DZ20 series plastic shell circuit breaker (hereinafter referred to as circuit breaker), its rated insulation voltage is 660V, AC 50Hz, rated working voltage 380V and below, and its rated current is from 32A to 1250A. Generally, it is used for power distribution, among which the rated current of type C is 160A and below, and the circuit breaker of type 630 and below shell frame can also be used as a protective motor. Under normal circumstances, the circuit breaker can be used for infrequent line conversion and infrequent start of the motor, respectively.
Number of poles: 3P
Rated operating voltage: 380
Rated insulation voltage: 660
RMS for short-circuit breaking capacity: 18/0.3 14/0.3
Circuit breaker current rating: 32.40.50.63.80.100
Operation frequency (times/hour): 120
Shunt trip:
Rated control power supply voltage: AC220V, AC380V.
When the rated control supply voltage is between 70% and 110%, the shunt trip should reliably trip the circuit breaker.
Undervoltage Tripper:
Rated working voltage: AC220V, AC380V. When the voltage drops (or even slowly drops) to the range of 70%-35% of the rated voltage, the undervoltage tripper should act, and when it is lower than 35% of the rated voltage of the tripper, the undervoltage tripper should be able to prevent the circuit breaker from closing, and when the power supply voltage is equal to or greater than 85%, the circuit breaker should be able to be closed.
Alarm Contacts:
Rated working voltage: AC220V, agreed heating current: 3A.
Auxiliary contacts: Auxiliary contacts can be installed when undervoltage trippers and shunt trippers are worn in different fashions. The number of non-energized operation performance of the auxiliary contact is the same as that of the circuit breaker, and the number of power-on operation is 6050 times, and when the number of operation performance of the circuit breaker is less than 6050 times, it is equal to the circuit breaker.
This article introduces CHINT/CHINT DZ20 series plastic case circuit breaker DZ20Y-100 If you are interested, please also contact our customer service, we are looking forward to your call, and hope our technology and service can bring you a better experience.
The company has been customer-centric, the concept of creating value for customers, winning the market with quality and service, and sincerely hopes to cooperate with all sectors of society to create success, create brilliance together, and work together to create a better tomorrow! In line with the concept of credibility and service-oriented, the company warmly welcomes new and old customers to inquire, visit and negotiate business!
|
More on that
|
CHINT/CHINT NB1-63□ miniature circuit breaker
NB1-63 □ miniature circuit breaker is suitable for AC 50Hz rated voltage 230/400V, rated current to 63A in the line, for overload and short circuit protection, under normal circumstances, as the line of infrequent operation and conversion, can also be used as a disconnecting switch for disconnecting the line for line and equipment maintenance...
|
|
CHINT/CHINT CJX1-K Series Contactors The operating frequency is 1200 hours
Introduction: CJX1-K series AC vacuum contactor (hereinafter referred to as contactor), mainly used for AC 50Hz-60Hz, rated insulation voltage of 1000V, rated working voltage of 380V under the AC-3 use category of rated working current to 820A in the circuit, for long-distance connection and disconnection ...
|
|
CHINT/CHINT NH5-125 disconnector
NH5-125 disconnector is mainly suitable for AC 50Hz, rated voltage to 400V, rated current 125A and below in the power distribution and control circuit, mainly as the main switch in the terminal combination electrical appliances, can also be used for infrequent control of various low-power electrical appliances and lighting, widely used in industrial and mining ...
|
|
CHINT/CHINT OVT-X3H Overvoltage Tripper
OVT-X3H overvoltage tripper is suitable for AC 50Hz, rated voltage 230V line, and NBH-125 series circuit breaker is used together, when the voltage at the end of the tripper rises to the voltage protection range, the tripper acts and drives the circuit breaker to automatically break, so as to achieve the overvoltage protection of the line.
...
|
|
CHINT/CHINT switch NXZ series rated insulation voltage AC800v
Introduction: NXZ series automatic transfer switch electrical appliances are suitable for AC 50Hz, rated voltage 400V/415V and below, rated current to 630A three-phase four-wire dual-circuit power supply grid, automatically connect one or several load circuits from one power supply to another, in order to ensure the normal supply of load circuits.
|
|
CHINT/CHINT CJ40 Series AC Contactor CJ40-630
CJ40 series AC contactor (hereinafter referred to as contactor) is mainly used for switching and breaking circuits in power systems with AC 50Hz or 60Hz, rated voltage to 660V or 1140V, and current to 1000A.
|
|
CHINT/CHINT CJ19 Series Switching Capacitor Contactor CJ19-115
CJ19 series switching capacitor contactor (hereinafter referred to as contactor) is mainly used in power lines with AC 50Hz (or 60Hz) and rated working voltage to 690V, which is used for low-voltage reactive power compensation equipment to put in or remove low-voltage shunt capacitors. Contactors with inhibition ...
|
|
CHINT/CHINT YBLX-WL Series Travel Switch YBLX-WL/CA12
YBLX-WL travel switch is mainly used in the control circuit of AC 50Hz or 60Hz, voltage 380V, DC voltage 220V, for the travel control of the moving mechanism, the transformation of the direction or speed of the movement, the automatic control of the machine tool, the limit action of the moving mechanism and the control of the stroke or program.
Accord with...
|
|
CHINT/CHINT NCH8G Household AC Contactor NCH8G-25/01
NCH8G series household AC contactor (hereinafter referred to as contactor) is mainly suitable for AC 50Hz (or 60Hz), rated working voltage to 400V rated working current to 63A circuit, control household appliances and similar uses of low-inductance and micro-inductance loads; It can also be used to control household ...
|
|
CHINT/CHINT AL-X3H alarm contact
The AL-X3H alarm contact conforms to GB/T 14048.5 standard. It is mainly used in lines with AC rated voltage to 415V or DC rated voltage to 130V, and assembled with NBH-125 series circuit breaker for signal indication of long-distance circuit breaker fault breaking.
Alarm contact is an accessory product, assembled in ...
|
|
CHINT/CHINT NCH8G Household AC Contactor NCH8G-63/31
NCH8G series household AC contactor (hereinafter referred to as contactor) is mainly suitable for AC 50Hz (or 60Hz), rated working voltage to 400V rated working current to 63A circuit, control household appliances and similar uses of low-inductance and micro-inductance loads; It can also be used to control household ...
|
|
CHINT/CHINT CJ19 Series Switching Capacitor Contactor CJ19-25
CJ19 series switching capacitor contactor (hereinafter referred to as contactor) is mainly used in power lines with AC 50Hz (or 60Hz) and rated working voltage to 690V, which is used for low-voltage reactive power compensation equipment to put in or remove low-voltage shunt capacitors. Contactors with inhibition ...
|
|
CHINT/CHINT NVF5 series inverter No PG vector
Introduction: NVF5 series simple vector inverter, using no speed sensor vector control technology, has the characteristics of small and lightweight, fast operation and excellent performance.
Product parameters
input
Voltage range: single-phase 230V (±15%) three-phase 380V (-15%) - 4 ...
|
|
CHINT/CHINT NP2 series buttons
NP2 series button is suitable for AC 50Hz or 60Hz, rated working voltage to 415V and DC working voltage to 250V in industrial control circuits, as electromagnetic starters, contactors, relays and other electrical circuit control, with indicator light button is also suitable for light signal indication ...
|
|
CHINT/CHINT AX-X3 auxiliary contacts
Rated operating current at different rated operating voltages:
Action characteristics: The wiring principle of the auxiliary contact is shown in Figure 1. When the auxiliary contact is opened, the 11th and 12th terminals are turned on; When the auxiliary contact is closed, the 11th and 14th terminals are turned on.
Life: The operating life of the auxiliary contact is 10,000 times.
This article describes ...
|
|
CHINT/CHINT CJ19 Series Switching Capacitor Contactor CJ19-170
CJ19 series switching capacitor contactor (hereinafter referred to as contactor) is mainly used in power lines with AC 50Hz (or 60Hz) and rated working voltage to 690V, which is used for low-voltage reactive power compensation equipment to put in or remove low-voltage shunt capacitors. Contactors with inhibition ...
|
|
CHINT/CHINT NM1B series plastic shell circuit breaker NM1B-250S
The circuit breaker is rated for insulation voltage up to 800V, suitable for AC 50Hz, rated working voltage up to 400V, rated working current from 10A to 250A in the distribution network circuit, used to distribute power and protect lines and power supply equipment from overload, short circuit, undervoltage and other faults. At the same time ...
|
|
CHINT/CHINT Terminal Appliance —NXHB-125 Disconnector
The NXHB-125 disconnector complies with IEC60898 and GB10963 standards. It is suitable for AC 50Hz or 60Hz, rated voltage 250V and below residential single-phase lines, to protect the overload and short circuit of electrical lines. The product has high breaking capacity, small size and a width of only 18mm. Zero, fire ...
|
|
CHINT/CHINT Terminal Appliance UVT-X1 Undervoltage Tripper
Rated Operating Voltage (Ue) : AC 230V , 50Hz;
Rated insulation voltage (Ui): 500V;
Undervoltage action setting value: (35%-70%) Ue;
Action characteristics: the external voltage ≤35%Ue, and the product should prevent the circuit breaker from closing; 35%Ue≤ external voltage ...
|
|
CHINT/CHINT CJ20 Series AC Contactor CJ20-63
CJ20 series AC contactor (hereinafter referred to as contactor) is mainly used in AC 50Hz (or 60Hz), rated working voltage to 660V, rated working current to 630A, for long-distance switching and breaking circuits, and can be combined with appropriate thermal overload relays.
|
|