Seriously affect the normal operation of the inverter. The core components of the inverter are IGBT power semiconductor switching components. When they are working properly, they generate a lot of heat. If there is no fan forced cooling, the sensor will immediately detect (IGBT) overheating, send it to the CPU, and immediately issue a command to stop. The display panel will display the overheating code (at this time, the display code will show ERR01, the inverter unit maintenance, which includes blocked air ducts, damaged fans, non-operation or abnormal operation), prompting the operator to check and clean before operation.
The following is a brief introduction to the requirements of the working environment and the key points of operation
(1) Inverter operating environment requirements: Inverter can only operate safely and reliably in a regular environment. If the environmental conditions do not meet the requirements, corresponding improvement measures should be adopted. The operating environment conditions of the inverter are as follows.
The ambient temperature is -10-+50 °C, and the 6-10kV medium voltage inverter is generally 0-40 °C. Beyond this temperature scale, electronic components are simply damaged and functions simply fail. Pay attention to ventilation and heat dissipation.
For constant torque loads, the high ambient temperature must not exceed 50°C, and for variable torque loads, the high ambient temperature must not exceed 40°C. For the sake of safety, in practical application, it is generally emphasized that the ambient temperature of the inverter device should not exceed 40 °C.
When the ambient temperature does not exceed 40°C, the inverter can output 100% of the additional current continuously; When the ambient temperature is 45°C, the inverter can only output 80% of the current continuously; Although the ambient temperature is only increased by 5°C, the additional output current is reduced by 20%. When the ambient temperature continues to rise to 50°C, the output current of the inverter is only 60%. It can be seen that the operating ambient temperature of the inverter has a great influence on the additional output current. Therefore, special attention should be paid to the ventilation and heat dissipation at the site of the inverter installation.
|
More on that
|
Delixi inverter parameter setting method
P0.00: Set to G type (constant torque load type).
P0.01: Set to 1 fundamental efficacy model.
P0.02: Set to 1V/F control.
P0.03: Set to 0 keyboard control.
P0.04: Set to be given by the external terminal for multi-segment commands.
...
|
|
Delixi occasion to choose the inverter
We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter.
When selecting the inverter, the current value of the actual motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a reference. Secondly, the output of the inverter should be fully considered ...
|
|
Precautions for instrument maintenance - Delixi
1. When using a multimeter ohm, remember not to measure with electricity.
2. When using the logic pen and oscilloscope to detect the signal, it is necessary to pay attention not to make the probe contact the two measurement pins together, because the essence of this situation is to constitute a short circuit in the case of power-on.
3. Detect filtering in the power supply ...
|
|
The meaning of type B, type C, type D in circuit breaker - Delixi
In the circuit breaker model, the requirement clearly indicates the type of tripper trip characteristic curve, which is a very important parameter in the circuit breaker model expression. The type of trip is generally indicated before the circuit breaker has additional housing current.
For example...
|
|
Inverter application skills - Delixi
1. Shielded wires should be used for signal lines and control lines, which is beneficial to avoid disturbance. When the line is long, for example the distance jumps 100m, the conductor cross-section should be enlarged. The signal line and the control line should not be placed in the same cable trench or tray with the power line, so as not to disturb each other, it is best to place it through the pipe, ...
|
|
The reason for the failure of the inverter - Delixi
1. Ability to adapt to the environment
When the motor on the bus starts in a group, when the bus is the largest motor unit starts, the impact on the operation of the inverter, which is related to the input voltage fluctuation scale parameters promised by the inverter, for thermal power units should ensure that the bus voltage drops by 30% when the frequency conversion ...
|
|
Delixi spare parts replacement cycle description
1. Cooling fan (2-3 years)
As long as the inverter is in use, the cooling fan has always been running, so the cooling fan is generally the shortest service life of the accessories, generally after the use of the cooling fan for 2-3 years, the bearings, balls, motors, etc. of the fan are seriously worn, and they need to be replaced.
|
|
Delixi reduces the number of inverter maintenance times
Inverter is a very widely used equipment in the modern factory, this is a new type of equipment, the price is very noble, and the price of inverter repair is also very expensive, so in the process of using inverter, pay attention to the use of inverter, on the one hand, inverter, delay inverter ...
|
|
Causes and solutions for circuit breaker closing failure - Delixi circuit breaker
1. Failure analysis.
1) Closing fuse, control fuse blowing or poor contact.
2) Poor contact of DC contactor or poor contact of control switch contact and auxiliary contact of circuit breaker.
3) The DC voltage is too low.
4) Closing and locking action.
...
|
|
Installation steps of motor protector - Delixi
1. According to the requirements of the device part and the needs of the maintenance function, reasonably select the motor maintainer model and its various maintenance action parameter settings;
2. According to the requirements of the product operation manual, the correct device should be connected correctly according to the use of each terminal, and the operating power supply should be connected to the control ...
|
|
Delixi voltage regulator in the case of no load stable work?
Most modern LDOs and switching regulators operate reliably under no-load conditions, and some older power devices require a minimum load to ensure stability, because one of the electrodes that needs to be compensated is affected by the payload resistance. For example, the LM1117 requires a load current of at least 1.7 mA (most ...
|
|
Judgment and treatment of inverter short-circuit fault characteristics - Delixi
(1) Fault characteristics
a) The first trip may occur during operation, but if it is restarted after resetting, it will often trip as soon as the speed is raised.
b) have a large inrush current, but most drives are now able to perform maintenance trips without damage. Due to the ...
|
|
Is a circuit breaker an air switch? - Delixi
1. Circuit breaker refers to a switchgear that can turn on, carry and turn off the current under normal circuit conditions and turn on, carry and turn off the current under abnormal circuit conditions within a regular time.
According to the voltage of Delixi circuit breaker, there are high-voltage circuit breakers and low-voltage circuit breakers. Below 1kV ...
|
|
Delixi circuit breaker mechanism spring design
The spring is a widely used component in the circuit breaker mechanism, and the critical spring has a great impact on the function of the circuit breaker. From the perspective of energy, combined with the installation space of the tension spring, the author uses the existing accounting formula of the tension spring to solve the unknown quantity from the known quantity to obtain the required tension spring parameters.
|
|
Delixi inverter load type
The correct choice of Delixi inverter is very critical to the normal operation of the control system. When selecting a frequency converter, it is necessary to fully understand the load characteristics driven by the frequency converter. In practice, people often divide production machinery into three types: constant torque load, constant power load and fan, water pump ...
|
|
Delixi power transformer protection role
In most large electrical systems, generators and power transformers are the two most expensive pieces of equipment. In addition to the capital cost of purchase, the continuity and reliable operation of these two key equipment systems are also the most critical.
For example, the test ...
|
|
Delixi inverter control motor problem
Question: Delixi inverter control motor contactor does not start when there is no action?
Solution: First check the output status of the controller reflected by the controller panel, and you can compare the 7 units on the panel described in the controller description book.
|
|
What are the advantages and disadvantages of dry and oil regulators? - Delixi
Oil Regulator: Also known as non-contact inductive regulator or intelligent non-contact regulator (only the name of the company's own selling point).
Forte:
1. No contact, no protection, impact resistance (especially instantaneous impact, 2 times of normal.) The reason for this is the slow response, which ...
|
|
How to change the original parameters of the inverter and re-set - Delixi
The inverter has many set parameters, each of which has a certain selection range. In the process of use, it is often encountered that the inverter cannot operate normally due to improper parameter settings. Therefore, the relevant parameters must be corrected.
...
|
|
Delixi three-phase motor electrical control circuit principle
What is the principle of the electrical control circuit of the three-phase motor? First of all, let's take a look at what is the principle of electrical control of work machinery. The schematic diagram of the electrical control circuit of the working machinery is actually connected with graphic symbols, text symbols and lines to show the connection relationship and circuit of each electrical component.
|
|