With the development of society, PLC programmable controller has been widely used in industrial production, but its maintenance and overhaul methods and skills, many engineers are not lawful, the following is to introduce the experience and skills of PLC use process.
1. PLC input and output
A small PLC flexibly controls a complex system, and all you can see is the upper and lower rows of staggered input and output relay terminals, corresponding indicators and PLC numbers, like an integrated circuit with dozens of legs. Anyone who doesn't look at the schematic diagram to troubleshoot faulty equipment will be helpless and will be particularly slow to find faults. In view of this situation, we draw a table according to the electrical schematic diagram, paste it on the console or control cabinet of the equipment, and indicate the electrical symbol corresponding to the number of each PLC input and output terminal, the Chinese name, that is, the functional description of each pin similar to the integrated circuit.
With this I/O table, it is time for an electrician who understands the operation process or is familiar with the ladder diagram of the equipment. But for those electricians who are not familiar with the operation process and do not know how to read the ladder diagram, they need to draw another table: PLC input and output logic function table. The table actually illustrates the logical correspondence between the input loops (trigger elements, associated components) and output loops (actuators) during most operations. Practice has proved that if you are proficient in using the input-output correspondence table and the input-output logic function table, you can troubleshoot electrical faults without drawings.
2. Input circuit overhaul
To judge the quality of an input circuit such as a button, limit, line, etc., you can press the button (or other input contact) when the PLC is energized (preferably in a non-running state to prevent the equipment from malfunctioning), then the corresponding PLC input point terminal and the common end are short-circuited, and the PLC input indicator light corresponding to the button is on, indicating that the button and the line are normal. If the light is not on, it may be twisted, the line contact is poor, or the wire is broken.
If further judgment, if the button is good, then use a watch pen of the multimeter, one end is connected to the common end of the PLC input terminal, and the other end is to touch the corresponding PLC input point (be careful with the above operation, do not touch the 220V or 110V input terminal). At this time, the indicator light is on, indicating that there is a fault in the line. If the indicator light is not on, it means that the PLC input point has been damaged (this situation is rare, generally caused by strong current intrusion).
3. Overhaul of output circuit
For the PLC output point (here only the relay output type), if the indicator light corresponding to the action object is not lit, after determining that the PLC is in the running state, then it means that the PLC input and output logic function of the action object is not satisfied, that is to say, the input circuit is faulty, according to the previous mention, check the input circuit. If the corresponding indicator light is on, but the corresponding actuator such as solenoid valve and contactor does not operate, first check the solenoid valve control power supply and fuse, and the easiest way is to use a pen to measure the common terminal of the corresponding PLC output point.
If the pen does not light up, it may be a power failure such as a blown fuse. The electric pen is bright, indicating that the power supply is good, and the corresponding solenoid valve, contactor, and line are faulty. After eliminating the fault of solenoid valve, contactor, line, etc., it is still abnormal, use a multimeter pen, one end is connected to the corresponding output common terminal, and the other end is in contact with the corresponding PLC output point, at this time, the solenoid valve is still not moving, indicating that the output line is faulty.
If the solenoid valve is in action at this point, then the problem is at the PLC output point. Because the electric pen sometimes falsely alarms, another method can be used to analyze, use the voltage of the multimeter voltage level PLC output point and the common end, the voltage is zero or close to zero, indicating that the PLC output point is normal, and the fault point is in the periphery. If the voltage is high, the contact resistance of this contact is too large and has been damaged.
In addition, when the indicator light is not lit, but the corresponding solenoid valve, contactor, etc. operates, this output point may be burned due to overload or short circuit. At this time, the external wiring of this output point should be removed, and then the resistance of the output point and the common end should be measured with the resistance of the multimeter resistance file, if the resistance is small, it means that this contact has been broken, if the resistance is infinite, it means that this contact is good, and the corresponding output indicator has been broken.
4. Program logic inference
Nowadays, there are many kinds of PLCs often used in the industry, for low-end PLCs, ladder instructions are similar, for high-end machines, such as S7-300, many programs are programmed in language tables. The practical ladder diagram must have Chinese symbol annotations, otherwise it is difficult to read, if you can roughly understand the equipment process or operation process before looking at the ladder diagram, it seems easier.
If the electrical fault analysis is carried out, the reverse check method or the reverse deduction method is generally applied, that is, according to the input and output corresponding tables, the output relay of the corresponding PLC is found from the fault point, and the logical relationship that satisfies its action is started to be reversed. Experience shows that when a problem is found, the fault can basically be eliminated, because there are not many points of failure of the equipment with two or more failures at the same time.
5. PLC self-fault judgment
In general, PLCs are extremely reliable devices with a low failure rate, but they can also cause PLC damage due to external causes.
(1) a working power supply is the proximity switch of 220V, and two leads of its input PLC signal contact share a 4-core cable with the power line of 220V of proximity switch, and this proximity switch is damaged once, and when the electrician replaces, mistakenly adjust the neutral line of the power supply and the common line of the input PLC, and cause the 3-way PLC input point to be burned out when the power is transmitted.
(2) The neutral line row of the primary system power transformer was interrupted due to corrosion, resulting in the power supply of the access PLC220V rising to 380V, burning out the power module at the bottom of the PLC, and adding a 380/220V isolation control transformer during the rectification.
(3) Siemens S7-200 PLC output common end mark 1L, 2L, etc., the working computer is AC L1 N means, +24V power supply is L+M means that it is easy to make mistakes for beginners or inexperienced people. If L+M is mistaken for a 220V power terminal, the PLC24V power supply will be burned out at the moment of power transmission.
The probability of hardware damage such as PLC and CPU or software operation error is almost zero, and the PLC input point will hardly be damaged if it is not caused by strong current intrusion, and the normally open point of the PLC output relay is not a short circuit or unreasonable design of the peripheral load, the load current exceeds the rated range, and the life of the contact is also very long.
Therefore, we find the electrical fault point, the focus should be on the peripheral electrical components of the PLC, do not always suspect that there is a problem with the PLC hardware or program, which is very important for the rapid repair of faulty equipment and rapid recovery of production, so the electrical fault repair of the PLC control loop, the focus is not on the PLC itself, but on the peripheral electrical components in the PLC control loop.
|
More on that
|
Hollysys PLC - PLC should be noted in operation (three, four, five)
3. Main anti-interference measures
(1) Reasonable treatment of power supply to suppress the interference introduced by the power grid
For grid disturbances introduced by the power supply, an isolation transformer with a shielded ratio of 1:1 can be installed to reduce the interference between the equipment and the ground.
|
|
What are the characteristics of Hollysys PLC - PLC program?
1. Correctness (low debugging cost)
First of all, the PLC program must be able to work correctly to meet the requirements of the actual control process. This is the essence of the PLC program, and if you don't do that, nothing else makes sense.
2. Reliability (low maintenance cost)
Not only to ...
|
|
HollySys PLC - What places should be avoided when installing PLC?
(1) The ambient temperature exceeds the range of 0-50 °C;
(2) The relative humidity exceeds 85% or there is dew condensation (caused by sudden temperature changes or other factors);
(3) direct sunlight;
(4) There are corrosive and flammable gases, such as hydrogen chloride, ...
|
|
Hollysys DCS - Introduction to I/O in DCS control system
The control system needs to establish the input and output channels of the signals, which is called I/O. The I/O in a DCS is generally modular, with one or more I/O channels on one I/O module for connecting sensors and actuators (control valves).
The control unit of the DCS: a process control station is ...
|
|
Hollysys PLC - what are the commonly used networking methods of PLC?
1 Universal serial port module
Based on the serial port communication module to realize the network connection, the network structure is shown in Figure 1, the form of computer link is adopted, the corresponding settings are carried out in the configuration software of the host computer, and the communication can be carried out with multiple PLCs without programming, and the FXlS of Mitsubishi ...
|
|
Hollysys DCS - DCS fault maintenance measures
Whether it is a new unit or an upgraded DCS, the equipment of the system and controller should focus on the reliability and load factor (including redundancy) objectives. The load rate planning of the communication bus must be controlled within a reasonable range, and the load rate of the controller should be balanced as much as possible.
|
|
Hollysys DCS - Introduction to the main features of DCS
(1) High reliability
DCS is designed to be fault-tolerant, so that when a computer fails, it does not cause the system to lose other functions. In addition, because the tasks undertaken by the individual computers in the system are relatively simple, it is possible to adopt a specific structure and ...
|
|
Hollysys PLC - PLC serial communication knowledge
1. What is serial communication?
Serial is a very versatile protocol for device communication on a computer (not to be confused with Universal Serial Bus or USB). Most computers contain two serial ports based on RS232.
The serial port is also an instrument ...
|
|
Hollysys PLC - Introduction to the functions and application fields of PLC
1. The function of PLC
PLC is a general industrial automatic control device with microprocessor as the core, integrating computer technology, automatic control technology and communication technology, which has high reliability, small size, strong function, simple program design, flexible and universal and maintenance methods.
|
|
Hollysys PLC - Introduction to the classification of PLC according to the structure and form
According to the structural form of PLC, PLC can be divided into two categories: integral type and modular type.
(1) Integral PLC
The integral PLC is a centralized power, CPU, I/O interface and other components in a chassis, which has the characteristics of compact structure, small size and low price. Small PLC ...
|
|
Hollysys debuted at the XCon2022 Security Focus Information Security Technology Summit
On September 19, 2022, the XCon2022 Security Focus Information Security Technology Summit was successfully held in Beijing. More than 10 technical experts, heads of security departments, and front-line security experts from well-known domestic network security enterprises shared in-depth topics at the meeting.
|
|
Hollysys PLC - What is the use of the PLC interrupt function?
PLC understands the interrupt function in this way, when understanding the interrupt, we must first understand the PLC operation cycle or the scanning cycle, it is necessary to say that the PLC sequential control cycle execution process, which is the premise of understanding the interrupt, must be mastered, divided into three parts, input processing, program processing, output ...
|
|
Hollysys DCS - Introduction to the hardware architecture of DCS
Examining the hierarchical structure of DCS, DCS level and control management level are the two most basic links that make up DCS.
The process control stage specifically realizes the decentralized control functions such as signal input, conversion, operation and output. The controls at the process control level vary in different DCS, ...
|
|
Century Qualcomm and Hollysys reached a strategic cooperation
With the inclusion of "exploring the construction of digital twin cities" in the 14th Five-Year Plan, the field of intelligent transportation is being endowed with more new business value. Recently, Century Qualcomm and Hollysys reached a strategic cooperation, based on the principle of "giving full play to advantages, mutual promotion, long-term cooperation, mutual benefit and win-win", ...
|
|
and Nesbitt DCS - the difference between SCADA and DCS and PLC
To put it simply, DCS is mainly used for process automation, PLC is mainly used for factory automation (production lines), and SCADA is mainly for wide-area needs, such as oil fields and pipelines that stretch for thousands of miles. If from the point of view of computers and networks, they are unified, and the reason for the difference is mainly in ...
|
|
Hollysys PLC - the isolation technology of the input/output loop of the PLC control system
1. Circuit isolation
The isolation of analog circuits is more complex, mainly depends on the accuracy requirements of the transmission channel, the higher the accuracy requirements, the higher the cost of the channel; However, when the performance requirements rise to the main contradiction, the isolation components should be selected based on performance, and the ...
|
|
Bureau Veritas signed a strategic cooperation agreement with Hollysys Group and issued a ball valve functional safety certificate to it
Recently, the signing ceremony of the strategic cooperation between Bureau Veritas and Hollysys and the functional safety certification ceremony of Hollysys valves were held in the Hangzhou base of Hollysys. Mr. Ye Jiong, General Manager of Bureau Veritas Technology Center, Mr. Zhong Aimin, Director of Product Certification Center, Mr. Yang Yang, Sales Director of Eastern Region, and Mr. Yang Yang, Director of Functional Safety ...
|
|
Hollysys launched an intelligent simulation teaching instrument system to help cultivate industry professionals
In recent years, the State Administration of Safety Supervision, the Ministry of Industry and Information Technology, the Ministry of Education, and the Ministry of Finance have successively launched a number of national policies to implement major decision-making projects such as vocational skills improvement actions, safety skills improvement actions, and vocational education reforms, aiming to create a highland for the training of technical and skilled talents.
|
|
Hollysys PLC - what are the application fields of PLC
1. Logic control of switching quantity
This is the most basic and most extensive application field of PLC, which replaces the traditional relay circuit to achieve logic control and sequence control, which can be used for the control of a single device, as well as for multi-machine group control and automatic assembly line. Such as injection molding machines, printing machines, ...
|
|
Hollysys was invited to participate in the 2023 China Petroleum and Chemical Industry Digital Transformation and Intelligent Development Conference and delivered a keynote speech
On March 15, the 2023 China Petroleum and Chemical Industry Digital Transformation and Intelligent Development Conference was held in Tai'an, Shandong. The conference aims to strengthen the construction of "intelligent oil and gas fields, intelligent petrochemicals, intelligent chemicals and intelligent oil and gas pipeline networks", and lead China's petroleum and chemical industry to achieve intelligent transformation.
|
|