The method of judging the damage of a power element in the rectifier part is to manipulate the single conductivity of the rectifier element, and the positive and negative resistance values should not be consistent when the static value is general, and the specific method is as follows:
The three-phase bridge rectification current of the rectifier part may be diode rectification, thyristor semi-controlled rectification, thyristor full control rectification or IGBT rectification. No matter what kind of case, the three-phase rectifier is symmetrical, then the static test resistance effect should be suitable for symmetrical rope ruler, that is, the positive and negative test values of the three-phase input or output terminal relative to the positive and negative poles of the DC bus should be symmetrical under static conditions. Select the "diode" setting of the multimeter.
(1) In the first step, connect the red watch pen to the DC bus cathode, and connect the black watch pen to the power supply input three-phase terminal respectively, and the three test values should be the same. On the other hand, connect the black watch pen to the DC bus cathode, and the red watch pen to the three-phase wiring of the input power supply, and the three test values should be the same. If the diode rectifier bridge is used for rectification, the multimeter shows 0.4-0.6V when the rectifier conduction is on, and the infinity is shown when the reverse is cut-off. If the three-phase measurement value is greatly wrong, or the positive and negative measurement values of a phase are close or not different, the diode component is damaged.
(2) In the second step, connect the red watch pen to the negative pole of the DC bus, and the black watch pen to the three-phase wiring of the input power supply, and the three test values should be the same. On the other hand, the black watch pen is connected to the DC bus anode, and the red watch pen is connected to the three-phase wiring of the input power supply, and the three test values should be the same, and the pre-charge back is conceived after the rectifier bridge, how the operation can be the same to judge the rights and wrongs of the three rectifier elements of the negative half circumference of the rectifier bridge (the test method for the 12-pulse rectifier bridge is the same as above).
Note: Regarding the pre-charge retracement, it is assumed that before the rectifier return, the thyristor semi-control or full-control bridge rectification is selected, and the test effect should have a phase and the other two-phase forward and reverse resistance test values are not different, that is to say, there is a phase reality is the resistance value of the test diode pre-charge back.
|
More on that
|
Application of Sunland inverter on gantry milling machine
The gantry milling machine is a machining equipment for processing larger workpieces, and its electrical control system includes two parts: the main transmission of the workbench and the logical control of the feed organization. Henan Jiaozuo Maike Company has a gantry milling machine, which has been used for many years since the 70s. The main drive of the operating table of the gantry milling machine is selected ...
|
|
What are the peripheral equipment for inverter selection - Senlan inverter
After the inverter selection is completed, it is necessary to consider whether other peripheral equipment needs to be equipped according to the actual situation of the site. The peripheral equipment for frequency converter selection mainly includes circuit breakers, reactors, contactors, braking resistors, etc.
1. Circuit breaker
...
|
|
Introduction to the inverter maintenance and energizing test - Senlan
First, the inverter is not repaired and the power test is tested
(1) Inverter repair test rectifier circuit
At the two ends of the inverter to detect the internal DC power supply, P and N ends, adjust the multimeter to the resistance RX10 gear, the red watch pen is connected to the P end, and the black watch pen is connected to R, S, T in turn.
|
|
Sunland inverter overcurrent fault maintenance method
When the inverter current is too large, exceeding the limit value of the inverter, the maintenance circuit will produce action, so that the inverter trips and stops, and the phenomenon of repairing such inverter can be divided into energized ...
|
|
The control performance standard of the inverter cabinet
The control specifications of the inverter cabinet include reliability, accuracy, safety, environmental habits and versatility, etc., which are important guarantees to ensure the normal operation and safe production of the inverter cabinet control system.
Reliability specification: The control system should have high reliability and can be used for a long time.
|
|
Precautions for inverter selection and capacity matching - Senlan
1. Select the inverter according to the load characteristics
Second, when selecting the inverter, the current value of the practical motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a reference. Secondly, it should be fully considered that the output of the inverter contains higher harmonics, which will form the power factor of the motor.
|
|
The reason for the low output voltage of the inverter - Senlan inverter
1. The power supply voltage is low
The solution is to preset the active voltage adjustment function of the inverter, so that when the frequency is low and the rated frequency is dry, the inverter has the function of active voltage stabilization, and if the output voltage is low, the inverter will actively increase the output voltage
...
|
|
Asynchronous motor with inverter method - Senlan
Before the asynchronous motor is equipped with an inverter, let's take a look at the three major types of mechanical equipment loads:
1. Constant torque load: such as conveyor belt and mixer; When the inverter drags the load of constant torque nature, the torque at low speed should be large enough, and the overload should be large enough. If you need ...
|
|
The key points of the use of inverter - Sunland inverter
In order to ensure the safe, efficient and reliable operation of the inverter, the following keys should be grasped when using the inverter:
1) It is necessary to reliably ground the grounding terminal of the inverter, so as to effectively press the radio frequency disturbance and enhance the reliability of the system.
|
|
The reason why the inverter damaged the motor - Senlan
The presentation of inverters has brought a revolution to industrial automation control and motor energy saving. Industrial production is simply inseparable from the inverter, even in the daily livelihood, elevators, inverter air conditioning has become a part of the insistence, inverter from the beginning into all corners of production, subsistence. However...
|
|
The manufacturing standard of Sunland inverter cabinet
Planning specifications: The planning of inverter cabinets should conform to relevant national norms and industry norms, such as GB/T15576-2018 "Low-voltage Distribution Cabinet", GB7251.1-2017 "Low-voltage Complete Switchgear and Control Equipment", etc.
Material specifications: The materials of the control cabinet should conform to the relevant codes and regulations.
|
|
EMC rules for inverters - Sunland inverters
When various factory equipment uses frequency conversion speed regulation, harmonic disturbance will occur on the power supply side and motor side of the inverter (VFD), which will form electromagnetic disturbance to the power supply network and other electrical equipment near the VFD. In addition, in order to ensure the long-term reliable operation of the VFD, the wiring of the VFD is very important.
...
|
|
Sunland inverter wiring standard
It is necessary to separate the signal line from the power line: when using analog signals for long-distance control of the inverter, in order to reduce the disturbance of the analog amount from the inverter and other equipment, please separate the signal line of the control inverter from the strong current circuit (main circuit and sequential control circuit). Inverter ...
|
|
Switching power supply failure maintenance - Senlan
In the process of repairing the switching power supply, the step-down method can be selected. The method is: by connecting the power plug of the display to a communication voltage regulator, and then adjusting the output voltage of the voltage regulator to about 100V, and then repairing it with electricity, and gradually improving the power supply voltage for repair. ...
|
|
Sunland inverter maintenance and cleaning inspection method
There are many special faults, which come and go, looming, making it impossible to judge and deal with. At this time, you can clean the circuit board with water or alcohol, and brush off the dust and rust on the circuit board with a soft brush, especially pay attention to the solder joints are dense, and the circuit near the 0 volt copper layer is also ...
|
|
Precautions for the selection of exhaust fan inverter - Senlan
1. Whether it has perfect maintenance function
There will be many problems in the production process of the equipment, and if you want to prevent accidents, the equipment must have a perfect maintenance function, so as to prevent the loss of the enterprise. Therefore, when buying an exhaust fan inverter, you need to understand the safety function of the equipment first.
|
|
Rapid selection method of low-voltage inverter - Sunland inverter
First, according to the classification and selection of inverters
1. Inverters can be divided into general-purpose inverters and special inverters.
2. General-purpose inverters are mainly used in: general fan pumps (referring to inverters that only drag a single fan or pump) loads, mechanical loads, and loads requiring high overloads.
|
|
Hope Sunland inverter fault code
Hope Sunland inverter part of the fault code
Er.ocb (1) Overcurrent at the moment of starting: There is a short circuit inside the motor
There is a short circuit in the motor wiring
The starting voltage is too high
Check the motor and wiring
Check the motor wiring
Seek service
Check the torque ...
|
|
Inverter-related knowledge - Senlan inverter
1. What does open-loop mean in the use of inverters?
The speed detector (PG) is installed on the motor equipment in operation, and the speed response of the actual speed is sent to the control equipment, which is called "closed loop", and the speed detector that does not use PG is called "open loop". Most general-purpose drives are open-loop ...
|
|
Get to know the capacitor of the inverter - Sunland inverter
1. The capacitance is generally indicated by "C" plus a number in the circuit (e.g., C25 indicates the capacitance numbered 25).
A capacitor is a component composed of two metal films close to each other and separated by an insulating material in the center. The characteristic of the capacitor is first and foremost the communication through the DC block. The size of the capacitance is ...
|
|