Composition of medium and low voltage bus protection - Wiener

Create Date: 2024-8-30 12:03:23|Source: Woehner/Wiehner

On the medium and low voltage side of the main transformer, the bus tie switch and the original electromagnetic relay maintenance DC circuit of each outlet, the PLC is used for logical comparison to determine whether it is a fault in the maintenance area or a fault outside the area.

                               Composition of medium and low voltage bus protection - Wiener

1. 10 kV bus maintenance The 10 kV main wiring of the substation, each outgoing line has no power supply, each outgoing line and bus tie maintenance selects two-phase incomplete star-shaped current quick break and overcurrent maintenance, and the low-voltage side of the main transformer is equipped with three-phase complete star-shaped composite voltage overcurrent maintenance. The instantaneous closing contact of the time relay is used as the input contact of the PLC, and the PLC output controls the DZ52 central relay to jump the switch on each side of the main transformer.

The low-voltage side of the main transformer selects three-phase complete star and each outgoing line, and the two-phase incomplete star wiring is selected for bus maintenance, which can prevent the two-point grounding short circuit between the B phase of the bus and the A or C phase of the outgoing line. The AC power supply used in the PLC is provided by the on-line UPS. The bus maintenance is divided into two sections, the I. section is instantaneous, and the maintenance scale is from the bus to each circuit breaker; II. Short delay, maintenance scale from main transformer circuit breaker to main transformer 10 kV current transformer (including circuit breaker).

2. 35 kV bus maintenance The 35 kV main wiring diagram of the substation is similar to Figure 1, some of the outgoing lines have power supply, and the outgoing line without power supply and bus tie maintenance choose two-phase incomplete star current quick break and overcurrent maintenance; The outgoing line with power supply is equipped with two-phase incomplete star direction overcurrent maintenance; The 35 kV side of the main transformer is equipped with a three-phase complete star composite voltage direction for overcurrent maintenance. The instantaneous closing contact of the over-current or directional over-current time relay is used as the input contact of the PLC.

More on that
The busway power system is a key component - Wiener The busway power system is a key component - Wiener

The busway is one of the more critical components in the power system, and it is an important part of connecting cables to important equipment such as substations, overhead lines, transformers, circuit breakers, etc. It is widely used in various power systems, mainly for the reliable operation of power systems. ...

Lighting power busway service life - Wienal Lighting power busway service life - Wienal

The system consists of a current box, a bus body, a branch plug and device accessories. When the heat dissipation of conductive copper strip has been effectively improved, the contact between the copper strip and the inner wall of the tube is reduced, and the insulation resistance and anti-aging ability of the tube body are strengthened, so as to prolong the service life of the pipe body. The life of the tube far exceeds ...

Characteristics of single bus wiring in the switchgear - Wiener Characteristics of single bus wiring in the switchgear - Wiener

In power distribution equipment such as voltage distribution cabinets and switchgear at all levels of power plants and substations, the conductors connected between large electrical equipment such as generators and transformers and various electrical equipment are called busbars. Busbars, also known as busbars, are used to gather, distribute, and transmit electrical energy. The connection methods of the bus bar are ...

Wiener bearing repair technology Wiener bearing repair technology

1. Comprehensive correction of bearings The comprehensive correction of the bearing includes the comprehensive and strict correction process of the damaged bearing after cleaning, dismantling, inspection, roller table grinding or replacement of inner and outer rings, new rolling element manufacturing/original rolling element grinding, rolling element replacement, assembly, clearance adjustment and inspection and packaging.

A new product has been added to the world of CrossBoard® systems A new product has been added to the world of CrossBoard® systems

A new addition to the world of CrossBoard® systems: the MOTUS® hybrid motor starter with IO-Link interface is a new networking feature in the MOTUS® IO-Link family that enables continuous communication between the control and device levels. Control the delivery of instructions, control the parameters ...

Common Bus Application Considerations – Wiener Common Bus Application Considerations – Wiener

  In the common DC bus system of multiple inverters, especially the common DC bus of inverters of different power levels, it is very important that the connection between the bus bars is maintained by fuses. When one of the inverter power equipment in the common bus is damaged by short circuit breakdown, the other inverter bus ...

Application and technical requirements for bus protection on the low voltage side - Wiener Application and technical requirements for bus protection on the low voltage side - Wiener

1. The use status of bus maintenance on the low-voltage side According to the national standard "Code for Relay Maintenance and Automatic Equipment Design of Power Equipment" (GB50062-92): about the 3-10kV bus and the double bus running in parallel of the power plant and the primary substation, as long as the following conditions are installed.

Introduction to busbars, busway, and busbridges - Wiener Introduction to busbars, busway, and busbridges - Wiener

generatrix In the field of electricity, the busbar can also be called the busbar, busbar, etc., which mostly refers to the busbar or power supply trunk in the high and low voltage cabinet, which is used to connect multiple electrical lines. The system will install various interface cards through the bus, and transmit various data to the devices connected to the interface cards.

Features of the use of closed busway - Wiener Features of the use of closed busway - Wiener

Compared with other air-type busway, Wiener closed busway has many similarities in appearance, and its difference lies mainly in the shell, the structure of the closed busway is more distinctive, which also makes its use have certain advantages. As long as it is in contrast ...

Wiener looks at the busway drawing method Wiener looks at the busway drawing method

First, in the CAD system drawing, it is a plan of the bus duct, and two parallel polylines can indicate the bus duct. 2. The busway includes the following parts: 1. Feeder busbar, which is used to transmit electricity 2. Plug-in busbar with plug-in interface above, ...

Scenarios for the use of various types of busbars - Vernal Scenarios for the use of various types of busbars - Vernal

1. The bus bar is divided into hard bus bar and soft bus bar. 2. According to different shapes, hard busbars can be divided into: rectangular busbars, tubular busbars, trough busbars, diamond busbars, etc. 3. Rectangular busbar is a commonly used busbar. According to its material ...

Analysis of the conditions for the use of sealed busbars - Wienal Analysis of the conditions for the use of sealed busbars - Wienal

Ambient air temperature: turn off the busbar system to benchmark the ambient air temperature; Unless otherwise ruled, the manufacturer should give an additional current to shut down the busbar system at a base ambient air temperature of 35°C; If applicable, the manufacturer should give an additional coefficient k: (K1=1 at 35°C) in order to determine the size of the package.

The role of the busbar in the excitation system – Wiener The role of the busbar in the excitation system – Wiener

The bus PT is used to measure the bus voltage on the high-voltage side of the main transformer, and is used to assist in grid connection. Before starting the synchronous grid connection, the excitation system actively adjusts the terminal voltage according to the bus voltage measured by the bus PT, so that the voltage on both sides of the grid-connected switch is basically equal, which is convenient for the same period of grid connection. ...

Wiener is a common way to wiring busbars Wiener is a common way to wiring busbars

Single bus wiring method: all outgoing wires are connected to the same busbar, which is also the most cost-effective and simplest wiring method Single bus segmentation: The outgoing line is arranged in two parts on different sections of the single busbar, so that a power failure in the meantime does not affect the power supply of the other bus ...

The operation procedure of the dual power supply automatic transfer switch The operation procedure of the dual power supply automatic transfer switch

The dual-supply ACT is a new generation of products. Beautiful appearance, good quality, long life, simple It is composed of two three-pole or four-pole shell graders and their parts/mechanical interlocking transmission arrangements, intelligent controllers, etc., which are divided into two structures: integral and split.

Advantages and disadvantages of bus full differential protection Advantages and disadvantages of bus full differential protection

Thorough differential maintenance of the bus is to connect the current transformer of all the connecting elements on the bus to the differential circuit according to the same name phase and polarity, the characteristics and transformation ratio of the current transformer should be the same, if the transformation ratio can not be together, the compensation converter can be used to compensate, satisfactory ΣI=0. ...

Wiener busway plug-in box wiring method Wiener busway plug-in box wiring method

The bus duct bracket has to be firmly installed, and the bus duct should be correctly placed according to the segment sequence number, phase sequence, number, direction and device mark, and when the sections are connected, the adjacent section of the bus duct should be aligned, and the conductor and shell of the bus duct should not accept mechanical stress after the connection. ...

The Wiener bus is a Siemens 3 VA1 and 3 VA2 adapter The Wiener bus is a Siemens 3 VA1 and 3 VA2 adapter

Wiener has developed a new series of 3 VA1 circuit breakers equipped with ® busbar adapters from Siemens in the 160 system with a compact range of 30. The safety articulation of the circuit breaker is the internal right of the tension spring device base and high-performance rails. ...

The service life of the lighting power busway – Wienal The service life of the lighting power busway – Wienal

The system consists of a current box, a bus body, a branch plug and device accessories. When the heat dissipation of conductive copper strip is effectively improved, the contact between the copper strip and the inner wall of the tube is reduced, the insulation resistance and anti-aging ability of the tube body are strengthened, and then the service life of the tube body is extended. The longevity of the tube far exceeds ...

Calculation method of bus system and distribution cabinet bus - Wiener Calculation method of bus system and distribution cabinet bus - Wiener

The bus system divides the bus into hard bus and soft bus. The 60mm bus system refers to the three-wire or four-wire bus with a distance of 60mm. 1. In the 60mm bus system, the different cross-sectional areas of rectangular copper bars or special-shaped copper busbars such as 2T and 3T can be used to achieve the best classification of current intensity grades.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top