1. First carry out the no-load test operation of the inverter

First of all, check whether all the wiring of the inverter is correct, do not connect the output of the inverter to the motor, and conduct a no-load test on the inverter first. Carefully read the user manual of the inverter before powering on, understand the relevant functions, settings, and operation methods, and then power on this basis.

There are two intentions of no-load test operation: one is to understand the keyboard and related operation methods through actual operation, such as forward, reverse, abort, etc., and observe the action of the inverter, whether the temperature rise is normal.

The second is to understand the setting and operation method of the relevant functions in combination with other things, and try to see the action state and action process of the fundamental function after setting, such as the setting of rise and fall time. On this basis, look at the signal of the external terminal to control whether the action is normal, such as whether the output frequency of the inverter changes with the given signal when rotating the potentiometer clockwise or changing the frequency to a given current.

                            Whether the inverter can be debugged without load - Delixi


2. No-load test operation of inverter with motor

After the no-load test operation of the inverter is normal, the motor can be connected to the no-load test operation. Before connecting the motor, it is necessary to confirm that the technical indicators of the motor are qualified.

The motor should not be loaded. Then let the inverter drive the motor to roll, and investigate whether it is normal, such as whether the direction of rotation of the motor meets the requirements. Turn the frequency given potentiometer counterclockwise to the left end of 0Hz, then turn on the forward switch (FWD) of the inverter, slowly rotate the potentiometer clockwise, so that the given frequency gradually increases, investigate the rolling situation of the motor, at 50% of the maximum frequency, let the motor roll for a few minutes, and investigate the value of voltage and current, and then let the output frequency of the inverter reach the maximum frequency, then let the motor roll for a few minutes, and investigate the value of voltage and current, and then let the output frequency of the inverter reach the maximum frequency, Let the motor roll for a few more minutes.

Then reduce the output frequency to 75% and 25% of the maximum frequency, let the motor roll for a while, then increase the output frequency, and then disconnect the forward switch (FWD) to see if the motor stops according to the set deceleration time. This process does not require parameterization at all, and it is possible to use the preset parameters of the inverter at the factory.

3. The inverter is operated and debugged with load

Before starting commissioning, check that there are no personnel around the load and no foreign objects on the load before loading and debugging. When debugging, first give a small frequency, investigate whether the load runs smoothly, whether there is abnormal sound in operation, and analyze the reasons if so; Investigate the torque of the inverter, whether the current is abnormal, generally when the inverter is started with load, the current torque is larger, and when it runs to a given frequency, the current torque is relatively stable.

Furthermore, after the external load run-in period, the torque current has a certain amplitude of decline, if the load always reaches the rated value after the inverter is running, it is necessary to judge whether the inverter and the motor are matched with the load, if so, the need to consider replacing the inverter and motor of the larger model in time, so that the control current and torque reach the scale; In addition, according to the load characteristics, set a reasonable acceleration and deceleration time to ensure that the inverter does not report overcurrent during operation and start-up.

More on that
The material of the transformer - Delixi The material of the transformer - Delixi

In view of the regulation and control effect of the transformer in the power system, technicians need to choose the appropriate transformer finishing device operation, so as to play a normal effect. Winding data is the primary problem that transformer devices need to pay attention to, and the effects of devices of different materials are different. Concerning...

Delixi circuit breaker model difference Delixi circuit breaker model difference

CDB1 miniature circuit breaker is a kind of current-limiting high-breaking miniature circuit breaker with double protection of overload and short circuit, which is suitable for AC 50Hz, rated voltage 400V and below, rated current 63A and below circuits, as line overload and short circuit protection, can also be used under normal circumstances.

Characteristics and parameters of industrial molded case circuit breaker - Delixi Characteristics and parameters of industrial molded case circuit breaker - Delixi

1. Extra limit short-circuit breaking can be used for Icu There are two types of breaking capacity targets for circuit breakers: additional limit short-circuit breaking capacity of 4U and additional operating short-circuit breaking capacity Ics. As a characteristic parameter, ICS is not only a brief consideration of the breaking ability of the circuit breaker, but also a breaking purpose.

Delixi voltage regulator working principle Delixi voltage regulator working principle

In Delixi voltage regulator, the voltage correction from and under voltage conditions is performed through two basic operations, namely Oersted and step-down operation. These operations can be switched on and off manually or automatically by electronic circuits. Under voltage conditions, the voltage of the boost operation is increased to the rated voltage.

Delixi spare parts replacement cycle Delixi spare parts replacement cycle

1. Cooling fan (2-3 years) As long as the inverter is in use, the cooling fan has always been running, so the cooling fan is generally a short-service life accessory, generally after the use of the cooling fan for 2-3 years, the bearings, balls, motors, etc. of the fan are seriously worn, and they need to be replaced.

Delixi circuit transformation attention to detail Delixi circuit transformation attention to detail

1. If strong electricity and weak electricity are to be separated by a long distance from the horizon walking line, the interval should generally exceed 30 cm to prevent disturbance and be interspersed with each other. 2. In order to facilitate the future line change, the PVC pipe must be cut down and straightened as much as possible.

The circuit breaker is set in accordance with the principle - Delixi circuit breaker The circuit breaker is set in accordance with the principle - Delixi circuit breaker

1. When the main circuit is equipped with a total leakage maintainer, the main barrier switch, the branch barrier switch, the main circuit breaker, the branch circuit breaker or the main fuse, and the shunt fuse should also be installed. When the total leakage maintainer is a leakage circuit breaker with short-circuit, overload, and leakage maintenance functions, it can not be ...

Delixi switching regulator basics Delixi switching regulator basics

1. What is a switching regulator? Switching regulator, English (regulatior), some people call it a regulator, a voltage regulator source. To achieve voltage regulation, it is necessary to control the system (negative feedback), from the theory of automatic control, we know that when the voltage rises, it is lowered by negative feedback, ...

Delixi relays and precautions Delixi relays and precautions

Quickness: It means that the maintenance device should be able to remove the short circuit as soon as possible, and its intention is to improve the stability of the system, reduce the damage to the peak equipment and lines, reduce the scope of the process, and improve the effect of active overlapping room and standby power supply or standby equipment active investment. ...

Low dropout linear regulator design power supply precautions - Delixi Low dropout linear regulator design power supply precautions - Delixi

1. Pay attention to the maximum value of output current: this is a very critical parameter, the current used exceeds the maximum output current of LDO, then the voltage is unstable, and the system will fail. LDO limit parameters: The output current is considered according to the 2/3 criterion. The cost of the whole system ...

The reason for the whitening of the copper bar installed on the Delixi plastic case circuit breaker The reason for the whitening of the copper bar installed on the Delixi plastic case circuit breaker

In the project, because of the 630 A circuit breaker wiring bar in the 500 kVA box-type transformer, see the second circuit breaker and circuit breaker on the left in the figure. The temperature of this corresponding region is significantly higher than that of the other two corresponding regions, and the other two phases are also hot, and the copper bars of this phase have turned white. There is no induction Deli ...

Low dropout linear regulator parameters and advantages and disadvantages - Delixi Low dropout linear regulator parameters and advantages and disadvantages - Delixi

Grounding current, also become quiescent current, load regulation (the smaller this value, the stronger the LDO can press the load) linear regulation (the smaller, the less influence of the input voltage on the output voltage, the better the LDO function) power supply ratio (PSSR), reflecting the Delixi LDO to the interference signal ...

Delixi launched a new 6 series CDW6i frame circuit breaker Delixi launched a new 6 series CDW6i frame circuit breaker

At the end of July, Delixi Electric launched a new 6 series CDW6i structural circuit breaker and a number of industrial control accessories. The new 6 series CDW6i structural circuit breaker has complete product specifications, which can provide professional customers with more choices, excellent functions, and ...

Delixi circuit breaker tripper selection and tuning analysis Delixi circuit breaker tripper selection and tuning analysis

Among the objects of circuit breaker maintenance, there are some electrical equipment that generate several times its rated current in a short period of time during the start-up process (1) The setting of the operating current of the instantaneous overcurrent tripper In the circuit breaker maintenance of ...

Delixi circuit breaker protection features Delixi circuit breaker protection features

Quickness: It means that the maintenance device should be able to remove the short-circuit fault as soon as possible, and its purpose is to improve the stability of the system, reduce the damage to the faulty equipment and lines, reduce the scale of the fault, and improve the effect of active reclosing and active investment of standby power supply or standby equipment. Reliability: Refers to ...

Delixi relay maintenance method Delixi relay maintenance method

Relay is a kind of electrical appliance that turns on or off the control circuit according to the change of external input signals, such as electrical quantity (voltage, current) or non-electrical quantity (heat, time, speed, etc.) to complete the control or maintenance mission.

Delixi circuit breaker common model features Delixi circuit breaker common model features

CDB1 miniature circuit breaker is a current-limiting high-breaking miniature circuit breaker with overload and short-circuit maintenance, which is suitable for communication 50Hz, additional voltage 400V and below, additional current 63A and below circuits, as line overload and short circuit maintenance, can also be used under normal circumstances.

Delixi inverter usage Delixi inverter usage

First of all, Delixi inverter has a very high control accuracy. It uses advanced electronic skills and digital control skills, and can control the speed, torque, and current of the motor with a high degree of control. Together, the controller of Delixi inverter also has a high overload capacity and strong ...

Delixi DZ47LE C40 air switch introduction Delixi DZ47LE C40 air switch introduction

The general leakage circuit breaker is wired using the principle of outgoing wire under the progressive line, only need to distinguish the phase line and the zero line, between, the zero line is marked with N on the right, and the incoming and outgoing lines are the same. Delixi DZ47LE C40 ...

Delixi anti-leakage is different from ordinary circuit breakers Delixi anti-leakage is different from ordinary circuit breakers

Circuit breaker refers to a switchgear that can close, carry and break the current under normal circuit conditions, and can close, carry and break the current under abnormal circuit conditions within a specified time. Circuit breakers can be used to distribute electrical energy, infrequently start asynchronous motors, and ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top