration software is to choose the driver,CP1L with MCGS driver with serial port to choose "Omron FINS serial port",Configuration king doesn't know how to choose to read the data,First of all, you have to see whether the driver selection is correct,There are also serial port attributes baud rate、Check bit、PLC station number and the like,It must be correct I used a lot of configuration software and touch screen,As long as the setting is correct, I have not found that it cannot be connected
6. Omron PLC does not communicate
To rule out whether the touch screen is broken, or PLC problems, if you don't know how to operate, you can send it to the Pengkong industrial control equipment maintenance center.
This problem generally considers the following aspects: 1. Whether the wire (communication line) is correct can be measured with a multimeter. 2. Whether the communication parameter settings are correct 3. Consider whether the serial port is not destroyed, I have encountered, the new touch screen, the serial port is broken, and finally the serial port is changed.
7. Omron PLC cannot communicate with a computer
I think maybe your port number is wrong, you connect the communication line to the PLC first, and then click on the port number in my computer properties, the device manager, and see what it is. Then change the port number in the communication settings in the PLC software to that number, and it's OK.
|
More on that
|
How Omron PLC works and what are the advantages
Omron PLC is a compact PLC with complete functions that provides highly additional machine control for industry-leading conveying and distribution control. It also has the ability to upgrade through a variety of advanced built-in boards, large program capacities and memory units for efficient software development in the Windows environment.
|
|
Recommended selection of Omron's commonly used products
Omron's recommended product models today:
K8DS is a triple opposite missing sequential appliance
The inverse lacks sequential electrical appliances
Three-phase voltage + inverted phase lack sequential electrical appliances
Three-phase unbalanced + inverted lack of sequential electrical appliances
Three-phase undervoltage + inverted inverted missing sequential electric
Three-phase voltage + three-phase ...
|
|
Features of Omron PLC programming
Programming features of Omron PLC.
Graphical instruction structure: The program is represented graphically, and the instructions are composed of different graphic symbols, which are easy to understand and remember. The software developers of the system have compiled the individual operating functions required for industrial control into symbolic graphics that the user can use according to the ...
|
|
Common problems and solutions in the maintenance process of Omron PLC
1. CPU abnormality:
When the CPU is abnormally alarmed, check all the devices connected to the internal bus of the CPU unit. The specific method is to replace the units that may have problems in turn, find out the problem units, and deal with them accordingly
2. Memory abnormality:
Memory anomaly ...
|
|
Omron's digital × low-carbon solutions were unveiled in the industrial automation exhibition area
The 5th China International Import Expo opened in Shanghai. Based on the ever-evolving manufacturing concept "i-Automation!" The digital and low-carbon solutions created were presented to the audience on the heavyweight platform of the Expo.
At present, the curtain of global carbon neutrality has opened, and the ...
|
|
Introduction to the classification of Omron relay switch contacts
1.A contacts
A contact is a contact in which the two contact terminals are separated (OFF) when the switch is not operated, and closed (ON) when the switch is operated. If you want to start the load by operating the switch, you can use the A contact. A circuit is a circuit that uses a contact without operating the switch (pressing ...
|
|
What are the common faults of Omron PLC?
1. CPU abnormality: When the CPU abnormality alarms, check the devices connected to the internal bus of the CPU unit. The specific method is to replace the units that may cause failures in turn, find out the faulty units, and deal with them accordingly.
2. Memory abnormality: When the memory is abnormal alarm, if it is a program ...
|
|
What is the main role of Omron micro switches in household appliances?
There are 3 types of micro switches, which perfectly match the precise control needs of household appliances
Micro switch refers to a contact mechanism with a small contact spacing and a snap-action mechanism, a contact mechanism that carries out the switch action with a specified stroke and a specified force, covered with a shell, and a drive rod on its outside, ...
|
|
Omron announces the opening of its California Robotics Headquarters
March 12, 2020 - Omron Corporation announces the opening of its Robotics and Safety Automation business headquarters in Pleasanton, California. The company has invested $10 million in its 128,000-square-foot facility to design, develop, test and manufacture robots and safe self-propelled robots.
|
|
【Omron industry case】Predictive maintenance of smoke machine in automobile welding workshop
Process introduction
Automobile welding is the second of the four major processes in vehicle production, which mainly assembles stamped body components into a complete body. In the welding process, spot welding and arc welding of robots are the mainstay, and there will be a station for visual inspection of the welding status in the middle.
Make...
|
|
Omron PLC--C200HE/C200HG/C200HX series product model
1. C200HE-CPU11-E CPU unit memory 3.2K maximum I/O points: 640 points
2. C200HE-CPU32-E CPU unit memory 7.2K maximum I/O points: 880 points
3. C200HE-CPU42-E CPU unit RAM 7.2K Max I/O points: 880 points with RS232C ...
|
|
FAQs on Omron PLC
1.How to install the USB driver of CP1H?
The computer is connected to CP1H (powered on) through a USB cable, and the PC will automatically prompt to find the new hardware and prompt to install the driver.
2.The built-in USB port of CP1H can be used ...
|
|
Omron C series PLC models and their main meanings
Omron C series P-type machines have three types: basic, extended, and special-purpose, with a total of 4 types of CPU hosts, 6 types of I/O short-range expansion machines, and a variety of dedicated units.
1. The basic unit (also known as the host) has a CPU
Among them, C stands for the series code; (1) Table ...
|
|
Analysis of the location and cause of Omron PLC failure
1. External equipment failure. Such faults come from external devices such as various sensors, switches, actuators, and loads. The failure of this part of the equipment will directly affect the control function of the system. This type of failure is usually caused by the quality and longevity of the equipment itself.
2. System failure ...
|
|
Where did the cable with screws at the bottom of the Omron micro switch come from?
Different models of Omron micro switches may have different wiring methods. Generally speaking, the wire with screws at the bottom of the Omron micro switch is usually the contact used to connect the switch, which needs to be connected to an external circuit.
The wiring steps are as follows:
1. Confirm the bottom of the switch ...
|
|
The working principle and purpose of Omron relays
How it works
Add a certain voltage at both ends of the coil, a certain current will flow through the coil, thus producing an electromagnetic effect, and the armature will overcome the tensile force of the return spring under the action of electromagnetic force attraction and attract to the core, thereby driving the dynamic contact and static contact (normally open contact) of the armature ...
|
|
Selection rules for Omron relays
1. Coil voltage: also known as input voltage, used to control the contact on/off, with AC24V, DC24V, AC220V and other specifications
2. Contact capacity: the voltage and current of the load
3. Contact structure: 2C (double-pole double-throw), 4C (four-pole double-throw), 1A, 1B, etc
4. Load type ...
|
|
What should Omron PLC pay attention to when selecting a model
Omron PLC is a compact PLC with perfect functions, which can provide high value-added machine control for industry-leading conveying and decentralized control; It also has the ability to upgrade through a variety of advanced built-in boards, large program capacity and memory units for efficient software development in the Windows environment ...
|
|
Precautions when using Omron switches
One. Omron switch in daily use, basically need to be used every day, when using Omron switch, you need to pay attention not to wet hand operation, to avoid electric shock accidents, and secondly, if the water vapor once invaded the inside of the switch line, it will cause internal damage to the switch, than ...
|
|
Routine maintenance methods of Omron relays
1. In the operation of Omron relay, if there is an abnormal sound or other abnormal conditions, the operation should be terminated first, and the skilled and professional repair staff should be notified to repair, and the operation can be resumed after the common fault is cleared.
2. In the whole process of maintenance, check the spring ...
|
|