1) When there is a power outage for any reason and the power cannot be restored in a short period of time, the backup power supply must be activated
1. Cut off the circuit breakers of the mains power supply (including the circuit breakers of the control cabinet in the distribution room and the mains power cut-off of the dual-power switching box), pull the double-throw anti-backing switch to the side of the self-provided power supply, and keep the self-provided power supply circuit breaker in the dual-power switching box in the disconnected state
2. Start the standby power supply (diesel generator set), and when the unit is running normally, close the generator air switch and the circuit breaker in the self-provided power control cabinet in order.
3. Close each standby power circuit breaker in the power switching box one by one to send power to each load.
4. During the operation of the standby power supply, the operator on duty shall not leave the generator set, and adjust the voltage and frequency in time according to the change of load, and deal with the abnormality in time.
2) When the mains power supply is restored, the power conversion should be done in time, the standby power supply should be cut off, and the mains power supply should be restored.
1. Disconnect the circuit breakers of the self-provided power supply one by one in order, the order is: the self-provided power supply circuit breaker of the dual power supply switching box, the circuit breaker of the self-provided power distribution cabinet, the main switch of the generator, and the double switch will be dialed to the side of the mains power supply.
2. Shut down according to the diesel engine shutdown steps.
3. In order, close each circuit breaker one by one from the main switch of the mains power supply to each branch switch, and put the circuit breaker of the dual power switching box from the mains power supply in the closed position.
|
More on that
|
Tianyi switch - PCB design considerations for switching power supplies
In the design of switching power supply, the physical design of the PCB board must be proper, otherwise it may cause excessive electromagnetic interference and lead to unstable power supply.
1. The design process from the schematic diagram to the PCB should be rigorous and perfect: the establishment of component parameters ...
|
|
Tianyi switch - the method of adjusting the current of Tianyi switch
1. Change the reference current of the feedback module
Regulating the reference current is the most basic way to regulate the output current of a switching power supply, and it can usually be achieved by rotating a potentiometer or toggling a switch. Changing the reference current allows the magnitude of the feedback current to be compared with it, so as to control the switch ...
|
|
Tianyi switch - common faults and troubleshooting methods of low-voltage switches
1 The contact is overheated
Contact heat is mainly caused by the current flowing through the contact, and there is power loss between the contacts (such as contact resistance loss, arc energy loss). It is normal for the contacts to heat up, but severe heat (overheating) is a malfunction.
The main ...
|
|
Tianyi switch - the allowable operating range of the disconnector
1. Pull together the voltage transformer and lightning arrester under normal conditions.
2. Pull together the 220kV no-load bus.
3. The neutral point of the transformer when there is no ground fault in the latching grid.
4. Pull the bypass current that is closed by a switch or an isolated switch.
5. Outdoor vertical splitting triple isolation ...
|
|
Tianyi switching power supply troubleshooting
1. Check the key points:
1) Whether the voltage at point B is 310V.
2) Whether the 15V voltage is normal.
3) Whether the voltage at point C is greater than 14V.
4) Whether the SS terminal of (8) pin IC6 is higher than 10V, whether the SD terminal of pin (10) is lower than 0.6V, and whether there is a square wave transmission at pin 13 and pin 14 ...
|
|
Tianyi switch - the performance and main features of dual power automatic transfer switch
performance
1. Adopt double-row composite contacts, cross-connected mechanisms, micro-motor pre-energy storage and micro-electronic control technology, basically achieve zero arcing (no arc extinguishing cover);
2. Adopt reliable mechanical interlocking and electrical interlocking technology;
3. Adopt zero-crossing technology;
4、 ...
|
|
Tianyi switch - introduction to the characteristics of high-voltage load switch
1. It can isolate the power supply, have obvious disconnection points, and is mostly used for fixed high-voltage equipment.
2. It has an arc extinguishing device and a certain opening and closing speed, and can pass the normal working current and the specified short-circuit circuit in the closing state.
3. It is strictly forbidden to turn on and off the circuit with load.
|
|
Tianyi switch - what is the function of high-voltage load switch
1. It can isolate the power supply, with a significant disconnection point, and is mostly used for fixed high-voltage devices;
2. It has arc extinguishing equipment and a certain opening and closing rate, and can pass through the normal working current and the specified short-circuit circuit in the case of closing;
3. It is forbidden to connect and cut off the circuit with load, ...
|
|
Tianyi switch - the role of air switch
1. The air switch is an important electrical appliance in the low-voltage distribution network and power drive system, which integrates control and a variety of protection functions. In addition to completing contact and breaking circuits, it can also generate short circuits to circuits or electrical equipment. Protection against severe overloads and undervoltages, etc.
|
|
What are the common problems of Tianyi switch - disconnector?
1. What are the common faults?
Answer: The common faults of the disconnector are: (1) The contact part is overheated. (2) Porcelain insulation damage and flashover discharge. (3) Refuse to pull and close. (4) Wrong pulling and closing.
2. The overheating of the contact part of the disconnector during operation is caused by ...
|
|
Tianyi switch - the difference between high-voltage load switch and high-voltage circuit breaker
1. The high-voltage load switch can be used as a load switch, which has the effect of self-extinguishing arc, but its breaking volume is very small and very limited.
2. The high-voltage isolation switch generally cannot be used as a load switch. There is no arc extinguishing cover in the structure, and there are also disconnectors that can switch loads on and off, but the structure is different from load switches ...
|
|
Tianyi switch button - the color meaning of the button and indicator light and the place of use
1. Buttons
1. Red
Operation in hazardous situations. It is often used for emergency stops
Stop and break. It is often used to stop all machines, stop one or more motors, stop a certain part of a piece of equipment, make the electrical components lose power, and have a stop function reset button.
...
|
|
Tianyi switch - the selection principle of air switch
1. Determine the type and protection form of the circuit breaker according to the requirements of the line for protection - determine the selection of frame type, device type or current limiting type.
2. The rated voltage UN of the circuit breaker should be equal to or greater than the rated voltage of the protected line.
3. The rated voltage of the circuit breaker undervoltage tripper ...
|
|
Where can Tianyi switch - limit switch be used?
daily life
There are many aspects of the use of limit switches, and it is found in many electrical appliances. So what effect can such a simple switch have? It is first and foremost a chain maintenance effect. The most common example is its use in washing machines and tape recorders (video recorders). ...
|
|
Tianyi switch - 5 methods to suppress ripple in switching power supply
1. Increase inductance and output capacitance filtering
According to the formula of the switching power supply, the current fluctuation in the inductor is inversely proportional to the inductance value, and the output ripple is inversely proportional to the output capacitance value. Therefore, increasing the inductance and output capacitance can reduce ripple.
In the same way, the output ripple is the same as the output ...
|
|
Tianyi switch - what does the 2P3P of the air switch mean
2P means two poles, which means that this air switch has two connection ports, one to connect to the neutral wire and one to the live wire, which is suitable for single-phase circuit connection, or can also be used to connect two-phase power supply in a three-phase circuit.
3P is the meaning of three poles, there are three connection ports, and all of them are ...
|
|
New Upgrades - A new member of the warning light family reports
JD series warning light is Tianyi electrical appliances in the field of signal control launched high-performance products, once launched, it has won the unanimous favor of customers, products in the design, manufacturing, quality control and other aspects of the company's quality system has always been under the strict testing and supervision of the company's quality system, to ensure that each product ...
|
|
VTeam participated in the 9th China CNC Machine Tool Exhibition
During the "Twelfth Five-Year Plan" period, China deepened reform and opening up and accelerated the transformation of economic development mode. Transformation and upgrading is the only way for the sustainable development of the machine tool industry, and the top priority of the industry's transformation and upgrading is to enhance the market competitiveness of high-end CNC machine tools. Exhibitors will take advantage of the CCMT ...
|
|
Tianyi switch - the use and function of air switch
What are the uses of air switches
1. The air switch is an important electrical appliance in the low-voltage distribution network and power drive system, which integrates control and a variety of protection functions. In addition to completing contact and breaking circuits, it can also generate short circuits to circuits or electrical equipment. Severe...
|
|
Tianyi switch - the role of the disconnector switch
1. After opening, establish a reliable insulation gap to separate the equipment or line that needs to be overhauled from the power supply with an obvious disconnection point to ensure the safety of maintenance personnel and equipment.
2. According to the operation needs, change the line.
3. It can be used to divide and combine small currents in the line, ...
|
|