DZ20 series plastic shell circuit breaker (hereinafter referred to as circuit breaker), its rated insulation voltage is 660V, AC 50Hz, rated working voltage 380V and below, and its rated current is from 32A to 1250A. Generally, it is used for power distribution, among which the rated current of type C is 160A and below, and the circuit breaker of type 630 and below shell frame can also be used as a protective motor. Under normal circumstances, the circuit breaker can be used for infrequent line conversion and infrequent start of the motor, respectively.
Number of poles: 3P
Rated operating voltage: 380
Rated insulation voltage: 660
Short-circuit breaking capacity** value: 12/0.3 8/0.5
Circuit breaker rated current: 100.125.160
Operation frequency (times/hour): 120
Shunt trip:
Rated control power supply voltage: AC220V, AC380V.
When the rated control supply voltage is between 70% and 110%, the shunt trip should reliably trip the circuit breaker.
Undervoltage Tripper:
Rated working voltage: AC220V, AC380V. When the voltage drops (or even slowly drops) to the range of 70%-35% of the rated voltage, the undervoltage tripper should act, and when it is lower than 35% of the rated voltage of the tripper, the undervoltage tripper should be able to prevent the circuit breaker from closing, and when the power supply voltage is equal to or greater than 85%, the circuit breaker should be able to be closed.
Alarm Contacts:
Rated working voltage: AC220V, agreed heating current: 3A.
Auxiliary contacts: Auxiliary contacts can be installed when undervoltage trippers and shunt trippers are worn in different fashions. The number of non-energized operation performance of the auxiliary contact is the same as that of the circuit breaker, and the number of power-on operation is 6050 times, and when the number of operation performance of the circuit breaker is less than 6050 times, it is equal to the circuit breaker.
This article introduces CHINT/CHINT DZ20 series plastic case circuit breaker DZ20C-100 If you are interested, please also contact our customer service, we are looking forward to your call, and hope that our technology and service can bring you a better experience.
The company has been customer-centric, the concept of creating value for customers, winning the market with quality and service, and sincerely hopes to cooperate with all sectors of society to create success, create brilliance together, and work together to create a better tomorrow! In line with the concept of credibility and service-oriented, the company warmly welcomes new and old customers to inquire, visit and negotiate business!
|
More on that
|
CHINT/CHINT DW17D series universal circuit breaker
DW17D series universal circuit breaker is suitable for AC voltage 400V (380V), 690V (660V), 50Hz, rated working current to 3900A power distribution network, used to distribute power and protect lines and power equipment from overload, undervoltage, short circuit and other hazards, under normal conditions, can also be used as ...
|
|
CHINT/CHINT OVT-X3H Overvoltage Tripper
OVT-X3H overvoltage tripper is suitable for AC 50Hz, rated voltage 230V line, and NBH-125 series circuit breaker is used together, when the voltage at the end of the tripper rises to the voltage protection range, the tripper acts and drives the circuit breaker to automatically break, so as to achieve the overvoltage protection of the line.
...
|
|
CHINT/CHINT YBLX-WL Series Position Switch YBLX-WL/NJ/S2
YBLX-WL travel switch is mainly used in the control circuit of AC 50Hz or 60Hz, voltage 380V, DC voltage 220V, for the travel control of the moving mechanism, the transformation of the direction or speed of the movement, the automatic control of the machine tool, the limit action of the moving mechanism and the control of the stroke or program.
Accord with...
|
|
CHINT/CHINT LW6 series universal transfer switch
LW6 series universal transfer switch is mainly suitable for control and conversion circuits in machine tool control circuits with AC 50Hz or 60Hz, voltage to 380V and DC voltage to 220V. It can also be used for the conversion of control circuits in other occasions, such as electromagnetic coils, electrical measuring instruments, etc.
Standards: GB ...
|
|
CHINT/CHINT NTP1 Series Industrial Touch Screen NTP1-102/102E
Based on the Linux system, the system is stable, efficient and reliable. Industrial-grade high-performance Cortex A8 processor with a clock speed of 600MHz. The COM port integrates RS232/422/485 communication mode. The product provides USB master station and USB slave port, USB slave download port supports 10M/s transmission speed, ...
|
|
CHINT/CHINT OVT-X1 overvoltage tripper
Rated working voltage (Ue): AC230V 50Hz;
Rated insulation voltage (Ui): 500V;
Overvoltage Action Setting Value (Uo): 280 (1+5%) V;
Tripper action characteristics: When the main circuit voltage is 230 (1+5%)V, the tripper should be able to keep the circuit breaker working for a long time. When the Lord ...
|
|
CHINT/CHINT NB1L (10kA) residual current operated circuit breaker
NB1L residual current action circuit breaker is suitable for AC 50Hz, rated voltage 230V, rated current to 40A line, when the person is electrocuted or the leakage current of the power grid exceeds the specified value, the residual current action circuit breaker can quickly cut off the fault power supply in a very short time, protect people and electrical equipment...
|
|
CHINT/CHINT AX-5 auxiliary contacts
The AX-5 auxiliary contact is suitable for AC 50Hz, the agreed heating current to 6A, the rated voltage to 415V or the DC rated voltage to 130V, and it is assembled with the NL1 residual current action circuit breaker for the signal indication of the long-distance circuit breaker.
Conform to the standard: GB/T 14048.5, ...
|
|
CHINT/CHINT YBLX-ME series travel switch
YBLX-ME series travel switch is suitable for AC 50Hz or 60Hz, voltage 380V, DC voltage 220V control circuit, for the travel control of the moving mechanism, the change of the direction or speed of the movement, the automatic control of the machine tool, the limit action of the moving mechanism and the control of the stroke or program.
Symbol...
|
|
CHINT/CHINT NXBF-63 miniature circuit breaker
NXBF-63 miniature circuit breaker is mainly used for overload and short circuit protection of power lines in household and similar places with AC 50Hz, rated voltage to 230/400V and rated current to 63A, and can also be used to turn on and off electrical devices and power lines infrequently under normal circumstances.
...
|
|
CHINT/CHINT NB8-40 miniature circuit breaker
NB8-40 miniature circuit breaker is mainly suitable for AC 50Hz, rated voltage to 240V, rated current to 40A in commercial office buildings, residential and general industrial use of terminal distribution lines, to provide overload, short circuit protection, but also under normal circumstances to the line infrequent turnover...
|
|
CHINT/CHINT YBLX-WL Series Travel Switch YBLX-WL/CA12
YBLX-WL travel switch is mainly used in the control circuit of AC 50Hz or 60Hz, voltage 380V, DC voltage 220V, for the travel control of the moving mechanism, the transformation of the direction or speed of the movement, the automatic control of the machine tool, the limit action of the moving mechanism and the control of the stroke or program.
Accord with...
|
|
CHINT/CHINT NC7 Series AC Contactor Free air heating current 20A
Introduction: CHINT/CHINT AC contactor NC7-09 (hereinafter referred to as contactor) is mainly used for AC 50Hz (or 60Hz), rated working voltage to 690V, in the AC-3, 400V use category rated working current to 620A circuit, mainly used for long-distance connection and breaking circuits...
|
|
CHINT/CHINT DZ20 Series Plastic Case Circuit Breaker DZ20Y-630
DZ20 series plastic shell circuit breaker (hereinafter referred to as circuit breaker), its rated insulation voltage is 660V, AC 50Hz, rated working voltage 380V and below, and its rated current is from 32A to 1250A. Generally used for power distribution, the rated current of type C is 160A and below, and the shell of type 630 and below ...
|
|
CHINT/CHINT NB1L-40□ residual current action circuit breaker
NB1L-40 □ residual current action circuit breaker is suitable for AC 50Hz, rated voltage single pole two wires, two poles 230V, three poles, three poles four wires, four poles 400V, rated current to 40A line, when the person is electrocuted or the leakage current of the power grid exceeds the specified value, the residual current action circuit breaker can be used in the pole ...
|
|
CHINT/CHINT CJ19 Series Switching Capacitor Contactor CJ19-43
CJ19 series switching capacitor contactor (hereinafter referred to as contactor) is mainly used in power lines with AC 50Hz (or 60Hz) and rated working voltage to 690V, which is used for low-voltage reactive power compensation equipment to put in or remove low-voltage shunt capacitors. Contactors with inhibition ...
|
|
CHINT/CHINT CJ40 Series AC Contactor CJ40-200
CJ40 series AC contactor (hereinafter referred to as contactor) is mainly used for switching and breaking circuits in power systems with AC 50Hz or 60Hz, rated voltage to 660V or 1140V, and current to 1000A.
|
|
CHINT/CHINT CJ19 Series Switching Capacitor Contactor CJ19-25
CJ19 series switching capacitor contactor (hereinafter referred to as contactor) is mainly used in power lines with AC 50Hz (or 60Hz) and rated working voltage to 690V, which is used for low-voltage reactive power compensation equipment to put in or remove low-voltage shunt capacitors. Contactors with inhibition ...
|
|
CHINT/CHINT NP8 series buttons
NP8 series button is suitable for AC 50Hz (60Hz), rated working voltage 415V and below or DC rated working voltage 250V and below in industrial control circuits, as electromagnetic starters, contactors, relays and other electrical circuit control, with indicator light button is also suitable for ...
|
|
CHINT/CHINT NP3 series buttons
The NP3 series pushbutton is suitable for circuit control systems with AC 50Hz or 60Hz, voltage up to 380V, DC working voltage up to 220V. It is suitable for remote control of equipment in the open air, rain, snow and dust, such as cranes, electric hoists and other equipment.
Standard: GB/T 14048. ...
|
|