The basic requirements of VFD installation design - Sunland inverter

Create Date: 2024-8-30 12:03:23|Source: Hope Sunland

(1) The VFD should be installed in the control cabinet.

(2) The VFD is best installed in the center of the control cabinet; The VFD It should be vertically installed with the top and bottom protected from large parts that may obstruct the exhaust and intake.

(3) The minimum distance between the upper and lower margins and the upper and lower margins of the VFD control cabinet or partition, or the large parts necessary for the installation shall be greater than 300mm. The fundamental requirement for installing a VFD in a cabinet

                                 The basic requirements of VFD installation design - Sunland inverter

(4) If special users need to disassemble the keyboard in use, it is necessary to use tape to tightly seal the keyboard hole of the VFD panel or replace it with a fake panel to prevent a lot of dust from entering the VFD.

(5) The VFD should be maintained regularly, and the internal dust should be sorted out in time.

(6) Other basic devices and application requirements must comply with the relevant instructions in the user manual; If you have any questions, please contact the technical support personnel of the corresponding manufacturer in time.

More on that
Senlan identifies the fault place of the inverter Senlan identifies the fault place of the inverter

How to distinguish where the inverter is wrong? Step 1: Static data checking 1. Check the inverter circuit The red watch rod is received to the P end, and the black watch rod is separated from U, V, and W, and there should be a resistance value of tens of ohms, and the resistance value base of each phase, the same, the opposite should be infinite.

The drive panel does not display fault analysis The drive panel does not display fault analysis

1. The rectifier module is damaged It is usually caused by grid voltage or internal short circuit. In the case of excluding internal short circuits, the rectifier bridge is replaced. 2. The inverter module is damaged It is usually caused by damage to the motor or cable and the failure of the drive circuit. After repairing the drive circuit, ...

About the basic selection of Hope Sunland inverter About the basic selection of Hope Sunland inverter

It is hoped that Sunland low-voltage inverter can be divided into four series: 1.HG1000 high-performance light-load intelligent inverter, the most cost-effective, the new series is widely used in medicine, food, packaging, cable, printing and dyeing, washing, centrifuge ...

The inverter is regularly replaced with the device - Sunland inverter The inverter is regularly replaced with the device - Sunland inverter

1. Cooling fan As a prerequisite for ensuring the normal operation of the inverter, efficient and fast in-line cooling fans have become an indispensable conversion configuration of the inverter. Because of the wear of the internal bearings of the cooling fan and the reduction of the grease function in the process of application, the cooling of the fan.

Application of Sunland inverter in sugar separator Application of Sunland inverter in sugar separator

First, the operation of the machine before the technical transformation The sugar separation process of a sugar factory in Yunnan uses centrifugal dehydration method. The separation machine is mainly composed of a cone drum and a drive motor, and the motor shaft is directly connected to the bowl. Solid sugar crystallized from a high concentration of sugar water, in a cone bowl ...

Inverter dustproof method - Sunland inverter Inverter dustproof method - Sunland inverter

1. Plan a special inverter room When the power of the inverter is large or the number is large, a special inverter room can be planned. The doors, windows and cable holes in the room need to be sealed to avoid dust ingress; It is necessary to plan air filtration equipment and circulation channels to adhere to the normal indoor air ...

The difference between a voltage signal and a current signal The difference between a voltage signal and a current signal

The general voltage in industry is 0... 5(10)V or current 0(4)... 20mA is used as an analog signal transmission method, and it is also a method often used by program control machines. So what is the difference between the transmission method of voltage and current, and when to choose what method, the following will be briefly introduced.

The method of heat dissipation of small-capacity inverter - Sunland inverter The method of heat dissipation of small-capacity inverter - Sunland inverter

Natural heat dissipation methods are generally used for heat dissipation of small-capacity inverters, because their operating environment should be well ventilated and free of dust and floating objects. The drag targets of such inverters are mostly household air conditioners, CNC machine tools, etc., and the power is small. Still...

Misunderstandings and countermeasures of industrial control inverter - Senlan Misunderstandings and countermeasures of industrial control inverter - Senlan

Today, with the rapid development of science and technology, with the continuous improvement of industrial automation, inverters have also been widely used. Choosing a suitable inverter is very important to ensure the normal and efficient work of the inverter, but in practice, it is necessary to pay attention to some ...

Motor encoder and rotor pole phase zero alignment repair - Sunland Motor encoder and rotor pole phase zero alignment repair - Sunland

1. Phase alignment method of incremental encoder The alignment between the phase of the UVW electronic transmutation signal and the phase of the rotor pole, or the phase of the TV spot, of the incremental encoder with the signal exchange is as follows: 1) Use a DC power supply to pass the UV winding of the motor to less than the amount of ...

The connection method of three-phase isolation transformer - Senland The connection method of three-phase isolation transformer - Senland

The three-phase barrier transformer adopts a three-phase double-winding structure, which has the characteristics of lightning protection and anti-disturbance. Each winding on the primary and secondary sides is divided into two coils, which are wound from two layers of metal foil insulated from each other. So there is capacitance C (capacitance barrier transformer) between the two coils. Then, being able to ...

Precautions for the selection of exhaust fan inverter - Senlan Precautions for the selection of exhaust fan inverter - Senlan

1. Whether it has perfect maintenance function There will be many problems in the production process of the equipment, and if you want to prevent accidents, the equipment must have a perfect maintenance function, so as to prevent the loss of the enterprise. Therefore, when buying an exhaust fan inverter, you need to understand the safety function of the equipment first.

Wiring specification of inverter control cabinet - Senland Wiring specification of inverter control cabinet - Senland

The signal line and the power line must be routed separately: when using the analog signal to remotely control the inverter, the signal line of the control inverter and the strong current circuit (main circuit and sequential control circuit) can be separated from the inverter and other equipment to the analog interference, and the interval should be more than 30cm. Signal ...

Sunland inverters are designed for environmental requirements Sunland inverters are designed for environmental requirements

1. The ambient temperature ---- is generally "-10-+40°C"; Derating between 40 and 50°C, the additional output current must be reduced by 1% for every 1°C increase. If the ambient temperature is too high and the temperature changes greatly, the insulation of the inverter will be greatly reduced, which will affect the life of the inverter. ...

Sunland SBH series high-voltage inverter eight development direction cases Sunland SBH series high-voltage inverter eight development direction cases

The following application case of Sunland SBH series high-voltage inverter is a very comprehensive display of the eight development directions of high-voltage inverter High-voltage inverters, petrochemicals, mining, electricity Application plan 1 petrochemical occupation: Senlan twin ...

The device inside the inverter that needs to be replaced regularly - Sunland The device inside the inverter that needs to be replaced regularly - Sunland

1. Cooling fan As a prerequisite to ensure the normal operation of the inverter, efficient and fast in-line cooling fans have become an indispensable conversion configuration of the inverter. Because of the wear of the internal bearings of the cooling fan and the reduction of the grease function in the process of application, the cooling of the fan.

Hope Sunland grid-connected PV inverter Hope Sunland grid-connected PV inverter

Grid-connected photovoltaic inverter is one of the core components of solar photovoltaic power generation system, the main types are: central inverter, modular inverter, micro inverter, DC ...

The reason why the frequency of the inverter cannot be adjusted - Senlan inverter The reason why the frequency of the inverter cannot be adjusted - Senlan inverter

If there is no damage to the hardware, the maximum torque output of the inverter is generally less than the load to increase the torque. The acceleration time is too short ...

Automatic gain adjustment part - Sunland inverter Automatic gain adjustment part - Sunland inverter

In fact, there are also options for automatic gain adjustment, which generally divide the control response into several levels, such as high echo, medium echo, and low echo, which can be set by the user according to actual needs. Azimuth Share Buff: 1. Set the share gain of the azimuth ring adjuster; 2 ...

Repair and maintenance of Sunland inverter Repair and maintenance of Sunland inverter

The input and output currents of the inverter contain many higher harmonic components. In addition to the lower harmonics that can constitute the reactive power loss of the power supply, there are many harmonic components with high frequencies. They will transmit their own energy in various ways, forming a positive impact on the inverter itself and other equipment.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top