1. Common faults of motor heating up too high or smoke motor
Causes: 1. Excessive load; 2. Two-phase operation; 3. Blocked air duct; 4. The working temperature is too high; 5. Interphase or inter-turn short circuit fault of motor stator winding; 6. Motor stator winding grounding device; 7. The power supply voltage is too high or too low;
Maintenance method: 1. Relieve the load or select a large space motor. 2. Eliminate air ducts; 3. Use hypothermic countermeasures; 4. Use a digital multimeter and ammeter to check the power supply voltage at the input end.
Second, the motor shell brings the phenomenon of motor failure
Causes: The windings are damp, the insulation layer is aging and embrittle, or the transformer grounding wire collides with the junction box shell.
Overhaul method: drying, replacing the winding.
3. Common faults of motor vibration motors
Reasons: 1. The motor rotor is unbalanced; 2. Shaft bending; 3. The transmission belt pulley is unbalanced; 4. The air gap is uneven, forming a unilateral magnetic pull
Maintenance method: 1. Correction of dynamic equilibrium; 2. When the bending of the straightening shaft or disassembling the shaft is not serious, you can turn it to 1-2 mm, and then add the sleeve; 3. Calibrate the balance 4. Center adjustment;
Fourth, the current three-phase unbalanced motor common faults
Reasons: 1. Lack of power supply voltage; 2. The number of turns of the three-phase coil is different; 3. Incorrect internal wiring.
Maintenance method: 1. Check the power supply voltage; 2. Dismantle and replace the motor or dispose of it; 3. Correct the wiring.
Fifth, the no-load current is too large motor common faults
Reasons: 1. The air gap of the stator and rotor is large, 2. The number of turns of the stator winding coil of the motor is too small; 3. Improper installation
Maintenance method: 1. Adjust and reduce 2. Adapt and winding from the beginning; 3. Install from scratch;
6. Insulation resistance reduces common faults of motors
Reasons: 1. Stator seepage and moisture collection; 2. Too much dust; 3. Insulation layer failure; 4. Aging and embrittlement of the insulation layer;
Maintenance methods: 1. Drainage and damp removal; 2. Remove dust; 3. Patching; 4. Dismantling and replacement;
|
More on that
|
Inverter overcurrent treatment method - Senlan inverter
Overcurrent or overload of the inverter is a common problem of the inverter, and overcurrent refers to the value of the current flowing through the inverter beyond its additional range.
1. If the power supply of the inverter is out of phase, the circuit at the output end is disconnected or the motor winding ...
|
|
What is the energy feedback of the inverter - Senlan inverter
The essence of energy feedback is active inverter, and the realization method of energy feedback of general inverter is to feed renewable energy to the grid with an anti-parallel three-phase inverter at the uncontrolled rectification of the pre-stage of the general inverter. The main circuit of the energy feedback equipment is mainly composed of thyristors, IGBTs and IPM modules.
|
|
Sunland inverter electromagnetic interference suppression method
When the peripheral equipment and the inverter share the same power supply, the disturbance generated by the inverter is transmitted against the power line, which will cause other equipment in the same system to malfunction. The following methods can be adopted:
(1) The input device of the inverter is equipped with an EMI filter or a ferrite common-mode filter (magnetic ring) ...
|
|
Sunland inverter does not show fault repair
After inspection, the circuit board of the machine is composed of a fan switching power supply board, a control board with a switching power supply and a driving board, etc., the fan power supply and the control board operation power supply are independent of each other, the fan power supply output is normal, and the control board operation power supply is not output due to the problem.
...
|
|
Senlan identifies the fault place of the inverter
How to distinguish where the inverter is wrong?
Step 1: Static data checking
1. Check the inverter circuit
The red watch rod is received to the P end, and the black watch rod is separated from U, V, and W, and there should be a resistance value of tens of ohms, and the resistance value base of each phase, the same, the opposite should be infinite.
|
|
Excessive capacity of the inverter causes harm to electrical equipment - Senlan inverter
(1) The harmonic current generated will directly cause the additional heating of the motor, so that the stator of the motor surpasses the additional temperature rise of the motor itself, so that the additional output capacity of the motor will be greatly reduced.
(2) The current output of the inverter ...
|
|
Whether the front end of the inverter can be installed with a motor protector - Senlan
Frequency conversion speed regulation motor is generally selected 4-level motor, the fundamental frequency operation point is planned at 50Hz, the frequency 0-50Hz (speed 0-1480r/min) scale of the motor for constant torque work, the frequency of 50-100Hz (speed 1480-2800r/min) scale of the motor for constant power work, the whole speed regulation scale of (0 ...
|
|
Senlan inverter motor failure analysis
1. The motor slows down too slowly
1) If the deceleration time is set too long, reduce the deceleration time
2) Install a braking resistor
3) Add DC braking
2. The motor is overheated
1) The load is too large, and the practical moment has exceeded the ...
|
|
Anti-interference measures in the application of Sunland inverter
The main manifestations of the disturbance of the inverter in the application are: higher harmonics, noise and oscillation, load matching, heat generation and other problems. These disturbances are unavoidable, because the input part of the inverter is a rectifier circuit and the output part is an inverter circuit, both of which are made up of nonlinear components that play a switching effect.
|
|
Common maintenance methods of inverter - Senlan inverter
1. Step-by-step decreasing method
The so-called gradual reduction method is to gradually reduce the scale of the problem through the analysis of the problem phenomenon and the identification of measurement parameters, and finally implement it to the specific circuit or component that causes the problem. In essence, it is a certainty, a negation, a negation, a negation, a final ...
|
|
Sunland Shore Power Innovation - The world's first high-voltage water-cooled four-quadrant shore power system rolled off the production line
In order to thoroughly implement the spirit of General Secretary Xi Jinping's important instructions that the economic power must be a maritime power, a shipping power, economic development, a strong country, and transportation, especially shipping, and the implementation of the outline for the construction of a transportation power, the port ship shore power system has become the standard for green ports.
|
|
The cause of the leakage problem of Sunland inverter
1. The cause of inverter leakage
According to the inverter to control the operation of the motor, the three-phase electricity is supplied to the inverter bridge (IGBT) through the filter capacitor through the rectification, and then the operation of the motor is controlled by the three-phase electricity with adjustable output frequency and voltage of the inverter.
We all know that the three-phase stator winding of the motor ...
|
|
Inverter maintenance method - hope sunland
1. Look
After taking over a faulty inverter, remove the inverter shell and clean it up, and carefully investigate the appearance, shape, and integrity of the relevant components on the circuit board with both eyes according to the type of inverter fault. This method is about charging resistors, filter electrolytic capacitors, IG ...
|
|
Sunland proposed a multi-machine parallel high-voltage shore power supply system solution
Air pollution in port cities mainly comes from cargo loading and unloading operations and emissions from ships calling at ports; Shore power connection refers to the closure of the auxiliary engine during the port of the vessel, and the shore power is supplied by the port.
At 9:08 on December 25, 2018, the world's first ...
|
|
Common problems in the use of inverters - Hope Sunland
1. Please clarify the maintenance function of the inverter?
(1) After detecting the abnormal situation, take the initiative to correct the action, such as overcurrent loss speed prevention, regeneration overvoltage stall prevention.
(2) Block the power semiconductors after detecting the abnormality...
|
|
Inverter control method for motor - Senlan
1. U/f stable control
U/f control is to change the voltage of the motor power supply together with changing the frequency of the motor power supply, so that the magnetic flux of the motor is kept constant, and the efficiency and power factor of the motor do not decrease within a wide range of speed regulation. Because it is to control the voltage and frequency ...
|
|
Sunland won the "well-known brand of China's domestic inverter" for the fifth time in a row
On April 15, 2011, the "Century Tour of China's Automation Industry (CAIE2011)" was held in Beijing, and Sunland inverter was once again re-elected as "China's well-known brand of domestic inverter". Dr. Chen Bin, President of Continental Hope Group and Chairman of Hope Sunland Technology Co., Ltd., personally ...
|
|
Common brand inverter modification power method - Senlan inverter
What are the advantages of inverter power correction? Many brands of inverter power boards, driver boards, and motherboards can be universal, as long as the type, volume, and hardware are the same, and the desired power and voltage value can be obtained by correcting the manufacturer's parameters.
...
|
|
Sunland inverter overcurrent fault maintenance method
When the inverter current is too large, exceeding the limit value of the inverter, the maintenance circuit will produce action, so that the inverter trips and stops, and the phenomenon of repairing such inverter can be divided into energized ...
|
|
Frequency conversion speed regulation of several special motors - Senlan frequency converter
A. Wound rotor asynchronous motor
The rotor winding of the wound rotor asynchronous motor is a set of three-phase windings with star connection. The end points of the three-phase winding are connected to the three collector rings, which are connected to the brushes and the external resistor (for starting or speed regulation) through the collector rings. Select inverter ...
|
|