DZ20 series plastic shell circuit breaker (hereinafter referred to as circuit breaker), its rated insulation voltage is 660V, AC 50Hz, rated working voltage 380V and below, and its rated current is from 32A to 1250A. Generally, it is used for power distribution, among which the rated current of type C is 160A and below, and the circuit breaker of type 630 and below shell frame can also be used as a protective motor. Under normal circumstances, the circuit breaker can be used for infrequent line conversion and infrequent start of the motor, respectively.
Number of poles: 3P
Rated operating voltage: 380
Rated insulation voltage: 660
Short-circuit breaking capacity** value: 25/0.25 19/0.30
Circuit breaker rated current: 125.160.180.200.225
Operation frequency (times/hour): 120
Shunt trip:
Rated control power supply voltage: AC220V, AC380V.
When the rated control supply voltage is between 70% and 110%, the shunt trip should reliably trip the circuit breaker.
Undervoltage Tripper:
Rated working voltage: AC220V, AC380V. When the voltage drops (or even slowly drops) to the range of 70%-35% of the rated voltage, the undervoltage tripper should act, and when it is lower than 35% of the rated voltage of the tripper, the undervoltage tripper should be able to prevent the circuit breaker from closing, and when the power supply voltage is equal to or greater than 85%, the circuit breaker should be able to be closed.
Alarm Contacts:
Rated working voltage: AC220V, agreed heating current: 3A.
Auxiliary contacts: Auxiliary contacts can be installed when undervoltage trippers and shunt trippers are worn in different fashions. The number of non-energized operation performance of the auxiliary contact is the same as that of the circuit breaker, and the number of power-on operation is 6050 times, and when the number of operation performance of the circuit breaker is less than 6050 times, it is equal to the circuit breaker.
This article introduces CHINT/CHINT DZ20 series plastic case circuit breaker DZ20Y-225 If you are interested, please also contact our customer service, we are looking forward to your call, and hope our technology and service can bring you a better experience.
The company has been customer-centric, the concept of creating value for customers, winning the market with quality and service, and sincerely hopes to cooperate with all sectors of society to create success, create brilliance together, and work together to create a better tomorrow! In line with the concept of credibility and service-oriented, the company warmly welcomes new and old customers to inquire, visit and negotiate business!
|
More on that
|
CHINT/CHINT CKJ5 Series Vacuum AC Contactor CKJ5-160
CKJ5 series vacuum AC contactor (hereinafter referred to as contactor) is mainly used in AC 50Hz, rated working voltage to 1140V, rated working current to 630A circuit, for long-distance connection and breaking of circuits, and can be used with appropriate thermal overload relay or electronic protection ...
|
|
CHINT/CHINT NXBFLE-32 residual current action circuit breaker
NXBFLE-32 residual current action circuit breaker is suitable for AC 50Hz, rated voltage 230V/400V, rated current to 32A in the line, play the role of overload, short circuit and leakage protection, can also be used as infrequent line on and off under normal circumstances.
The product conforms to IEC61009-1, GB/T...
|
|
CHINT/CHINT NBH8LE-40□ residual current action circuit breaker
NBH8LE-40 □ residual current action circuit breaker (hereinafter referred to as circuit breaker) is suitable for AC 50Hz, rated voltage 230V, rated current to 40A in the line, when the person is electrocuted or the leakage current of the power grid exceeds the specified value, the circuit breaker can quickly cut off the fault power supply in a very short time, ...
|
|
CHINT/CHINT NBH-40 miniature circuit breaker
NBH-40 miniature circuit breaker is mainly used for overload and short circuit protection of power lines in household and similar places with AC 50Hz, rated voltage to 230V and rated current to 40A, and can also be used for infrequent switching of electrical devices and power lines under normal circumstances.
Products...
|
|
CHINT/CHINT LA19 series buttons
The LA19 series pushbutton is suitable for electromagnetic starters, contactors, relays and other electrical circuits with AC voltage from 50Hz or 60Hz to 380V and DC voltage to 220V for remote control.
Conform to the standard: GB/T 14048.5.
Rated insulation voltage: 380V
Agree on free air ...
|
|
CHINT/CHINT NSD1 series servo drives
Servo drives, also known as "servo controllers" and "servo amplifiers", are a kind of controller used to control servo motors, and their functions are similar to those of inverters acting on ordinary AC motors. Servo drives are part of the servo system and are mainly used in high-precision ...
|
|
CHINT/CHINT V9 undervoltage tripper
V9 undervoltage tripper is mainly used for AC 50Hz (60Hz), rated working voltage of 230V in the line with NB1, NB1L series circuit breaker for under-voltage protection.
Meets the standard: IEC60947-5-1, obtained CE certification.
Basic parameters
1. Rated working voltage Ue: 230V AC
...
|
|
CHINT/CHINT NCH8G Household AC Contactor NCH8G-25/11
NCH8G series household AC contactor (hereinafter referred to as contactor) is mainly suitable for AC 50Hz (or 60Hz), rated working voltage to 400V rated working current to 63A circuit, control household appliances and similar uses of low-inductance and micro-inductance loads; It can also be used to control household ...
|
|
CHINT/CHINT NB8LE-40 residual current action circuit breaker
NB8LE-40 residual current action circuit breaker is mainly suitable for AC 50Hz, rated voltage to 230V, rated current to 40A in commercial office buildings, civil residential and general industrial terminal distribution lines, to provide overload, short circuit protection and leakage protection for the line, but also in normal conditions ...
|
|
CHINT/CHINT NXCQ contactor type mechanical emergency starter
Product Overview
NXCQ series contactor emergency start device is a product specially designed and developed for fire water supply system, with the function of manual mechanical emergency start fire pump, in line with GB/T50974-2014 "Technical Specification for Fire Water Supply and Fire Hydrant System" for manual mechanical emergency starting.
|
|
CHINT/CHINT SHT-X1H shunt tripper
SHT-X1H shunt trip is suitable for AC rated voltage to 400V or DC rated voltage 48V in the line, and NBH-63, NBH-40 series circuit breaker matching, when the tripper terminal is connected to the rated control voltage, the tripper action and drive the circuit breaker to automatically break, so as to achieve long-distance ...
|
|
CHINT/CHINT LW32 series universal transfer switch
LW32 series universal transfer switch can replace (CA10, LW26) transfer switch, mainly used for AC 50Hz or 60Hz, rated working voltage 380V and below, DC voltage 220V and below the control circuit for master control, can also directly control small capacity motor.
Standards: GB/...
|
|
CHINT/CHINT NB1LE-40□ residual current operated circuit breaker
NB1LE-40□ residual current action circuit breaker is suitable for AC 50Hz, rated voltage single pole two wires, two poles 230V, three poles, three poles four wires, four poles 400V, rated current to 40A line, when the person is electrocuted or the leakage current of the power grid exceeds the specified value, the residual current action circuit breaker can be ...
|
|
CHINT/CHINT Terminal Appliances —NXU-III. Surge Protective Device
CHINT/CHINT Terminal Appliances —NXU-III. Surge Protective Device
Basic parameters and technical performance indicators (Table 1)
Design types and protection mode combinations for different models of surge protective devices (see Table 2)
SPECIAL FEATURES
The surge protective device has a deterioration indication, as shown in sequence 3 in the figure ...
|
|
CHINT/CHINT NB5 miniature circuit breaker
CHINT Xinrui NB5 series terminal power distribution products are suitable for power line facilities and electrical equipment in commercial buildings, residential buildings, industrial equipment and similar places with AC 50Hz, rated voltage of 230V/400V and rated current up to 125A.
|
|
CHINT/CHINT HY23 series reverse switch
HY23 series instead of HZ3 series combination switch is suitable for AC 50Hz or 60Hz, voltage 380V circuit, as a power supply introduction switch, or as a three-phase squirrel cage induction motor with a control operation frequency of no more than 300 times per hour.
Standards: GB/T 14048.3, IEC 60947-3 ...
|
|
CHINT/CHINT NXBLE-125G residual current action circuit breaker
CHINT/CHINT NXBLE-125G residual current action circuit breaker
Rated current(In) : 63A, 80A, 100A, 125A (1P+N.2P) ;
Rated Residual Operating Current (IOn): 0.03A, 0.05A, 0.075A, 0.1A, 0.3A;
Rated Operating Voltage (Ue) ...
|
|
CHINT/CHINT NXBF-63 miniature circuit breaker
NXBF-63 miniature circuit breaker is mainly used for overload and short circuit protection of power lines in household and similar places with AC 50Hz, rated voltage to 230/400V and rated current to 63A, and can also be used to turn on and off electrical devices and power lines infrequently under normal circumstances.
...
|
|
CHINT/CHINT soft starter NJR2-D series rated insulation voltage 660V
Introduction: NJR2-D series soft starter is based on advanced dual CPU control technology as the core, controls the thyristor module, realizes the soft start and soft stop functions of the three-phase AC asynchronous motor, and has the functions of overload, input phase loss, output phase loss, load short circuit, starting current limiting timeout, overvoltage, ...
|
|
CHINT/CHINT NSC1 Series Motion Controller NSC1-D16
32-bit high-performance CPU, compiled execution mode, scan cycle is 10 times faster than analytical type, and the basic instruction single-step running time is 0.05μs.
Weight: 102
Power consumption: 2
Digital inputs: 16
Degree of protection: IP30