One. The touch screen is not allowed

Fault phenomenon: A surface acoustic wave touch screen, touching the part of the monitor screen with your finger can not complete the corresponding operation normally.

Fault analysis and processing

This phenomenon may be that after a period of use, the reflective stripes around the sonic touch screen are covered with dust, which can be wiped with a dry soft cloth, then power off, restart the computer, and recalibrate. It is also possible that the reflective fringes of the sound wave screen are slightly damaged, and if this happens, it will not be completely repaired.

In the case of a capacitive touchscreen, run the screen calibration procedure (Start --Procedure --MicrotouchTouchware) in the following cases:

1) Complete the installation of the driver software for the first time.

2) After changing the resolution or display mode of the monitor every time.

3) After changing the display area of the display every time.

4) After adjusting the frequency of the controller each time.

5) Every time the cursor does not correspond to the touch point.

After calibration, the calibrated data is stored in the controller's registers, so there is no need to calibrate the screen after each system boot.

Two. The touch screen is unresponsive

Fault phenomenon: A touch screen can not work, and there is no response to touch any part.

Fault analysis and processing

First, check whether the wiring interface is loose, and then check whether there is a conflict between the serial port and the interrupt number, if there is a conflict, the resources should be adjusted to avoid the conflict. Then check whether there are cracks on the surface of the touch screen, and replace them in time if there are cracks. It is also necessary to check the surface of the touchscreen for dirt and, if so, remove it with a soft cloth. Observe and check whether the indicator light on the control box is working properly, and when it is normal, the indicator light is green and flashing.

If the above parts are normal, you can use the replacement method to check the touch screen, first replace the control box, then replace the touch screen, and finally replace the main unit.

If it is a surface acoustic wave touch screen, it can be overhauled as follows:

1. It may be that one of the cables connected to the keyboard port of the host (take the 5 volt touch screen working voltage from the keyboard port) is not connected in the connection of the touch screen, please check the connection.

2. It may be that the string slogan selected during the driver installation process of the touch screen does not correspond to the string slogan actually connected to the touch screen, please uninstall the driver and reinstall it.

3. It may be that the host is a domestic original machine, and the operating system installed is the OEM version, which has been adjusted by the manufacturer, resulting in the non-standard nature of serial port communication, and the touch screen driver is incompatible.

4. It is possible that the touch screen driver version is too low, please install the latest driver.

5. Check whether there is a conflict between the device and the serial port resource in the host, check the hardware device and adjust it. For example, if the default IRQ of some NICs is 3 and conflicts with the IRQ of COM2, you should change the IRQ of the NIC to an idle and unused IRQ.

If it is a resistive touch screen, it can be overhauled as follows:

1. Check whether the connection of the touch screen is right, and whether one of the wires connected to the keyboard port of the host (take the working voltage of 5 volts touch screen from the keyboard port) is connected, please check the connection.

2. Observe the situation of the touch screen control box light, if it is not lit or the red light is on, it means that the control box is broken, please replace it.

3. If you confirm that it is not the above situation, please delete the touch screen driver and restart the computer to reinstall the driver, or replace the driver with a newer version.

4. Check and adjust whether there is a conflict between the device and the serial port resource in the host. For example, if the default IRQ of some NICs is 3 after installation, which conflicts with the IRQ of COM2, you should change the IRQ of the NIC to an idle and unused IRQ.

5. If the touch screen is used for a long period of time (3-4 years) and you find that there are some areas of the touch screen that cannot be touched, it may be that the touch screen is broken, please replace the touch screen.

Three. The touch screen has a long response time

Fault phenomenon: A touch screen, after touching the monitor screen with your finger, it takes a long time to react.

Fault analysis and processing

This could be a sign that there are moving water droplets stuck to the touchscreen, just wipe them with a dry, soft cloth. It is also possible that the grade of the host is too low, such as the clock frequency is too low, if this is the case, it is best to replace the host.

Four. The touch screen is partially unresponsive

Fault phenomenon: A touch screen, after touching the monitor screen with your finger, there is no response in some places.

Fault analysis and processing

This may be due to the fact that the reflective streaks of the touch screen are partially covered and can be wiped clean with a dry, soft cloth. It is also possible that the reflective stripes of the touch screen are partially scraped off by a hard object and cannot be repaired.

Five. The touch screen is working but the computer is not operating

Fault phenomenon: A touch screen, after the test itself, everything is normal, but after connecting to the host, the computer can not be operated.

Fault analysis and processing

This may be because the touchscreen control card receives the operation signal before the host computer starts to load the touchscreen driver, and only needs to power off again and then start the computer. It's also possible that the touchscreen driver version is too low and you need to install the latest driver.

Six. The first time the touchscreen is booted after installing the driver, it is unresponsive

Fault symptom: A touch screen, the touch screen does not respond when the driver is installed for the first time.

Fault analysis and processing

First of all, confirm whether the touch screen line connection is correct, if not, it should be turned off and connect all the lines correctly. For example, the default IRQ of some NICs is 3 after installation, which conflicts with the IRQ of COM2, and the IRQ of the NIC should be changed to an idle and unused IRQ.

Seven. No response to touch after using it for a while

Fault phenomenon: a touch screen, after turning on the machine after normal use for a period of time, there is no response.

Fault analysis and processing

1. Check if the hard drive is set to turn off the hard drive in the "Display Energy Saving Settings" of Wlndows9x. You can do this by right-clicking on the desktop, selecting the Properties command, selecting the Screen Saver tab from the dialog box, clicking the Settings button, and setting the parameters to Never, except for the Power Scheme which is Always On.

2. In some applications, due to poor grounding performance, the shell of the control box will be covered with a large amount of static electricity, which will affect the working electric field inside the control box, resulting in the gradual failure of the touch. At this time, use a wire to ground the shell of the control box and restart it.

3. Because the surface sound wave touch screen is covered with sound waves on the surface of the touch screen when working, if the touch screen is not wiped for a long time, it will cause excessive dust accumulation and block the reflection stripes of the wave, which will cause the touch screen to not work normally. For touch monitors, use clean business cards or banknotes to gently wipe the dust off the surrounding reflective streaks through the gap between the front cover of the monitor and the touch screen, and then restart the computer. For All-in-One Touchscreens, open the front cover of the monitor, wipe the dust off the surrounding reflective streaks with a clean towel, and then restart the computer.

4. Many touch all-in-one touch screen control boxes use the way of taking power from the all-in-one power supply instead of taking power from the host, so you should also check whether the 5V output of the all-in-one power supply is correct, sometimes the instantaneous current is too large, resulting in the fuse being burned, and the fuse needs to be replaced at this time.

8. The touch screen click accuracy decreases

Fault phenomenon: A touch screen, its click accuracy decreases, and the cursor is difficult to locate.

Fault analysis and processing

1.Run the touch screen calibration program. (Start - Settings - Control Panel - Sonic Screen ---Capberate button)

2. If it is a newly purchased touch screen, please try to delete the driver, and then power off the main unit for 5 seconds to power on and reinstall the driver.

3. If the above method does not work, it may be that the reflection fringes of the sound wave screen during transportation are slightly damaged and cannot be completely repaired, and you can deviate from the calibration bullseye at equal distances in the opposite direction (relative to the direction of deviation from the mouse) for positioning.

4. If the sound wave screen is not allowed after a period of use, it may be that the reflective stripes around the screen or the transducer is covered with dust, if you are using our company's KA type cabinet, you can open the upper cover and use a dry soft cloth dipped in industrial alcohol or glass cleaning liquid to clean its surface, and then re-run the system, pay attention to the upper left, upper right, lower right transducer can not be damaged. Then power off, restart the computer and recalibrate.

5. There are water droplets or other soft things stuck to the surface on the surface of the touch screen, and the touch screen is misjudged to have a hand touch, resulting in the inaccurate surface sound wave screen, and it can be removed.

The touch screen cannot be calibrated for fault analysis processing

1. If you are using a Lenovo console, which has a pre-installed MOUSEWARE software that conflicts with the touch screen driver, please delete this software and restart the calibration program.

2. It is possible that the touch screen control card receives the operation signal before the host starts to load the touch screen driver, please power off and restart the computer and recalibrate.

3. It may be that the touch screen driver is installed abnormally, please delete the driver and reinstall it. (Removed from the Control Panel Add Removal Program.) )

4. It is possible that the sound wave screen is used for a period of time, the reflection stripes around the screen are covered by a large amount of dust, resulting in the calibration can not be carried out, if you use our company's KA cabinet, you can open the upper cover and wipe it with a dry soft cloth, pay attention to the upper left, upper right, lower right transducer can not be damaged. Start your computer and calibrate.

9. The mouse stays on a certain point on the touchscreen

Fault analysis and processing

This situation occurs because the touch area of the resistive screen (the surface of the resistive screen is divided into two parts: the touch area and the non-touch area, and there is no reaction when you click on the non-touch area) is pressed by the display shell or cabinet shell, which is equivalent to being touched all the time at a certain point. If the cabinet housing is pressing the touch area, you can increase the distance between the cabinet and the monitor screen a little more, and if the monitor housing is pressing the touch area, you can try to loosen the screws of the monitor housing a little bit.

10. The touch screen works unstable

Fault phenomenon: a touch screen, its work is extremely unstable, sometimes it can click normally, sometimes it does not respond.

Fault analysis and processing

In view of this phenomenon, it is necessary to focus on checking whether the wiring interface is loose and whether the serial port and interrupt number are conflicting.
Kunlun Tongtai touch screen - 10 kinds of fault phenomena and treatment methods of touch screen

More on that
Kunlun touch screen IP address view and setting Kunlun touch screen IP address view and setting

1) After the above touch calibration is completed, click [Enter Operating System] in the [Startup Properties] dialog box to enter the operating system; 2) Click [Start] --> [Settings] --> [Network & Dial-up Connection]; 3) Double-click [DM9000A] to bring up the corresponding dialog box, ...

Kunlun Tongtai touch screen - comparison of the advantages and disadvantages of various industrial touch screens Kunlun Tongtai touch screen - comparison of the advantages and disadvantages of various industrial touch screens

1. Surface acoustic wave screen The three corners of the acoustic screen are pasted with transducers that transmit and receive sound waves in the X and Y directions respectively (transducers: made of special ceramic materials, divided into transmitting transducers and receiving transducers. It is to convert the electrical signal sent by the controller through the touch screen cable into sound.

The main function of Kunlun Tongtai embedded configuration software The main function of Kunlun Tongtai embedded configuration software

The main features of the MCGS embedded configuration software 1. Simple and flexible visual operation interface: using full Chinese and visual development interface, in line with the usage habits and requirements of Chinese. 2. Strong real-time performance and good parallel processing performance: it is a real 32-bit system...

Kunlun Tongtai touch screen and 200smart communication Kunlun Tongtai touch screen and 200smart communication

1. First of all, go to the MCGS official website to download the latest embedded version, and you can find the PPI of S7-200 in the "Equipment Toolbox", which is compatible with the driver of Siemens SMARTPLC. 2. Secondly, all non-board equipment in Kunlun MCGS is the first to pass ...

How to insert primitives into MCGS Kunlun Tongtai touch screen? How to insert primitives into MCGS Kunlun Tongtai touch screen?

Open Kunlun Tongtai touch screen software, create a new [Window 0], and click to open. Find the Bitmap icon in the toolbox and click to open it. After creating a bitmap in Window 0, right-click and select Load Bitmap. Open the text where the image is saved ...

Kunlun Tongtai touch screen - maintenance method of resistive touch screen Kunlun Tongtai touch screen - maintenance method of resistive touch screen

1) Check whether the connection of the touch screen is right, and whether one of the wires connected to the keyboard port of the host (take the working voltage of 5 volts touch screen from the keyboard port) is connected, please check the connection. 2) Observe the situation of the touch screen control box light, if it is not lit or the red light is on, it means that the control box is broken, please change it.

Kunlun Tongtai touch screen - operation methods and skills of touch screen Kunlun Tongtai touch screen - operation methods and skills of touch screen

1. If you are using a capacitive touch screen, then it is recommended that you first install the driver required for the capacitive touch screen correctly according to the requirements of the manual when you use it for the first time, and then click "Start" / "Programs" / "Microtouch" on the screen with your fingers.

Common Problems and Solutions of Embedded Version of Kunlun Tongtai MCGS Touch Screen(31-40) Common Problems and Solutions of Embedded Version of Kunlun Tongtai MCGS Touch Screen(31-40)

31. Historical alarms are not displayed (1) "Automatically save the generated alarm information" is not selected in the attribute setting of the alarm data object; (2) The alarm data does not reach the upper/lower limit of the alarm value; (3) "MCGS_ALARM" is not selected for the group object. 32. ...

Kunlun Tongtai touch screen arrived in large quantities Kunlun Tongtai touch screen arrived in large quantities

Kunlun Tongtai touch screen arrives in large quantities, can be easily matched with Siemens PLC, details can be consulted There is a stock model TPC1061TI TPC1071GI TPC1561HII TPC1570GI TPC7062TI TPC7072GI ...

Common problems and solutions of embedded version of Kunlun Tongtai MCGS touch screen(41-43) Common problems and solutions of embedded version of Kunlun Tongtai MCGS touch screen(41-43)

41. How to implement pop-up sub-windows This is achieved using the OpenSubWnd() function, which is described in the MCGS help document. 42. After power failure, save it as the initial value of the next boot Use it in the script of the exit strategy! SaveSingleDataInit() and ! FlushDat ...

Hardware Problems and Solutions of Kunlun Tongtai MCGS Touch Screen(96-100) Hardware Problems and Solutions of Kunlun Tongtai MCGS Touch Screen(96-100)

96. How to check the status of the PC connection to the TPC network? Connect the PC to TPC with a network swap cable, click "Start-Run" on the PC, enter CMD enter in the run bar, and then enter the ping IP address in the DOS interface.

How to modify the time of Kunlun Tongtai touch screen? How to modify the time of Kunlun Tongtai touch screen?

1. Tap the settings icon in the top right corner of the screen to enter the settings menu. 2. Find the "Time Settings" option in the menu and click to enter. 3. On the time settings screen, you can manually modify the current date and time. There is also the option to automatically get the time so that the device ...

Kunlun Tongtai touch screen - comparison of the applicability of infrared touch screen and other touch screens Kunlun Tongtai touch screen - comparison of the applicability of infrared touch screen and other touch screens

1 Resistive touch screen - Not afraid of water and dirt - It has the cost advantage of small size, which is suitable for industrial control products and personal portable products - Fear of scratches, low light transmittance, low temperature dullness 2. Surface acoustic touch screen - New and easy to use, suitable for short-term products ...

Can the Kunlun Tongtai touch screen program be programmed when read out? Can the Kunlun Tongtai touch screen program be programmed when read out?

Kunlun Tongtai touch screen USB flash drive backup program can be edited. 1. Insert the USB flash drive. 2. Insert the USB port behind the touch screen, restart the touch screen, and wait for the touch screen screen to appear. 3. Click System Maintenance. 4. Click Back up system information. 5. Determine the ...

Kunlun Tongtai touch screen - the types of touch screen and a comprehensive introduction Kunlun Tongtai touch screen - the types of touch screen and a comprehensive introduction

Infrared touch screen The infrared touch screen selects the infrared matrix densely packed in the X and Y directions to detect and locate the user's contact, the infrared touch screen is provided with a circuit board frame on the front side of the display, and the circuit board is equipped with an infrared emitting tube and an infrared receiving tube on the four sides of the screen.

Introduction to the main performance and parameters of MCGS Kunlun Tongtai touch screen TPC7062TI Introduction to the main performance and parameters of MCGS Kunlun Tongtai touch screen TPC7062TI

1. Processor: Intel Celeron J1900 quad-core processor, frequency 2.0GHz, stable and reliable performance. 2. Operating system: Support Windows, Linux and other operating systems, and provide pre-installed software (such as remote monitoring software). 3. Display: 7 inch T...

Kunlun Tongtai touch screen - precautions and common problems of capacitive touch screen Kunlun Tongtai touch screen - precautions and common problems of capacitive touch screen

1. If the user is using a capacitive touch screen, it is recommended that the user first install the driver required for the capacitive touch screen correctly according to the requirements of the relevant manual, and then click "Start"/"Program"/"Micro ...

How to set the Kunlun Tongtai touch screen and PLC communication is normal How to set the Kunlun Tongtai touch screen and PLC communication is normal

The first channel of all non-board devices in Kunlun MCGS is the communication status channel. After entering the running environment, after the device driver starts working, the communication status of the device is returned in this channel, for example, 0 indicates that the device communicates normally, and non-0 indicates that it is abnormal. Elder brother...

Kunlun Tongtai touch screen - precautions for the purchase of industrial touch screen Kunlun Tongtai touch screen - precautions for the purchase of industrial touch screen

First of all, there is touch technology, which is very important. At present, there are three commonly used types of touch technology for touch screens, which are resistive touch screens, capacitive touch screens, and infrared touch screens. Capacitance and resistance can not be made of large size, infrared touch screen can be made of small size, can also be made of large ...

Kunlun Tongtai touch screen - what parts are the touch screen composed of Kunlun Tongtai touch screen - what parts are the touch screen composed of

(1) FILM- For touch film, the substrate is PET. When touched, the ITO in the upper and lower layers passes through the membrane, which creates deformation contacts in the X and Y axes (similar to the principle of moving a rheostat) with different "resistance values". According to different requirements, the surface of the film is divided into two types ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top