Low-voltage electrical faults and maintenance methods - Mitsubishi

Create Date: 2024-8-30 12:03:23|Source: Mitsubishi Electric/Mitsubishi Electric

In the process of operation, low-voltage electrical appliances will present problems due to improper use or long-term operation of aging components, and there are many kinds of problems, and the common problems are analyzed and dealt with.

1. Contact problems and repairs

The contact is the primary component of the low-voltage switching coupon, and common problems are overheating, wear and fusion welding.

1. Contact overheating: Contact overheating refers to the cause of contact overheating or burns caused by the heat generation of the working contact exceeding the additional temperature and the treatment method

(I)) The contact pressure should be adjusted for overheating caused by the lack of contact pressure, usually to replace the tension spring pressure tissue. The measurement method is shown in Fig

(2) If the contact is poorly touched, the contact surface is oily or uneven, or the contact surface is oxidized, the contact can be cleaned up, and gasoline or knives can be used to remove it.

(3) If the operating frequency is too high or the operating current is too large, first check whether the power supply voltage is in the rated voltage scale and whether the load is overloaded, and then exchange the electrical appliances with larger capacity as needed. Electrical appliances with large capacity should be replaced or degraded due to ambient temperature or used in a closed environment.

2. Excessive wear of contacts, there are two types of contact wear damage, namely electric grinding and mechanical wear, which should be replaced when worn to a certain extent. Causes of excessive wear and tear and cleaning methods;

(1) Excessive wear caused by the non-synchronization of three-phase contacts can be adjusted to synchronize and replace the contacts.

(2) If it is formed by a short circuit on the load side, it is necessary to clean up the short circuit.

(3) If the overtravel is too small and the capacity is lacking from time to time when the equipment is selected, it should be replaced with a large capacity equipment.

3. Contact fusion welding Contact fusion welding refers to the phenomenon that the dynamic contact touch surface is welded together after melting. Causes of contact soldering and cleaning methods:

(1) If the operation frequency is too high or overloaded, the equipment should be selected from scratch according to the operating conditions.

(2) If the contact pressure is too small, the tension spring pressure should be adjusted or a new pressure tissue should be replaced.

(3) If there is a metal foreign matter on the surface of the contact, replace the contact with a new one.

(4) If the voltage of the operating circuit is too low or the contact is stuck in the direction of the just touch, the operating voltage should be improved to eliminate the jamming phenomenon.

                               Low-voltage electrical faults and maintenance methods - Mitsubishi

2. Problems and repairs of electromagnetic structure

Electromagnetic structure is an important part of low-voltage electrical appliances, playing the role of energy conversion and operation movement, common problems are loud noise, can not be suction or lack of suction, do not release or slow release, coil overheating or burning, etc.

1. The causes and treatment methods of large noise;

(1)) If the power supply voltage is low, the power supply voltage should be improved.

(2) If the armature is in contact with the iron core and there is oil, dust or rust on the iron core, the touch surface should be cleaned up.

(3) If the touch surface of the iron core is caused by excessive wear and unevenness, the iron core should be replaced.

(4) If the parts are skewed or formed by mechanical jamming, the relevant parts should be adjusted or cleaned up from the beginning.

(5) If the contact pressure is too large, the contact tension spring pressure structure should be adjusted.

(6) If the short-circuit ring is damaged, replace the iron core or short-circuit ring.

2. After the armature cannot be sucked or the suction power is lacking, the reasons and treatment methods for the armature cannot be sucked or the suction power is lacking:

(1)) If the power supply voltage of the operation circuit is too low, or the wire is broken, the coil inlet and outlet lines fall and the wiring is faulty, the power supply voltage should be increased and the line should be cleaned up.

(2) If the power supply voltage is too low or shakes too much, or the movable part is jammed, the shaft is rusty, skewed, etc., the power supply voltage should be adjusted and the fault of the movable part should be removed.

(3) If the contact pressure is too large or the overtravel is too large, the pressure organization should be adjusted or replaced.

3. When the armature is not released or the release is slow, when the power supply is disconnected, the armature is not released or the armature is released slowly, and the reasons and treatment methods are presented:

(1) If the pressure of the contact tension spring is too small, the pressure organization should be adjusted or replaced.

(2) If the contact is formed by fusion welding, the cause of fusion welding should be found and the contact should be replaced.

(3) If the movable parts are jammed or the shaft is rusted or skewed, the relevant parts should be adjusted or the shaft should be replaced. If there is oil stain on the end face of the iron core or the air gap between the end faces disappears, the end face should be cleaned or the repair core should be replaced.

(5) If the reaction tension spring is damaged, the tension spring or the entire reaction force organization should be replaced.

4. Causes of overheating or burnout of the coil during the operation of the coil and the cleaning method of the fault:

(1) If the coil voltage is too high or too low, the power supply voltage or coil voltage should be adjusted.

(2) If the operating frequency is too high or the coil parameters do not meet the requirements, the coil needs to be replaced or the equipment should be selected according to the application conditions.

(3) If the end face of the iron core is uneven and there is a gap between the armature and the iron core, the iron core should be repaired or replaced. If the coil insulation aging is caused by an inter-turn short circuit or a partial short circuit to the ground, a new coil should be replaced.

There will be other faults in the electrical industry, and when the fault analysis and cleaning should be carried out according to the practical phenomenon as much as possible to analyze the causes, sweep them one by one, operate carefully in accordance with the safety requirements, and carry out the power transmission test operation after confirming the correct cleaning and wiring.

More on that
Functional characteristics of Mitsubishi's various series of servo motors Functional characteristics of Mitsubishi's various series of servo motors

Mitsubishi servo motor system series: MR-J2S series, MR-J3 series, MR-ES series, MR-E series. Mitsubishi servo motor MR-J2S series 1. The product also has RS-232 and RS-422 serial communication functions, which can be used by a personal computer equipped with servo setting software.

Introduction to the Mitsubishi PLC encryption process method Introduction to the Mitsubishi PLC encryption process method

The encryption process is as follows: ** Open the serial port for the first time [00000000] IOCTL_SERIAL_SET_BAUD_RATE Baud Rate: 9600 (Set baud rate here) [00000000] IOCTL_SERIAL_SET_LINE_CONTROL StopBits: 1, Parity: Ev ...

PLC troubleshooting method - Mitsubishi PLC troubleshooting method - Mitsubishi

1. If the PLC stops in the middle of some outputs where the output is excited, then look for the signal that caused the next operation (input, timer, line, drum manipulator, etc.). The programmer will show the ON/OFF status of that signal. ...

Mitsubishi inverter heat dissipation causes and countermeasures Mitsubishi inverter heat dissipation causes and countermeasures

1. Whether there is abnormal change in the sound during the operation of the equipment, including whether there is oscillation during the operation of the motor. 2. Whether the ambient temperature of the inverter installation is too high or too low, the working temperature is generally required to be in the range of -10°C - +40°C, and it is better to be about 25°C. ...

The correct maintenance method for Mitsubishi inverters The correct maintenance method for Mitsubishi inverters

Mitsubishi inverter we have to maintain the inverter module frequently, to regularly check the Mitsubishi inverter module, especially the maintenance of the cooling fan, due to the high power of the cooling fan, high speed, in the dusty working environment, simply lead to the radiator exhaust hole blockage, so that the internal electric ...

Precautions for the use of Mitsubishi servo motor with brake Precautions for the use of Mitsubishi servo motor with brake

1. Occasions to choose a servo motor with brakes: The servo motor is mainly loaded through the motor shaft, if the load driven by the motor shaft is in the straight direction, after the whole control system is powered off, the load on the servo motor shaft will be driven to run down under the effect of gravity, so that ...

Mitsubishi FX series PLC master control command Mitsubishi FX series PLC master control command

The FX2N has a total of 27 fundamental logic instructions, including 20 fundamental logic instructions of some sub-series PLCs. Master Control Command (MC/MCR) (1) MC (Master Control Command) for common tandem contacts ...

The difference between the measurement of ordinary motors and inverter motors - Mitsubishi The difference between the measurement of ordinary motors and inverter motors - Mitsubishi

1. The actual output waveform of the inverter is PWM wave, which contains carrier signals in addition to the fundamental wave. The carrier signal frequency is much higher than that of the fundamental wave, and it is a square wave signal, which contains a lot of higher harmonics, and the test system requires a higher sampling frequency and bandwidth. ...

Mitsubishi PLC main maintenance and overhaul content points Mitsubishi PLC main maintenance and overhaul content points

The main content of the protection and maintenance of Mitsubishi PLC Although the failure rate of PLC is very low, the control system composed of PLC can operate stably and reliably for a long time, and it is essential to protect and view it alone. Generally, every six months ...

Mitsubishi PLC control inverter method Mitsubishi PLC control inverter method

1. Mitsubishi PLC's analog signal control inverter Hardware: FX1N, FX2N PLC hosts, equipped with 1 simple FX1N-1DA-BD extended analog output board; or analog input-output hybrid module FX0N-3A; or FX2N-2DA with two outputs; or four outputs ...

Mitsubishi Q series PLC and GX Works2 connection method Mitsubishi Q series PLC and GX Works2 connection method

01 USB connection USB connection requires the device USB driver, generally the device will be actively driven after the installation of GX Works2 software, but at a single time due to anti-virus software or system reasons, or the device may not be available, then we need to manually drive the device to the accounting machine. The specific device method is ...

Mitsubishi servo system failure problem Mitsubishi servo system failure problem

The origin position is incorrect, and the encoder debugs/zeros the bit Replacement bearings, bearing groove wear, rotor cracking, shaft cracking Gear groove wear The magnet bursts steel, the magnet falls, gets stuck and doesn't move Encoder wear, code ...

Mitsubishi tells you what IGBT is Mitsubishi tells you what IGBT is

Mitsubishi Electric IGBT is the English word Insulated Gate Bipolar Transistor, which means insulated gate bipolar transistor in Chinese. Functionally, IGBT is a circuit switch, and the advantage is that it uses electricity.

Mitsubishi inverter FR-A800 series selection Mitsubishi inverter FR-A800 series selection

Q: When will the CS84 series inverter be selected? A: CS80 series inverter belongs to the diversified function of small intelligent inverter, covering excitation control and general flux vector control, the volume is 57% of the same model, very fast, in some general functions can be used in this model ...

Mitsubishi participated in the 4th CIIE to introduce the E-JIT green induction solution Mitsubishi participated in the 4th CIIE to introduce the E-JIT green induction solution

On November 5, 2021, the 4th China International Import Expo was grandly held at the National Convention and Exhibition Center in Shanghai. At the 4th CIIE, Mitsubishi Electric's booth was located in Hall 4.1 of the Technical Equipment Zone of the Convention and Exhibition Center, with an exhibition space of 400 square meters. At Mitsubishi Electric's booth, the high-profile event was ...

Advantages of Mitsubishi Electric fresh air system Advantages of Mitsubishi Electric fresh air system

Mitsubishi Electric's fresh air system realizes indoor ventilation, but of course, we can't just replace the outdoor air into the room, a good fresh air should filter the harmful substances in the air, so that the air entering the room is not only fresh, but also clean and harmless. ...

Mitsubishi PLC keeps the circuit written Mitsubishi PLC keeps the circuit written

There is a very common kind of circuit in Mitsubishi PLC - the persistence circuit. The holding circuit means that when the external input switch is a button, it can press the button through the holding circuit to insist on the output, similar to the self-locking in the electrical diagram. We use Mitsubishi PLC as an example to write a sticking circuit. ...

Anti-interference performance measures of Mitsubishi PLC system Anti-interference performance measures of Mitsubishi PLC system

1. Choose a power supply with excellent performance and press the disturbance introduced by the power grid In the PLC control system, the power supply occupies a very important position. The power grid disturbance series into the PLC control system is mainly through the power supply of the PLC system (such as CPU power supply, I/O power supply, etc.), the power supply of the transmitter and the power supply with P ...

Mitsubishi PLCFX2NCPU plate fault solution Mitsubishi PLCFX2NCPU plate fault solution

Customer's description of the problem: Mitsubishi FX2N-32MR-001, the PLC running light does not light up after powering on, and the alarm light is always on (hardware problem) Inspection and repair: turn on the power supply, power on the PLC, according to the detection process, the PLC is in the POWER...

Mitsubishi servo motor method Mitsubishi servo motor method

1. Torque control: Torque control sets the output torque of the motor shaft through external imitation input or direct address assignment. For example, 10V is equivalent to 5Nm. When the external analog is set to 5V, the output of the motor shaft is 2.5 Nm. If the motor shaft load is less than 2.5 Nm, when the external load is 2.5 N...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top