Functions of the Siemens 3RV2 circuit breaker

Create Date: 2024-8-30 12:03:23|Source: Siemens/Siemens

The 3RV2 circuit breakers are available with screw, spring-loaded or ring terminals, giving you the flexibility to choose the right wiring type for your application.
Functions of the Siemens 3RV2 circuit breaker

Installation

The 3RV2 circuit breaker can be snapped on a standard 35 mm rail.

The S00 and S0 sizes are available with 3RV29 28-0B lugs for direct screw attachment to the base plate.

Trippers

The 3RV2 motor protection circuit breaker is equipped with a reverse-time bimetallic thermal overload trip and an instantaneous overcurrent trip (electromagnetic short circuit trip).

The thermal overload trip current can be adjusted according to the load current. In order to start the motor without failing, the short-circuit trip current is fixed at 13 times the rated current of the circuit breaker.

In order to prevent tripping caused by higher transformer inrush currents, the circuit breaker for transformer protection on the power side is set to short-circuit trip current at 20 times the rated current of the transformer.

Trip level

The tripping rating of the thermal overload tripper is based on the tripping time at 7.2 times the cold operating current

(tA) (from IEC 60947-4 standard):

  CLASS 10A:2s < tA ≤ 10s

  CLASS 10:4s < tA ≤ 10s

  CLASS 20:6s < tA ≤ 20s

  CLASS 30:9s < tA ≤ 30s

The motor protection circuit breaker must trip within that time frame.

Operating mechanism

The 3RV2 circuit breaker works by rotating the operating mechanism. When the circuit breaker trips, the rotary operating mechanism will switch to the "tripped" position to indicate it. Before the circuit breaker is re-closed, the rotary operating mechanism must be manually reset to the "0" position to prevent the circuit breaker from being misclosed before troubleshooting, after which the circuit breaker can be placed in the "I" position.

All rotary control mechanisms can be locked in the "0" position with a single padlock (padlock hook diameter 3.5 mm - 4.5 mm).

The isolation function of the 3RV2 circuit breaker complies with the standard IEC 60947-2.

More on that
What is the bypass operation of the 3RW series soft starter? How to choose a bypass contactor? What is the bypass operation of the 3RW series soft starter? How to choose a bypass contactor?

After the 3RW series soft starter is started, there are two main operation methods: continuous operation and bypass operation. At this time, the thyristor is in a fully conductive state, and the system enters a constant speed operation state. Here, we advocate that the user should choose the bypass method to operate, that is, when the starting is completed to reach the full voltage ...

What mechanism does the Siemens S7-1200 CPU cycle work by? What mechanism does the Siemens S7-1200 CPU cycle work by?

The S7-1200 CPU cycles according to the following mechanism: 1. Write the output value from the process image output area to the physical output 2. Read the physical input before the user program is executed, and save the input value to the process image input area 3. Execute the user program, carry out the logical ...

Siemens S7-1200 PLC power requirements and calculations Siemens S7-1200 PLC power requirements and calculations

The S7-1200 CPU offers 5 VDC and 24 VDC power supplies: When there is an expansion template, the CPU provides it with 5 VDC power over the I/O bus, and the sum of the 5 VDC power consumption of all expansion modules cannot exceed the power rating provided by the CPU. If it's not enough, you can't go outside ...

Siemens launches an open digital business platform Siemens launches an open digital business platform

Siemens Xcelerator enables companies of all sizes in industry, buildings, power grids, and transportation to accelerate digital transformation and value creation. With this business channel, digital transformation will be easier, faster, and easier to scale. Siemens Xcelerator integrates the best ...

Siemens PLC has six common fault-prone points Siemens PLC has six common fault-prone points

1. The first type of fault point is also the location of the most faults in relays and contactors For example, in the daily maintenance of the PLC control system of a production line, the largest consumption of electrical spare parts is all kinds of relays or air switches. In addition to the quality of the product itself, it is mainly due to the fact that the on-site environment is more ...

Siemens will acquire FORAN entirely Siemens will acquire FORAN entirely

Siemens will fully acquire POLLAN in October 2021 to enhance its marine planning and engineering capabilities. The FORAN business will then be integrated into the Xcelerator channel, which Siemens has been promoting in recent years. With the acquisition of FORAN, Siemens will provide the shipbuilding industry with a comprehensive software and ...

Siemens is investing 600 million euros in an industrial and technological center in Berlin Siemens is investing 600 million euros in an industrial and technological center in Berlin

Sept. 16 (Reuters) -- Siemens returned to its headquarters in Berlin on Wednesday to announce plans to invest 600 million euros ($681 million) in an industrial and technological center in Germany's capital. This investment will contribute to the creation of a new Siemensstadt in the Berlin area, the predecessor of Siemens ...

SIMATIC S7-1200 compact CPU SIMATIC S7-1200 compact CPU

Installation 1. Remove the backplane bus cover 2. Insert the SM onto the standard mounting rail 3. Push the SM to the adjacent module 4. Lock the standard rail mounting clip 5. Push the latch used to connect the bus connector to the left so that the bus pin is connected to the adjacent module ...

Siemens loads the item to a memory card in transfer mode Siemens loads the item to a memory card in transfer mode

Mount items to a memory card in transfer mode Step 1: Follow the above method to set the memory card to "Transfer Card" mode. Customers are advised to clear all files from the memory card before doing this. Step 2: Set the boot state of the CPU: In the "Project ...

Basic data types supported by Siemens S7-1200 Basic data types supported by Siemens S7-1200

The basic data types supported by the Siemens S7-1200 include the following:   Boolean data is a one-digit binary number, the value of which is 0 or 1, and the constant value of the data is TRUE, FALSE, 0, 1, etc. The byte-type data is an eight-digit binary number, and the value scale is 16-base 00 to 16-base FF, ...

Siemens presents the new Sinamics G220 high-performance inverter Siemens presents the new Sinamics G220 high-performance inverter

On the eve of the Hannover Messe 2023, Siemens launched a new product in the Sinamics series, the Sinamics G220 high-performance frequency inverter. This innovative inverter product uses clean converter technology to reduce harmonics by up to 97% without the need for incoming filters or incoming reactors.   ...

Siemens acquires a minority stake in WiTricity Siemens acquires a minority stake in WiTricity

Siemens invested $25 million to acquire a minority stake in WiTricity, a United States wireless charging technology company. Siemens and WiTricity will work together to promote the innovation of new shopping malls for wireless electric car charging, according to Siemens' calculations, by 2028, only in Europe and North America, which ...

Siemens helped CIMC ENRIC win the hydrogen energy track Siemens helped CIMC ENRIC win the hydrogen energy track

ENRIC is a leading manufacturer of clean power equipment under World Marine Containers (Group) Co., Ltd. in China, and has accumulated full tacit understanding and trust with Siemens in projects such as LNG system integration project and Hebei Xiong'an oil, gas and hydrogen integrated power service station. ...

How do I clear the error status 16 # 8382 when I am connected to a Modbus TCP between SIMATIC S7-1500/S7-1200 and a SENTRON PAC device? How do I clear the error status 16 # 8382 when I am connected to a Modbus TCP between SIMATIC S7-1500/S7-1200 and a SENTRON PAC device?

The S7-1500 CPU or S7-1200 CPU uses the "MB_CLIENT" command as a Modbus TCP client via the integrated PROFINET interface. Use the "MB_CLIENT" command to establish a connection between the Modbus TCP client and the Modbus TCP server. Fig. 1 as ...

Whether the input module of Siemens S7-300 supports the connection of NPN and PNP proximity switches Whether the input module of Siemens S7-300 supports the connection of NPN and PNP proximity switches

Does the S7-300 input module SM321 support connecting NPN and PNP proximity switches? The vast majority are drain inputs (including 31xC integrated DI) with PNP proximity switches; Source input: 6ES7321-1BH50-0AA0, connected to NPN proximity switch; Source/Drain Inputs: 6E ...

Siemens helps Birdon build a digital shipyard Siemens helps Birdon build a digital shipyard

Birdon shipyard in Australia has selected Siemens' Teamcenter software to support its digital shipyard strategy. The software is used for Product Life Cycle Management (PLM) and is integrated with NX software for computer-aided planning (CAD) to improve the overall planning process by ...

What is RFC1006 and what does it do? What is RFC1006 and what does it do?

RFCs (Requests for Comments) are technical documents that cover topics such as Ethernet architecture, protocol design, email header design, etc. - Detailed description of RFC 1006 "ISO Transport Service on top of the ...

Siemens S7-1200 PLC basic functions Siemens S7-1200 PLC basic functions

1. S7-1200 CPU real-time clock hold time 20 days typical, 12 days minimum at 40°C (maintenance-free supercapacitors); With the BB1297 battery plate and CR1025 battery, the real-time clock power off hold time is approximately 1 year. 2. S7-1200 CP ...

How to view the full order number of our 3RW soft starter How to view the full order number of our 3RW soft starter

1. Find from the front panel of the product, as shown in the figure below, the part of the red box in the picture The characters that start with 3RW are the order number: 3RW4036-1BB14 2. Look for the white sticker label on the right side of the product, as shown in the figure below, look at the part that is boxed in red, and find the one that starts with 3RW.

Common solutions for Siemens G120 inverter F08502 faults Common solutions for Siemens G120 inverter F08502 faults

1 Check whether there is EMC interference in the inverter or network cable To ensure that the inverter is firmly grounded, the grounding resistance of the inverter is generally required to be less than 4 ohms. Industrial-grade shielded network cables and network cable connectors are used The shielding layer of the network cable should be firmly grounded, and the shielding of the more ambitious ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top