Introduction: Rosemount/Rosemount 2410 Tank Hub, the Rosemount 2410 handles data communication between field devices and the control room and is available in single and multi-tank versions. Control room communication options include Modbus, IEC 62591 (WirelessHART® protocol), and simulation of other vendor protocols. The Rosemount 2410 can also power Rosemount field devices on FISCO-compliant intrinsically safe Tankbuses.
Features:
Data is collected from one or more tanks and transmitted to the control room.
Save installation costs by using the bus-powered, intrinsically safe 2-wire Tankbus.
Choose from a variety of control room communication possibilities, including Modbus, IEC 62591 (WirelessHART® protocol), and emulation of other vendor protocols.
Calculate average temperature, observed density, and volume based on volume table.
Simplified start-up through automatic configuration of the tank equipment.
Get two configurable output relays and one level alarm analogue output, both SIL certified.
Product parameters
Tank Hub VersionSingle Tank Version: Supports one Rosemount 5900S 2-in-1 gauge or two radar gauges, with the Rosemount 5300, 5400 or 5900 mounted on the same tank.
Multi-tank version: for Rosemount 5300/5400/5900 system configurations:
The software supports the installation of 16 field devices and 10 tanks per hub.
Up to five Rosemount Model 5300 or 5400 gauges on each Hub.
Transfer of Custody certification OIML R85: 2008 and national certifications such as PTB, NMi and many more
Safety • SIL 2 and SIL 3 certified.
• Overfill protection is TÜV tested and WHG certified.
Tank Bus Foundation™ Fieldbus FISCO (self-configuring).
The fieldbus Rosemount 2410 communicates with a host or field communication unit via TRL2 Modbus, RS485, 4-20 mA/HART, Enraf, L&J Tankway, Varec Mark/Space, Whessoe, GPE, Sakura, Tokyo Keiso and WirelessHART® protocols.
The relay outputs two SIL-certified relays that can be configured for different tanks and process variables.
The analog input has one input channel and the current range is 0-23 mA.
One output channel for the analog output (SIL certified) with a current range of 3.5-23 mA (HART).
Simulation capabilities can be integrated with traditional tank metering systems. Support emulating communication protocols from other vendors. See "Fieldbus" above.
Display/interface integrated digital readout display: liquid level, rate of change of liquid level, air height, signal strength, volume (TOV), average liquid temperature, 1–16 point temperature, average vapor temperature, ambient temperature, free water level, liquid pressure, vapor and air pressure, observed and reference density, and flow rate.
Power supply • 24-48 VDC (-15% to +10%).
• 48-240 VAC (-15% to +10%), 50/60 Hz.
Ambient temperature -40 to +70 °C (-40 to +158 °F). The minimum start-up temperature is -50 °C (-58 °F).
When using an LCD display: -25 to 70 °C (-13 to 158 °F).
Our customer-centric service concept: the pursuit of a full range of services is a high-quality, high-standard service, the pursuit of every detail of the service process. It is impossible for interests to blossom into brilliant flowers from lies. Only every process, every action, and every detail of the service can be professional and careful, in order to meet or even exceed customer expectations, so that customers are satisfied and recognize us. Honest, professional, affordable, fast, so let you rest assured." Integrity and professional service, affordable price, and continuous improvement" is our service concept.