Introduction: Omron/Omron 3G3RX Advanced General Inverter Heat dissipation mode: forced air cooling, control mode two-phase sinusoidal modulation PWM, output frequency range 0.1~400Hz.
peculiarity
Pay attention to the environment
Easy to operate
Support more applications
parameter
project | specification | Protection Specifications | IP20 (0.4~55kW)
IP00 (75~132kW) | Heat dissipation | Forced air cooling | Control mode | Two-phase sinusoidal modulation PWM | Output frequency range | 0.1~400Hz | Frequency accuracy | Digital Commands: ±0.01% of Maximum Frequency
Analog command: ±0.2% of maximum frequency (25°C ± 10°C) | Frequency resolution | Digital setting: 0.01 Hz
Analog setting: maximum frequency/4000
(Terminal FV: 12 bits/0~+10V), (Terminal FE: 12 bits/-10~+10V), (Terminal FI: 12 bits/0~+20mA) | Voltage/frequency characteristics | (Optional) V/f can be changed in the base frequency of 30~400Hz, V/f braking constant torque, torque reduction, sensorless vector control, 0Hz sensorless vector control | Fluctuations in speed | ±0.5% (under sensorless vector control or 0Hz sensorless vector control) | Overload current rating | 150%/60s、200%/3s | Acceleration/deceleration time | 0.01~3600.0s (line/curve selection) | Starting torque | 200%/0.3Hz (under sensorless vector control or 0Hz sensorless vector control) | 150%/torque at 0Hz (under sensorless vector control at 0Hz when connected to a motor whose size is one bit lower than the specified motor rank) | DC braking | Operates at a lower starting frequency than when decelerating by a stop command, when the frequency command is lower than the operating frequency, or via an external input (variable braking power, time, and frequency). | input | Multi-function input | 8 terminals, NO/NC switchable, drain/source logic switchable
[Terminal Function] You can select 8 functions from 61 functions.
Backward (RV), Multi-Step Speed Set Binary 1 (CF1), Multi-Step Speed Set Binary 2 (CF2), Multi-Step Speed Set Binary 3 (CF3), Multi-Step Speed Set Binary
4 (CF4), Stepper (JG), DC Braking (DB), Second Control (SET), Two-Step Acceleration/Deceleration (2CH), Free Run Stop (FRS), External Trip (EXT), USP Function
(USP), Commercial Switching (CS), Soft Lock (SFT), Analog Input Switching (AT), Third Control (SET3), Reset (RS), 3-Wire Start (STA), 3-Wire Stop (STP), 3-Wire Direction
Forward/Backward (F/R), PID Enable/Disable (PID), PID Integrated Reset (PIDC), Control Gain Switching (CAS), UP/DWN Function Acceleration (UP), UP/DWN Function Deceleration
(DWN), UP/DWN Function Data Erase (UDC), Forced Manipulator (OPE), Multi-Step Speed Set Bit 1 (SF1), Multi-Step Speed Set Bit 2 (SF2), Multi-Step Speed Set Bit
3 (SF3), multi-step speed set bit 4 (SF4), multi-step speed set bit 5 (SF5), multi-step speed set bit 6 (SF6), multi-step speed set bit 7 (SF7), overload limit switch
(OLR), Torque Limit Enabled (TL), Torque Limit Switch 1 (TRQ1), Torque Limit Switch 2 (TRQ2), P/PI Switch (PPI), Brake Confirmation (BOK), Direction (ORT),
LAD Cancellation (LAC), Position Deviation Clear (PCLR), Pulse Train Position Command Input Permission (STAT), Frequency Increase Function (ADD), Forced Terminal Block (F-TM), Torque Command
Input License (ATR), Integrated Power Purge (KHC), Servo ON (SON), Primary Excitation (FOC), Analog Instruction Hold (AHD), Position Instruction Select 1 (CP1), Position Finger
Order Choice 2 (CP2), Position Command Option 3 (CP3), Zero Return Limit Signal (ORL), Zero Return Start Signal (ORG), Forward Drive Stop (FOT), Backward Drive Stop
(ROT), Speed/Position Switch (SPD), Pulse Counter (PCNT), Pulse Counter Clear (PCC), No Assignment (no) | Thermistor input terminal | 1 terminal (positive and negative temperature coefficient of resistance element can be switched) | output | Multi-function output | 5 open collector output terminals: NO/NC switchable, drain/source logic switchable
1 relay (SPDT contact) output terminal: NO/NC switchable
[Terminal Functions] You can select 6 functions from 45 functions.
Signal during operation (RUN), constant speed reach signal (FA1), exceeding set frequency reach signal (FA2), overload warning (OL), excessive PID deviation (OD), alarm signal (AL),
Only the frequency reached signal (FA3), over-torque (OTQ), signal during instantaneous power interruption (IP), signal during under-voltage (UV), torque limit (TRQ), and run-time exceeded are set
(RNT), Power ON Time Exceeded (ONT), Thermal Warning (THM), Brake Release (BRK), Brake Error (BER), 0Hz Signal (ZS), Excessive Speed Deviation (DSE), Position
Ready (POK), Set Frequency Over 2 (FA4), Set Frequency Only 2 (FA5), Overload Warning 2 (OL2), Analog FV Disconnect Detection (FVDc), Analog FI Disconnect
Detection (FIDc), Analog FE Disconnection Detection (FEDc), PID FB Status Output (FBV), Network Error (NDc), Logic Operation Output 1 (LOG1), Logic Operation Output
2 (LOG2), Logic Operation Output 3 (LOG3), Logic Operation Output 4 (LOG4), Logic Operation Output 5 (LOG5), Logic Operation Output 6 (LOG6), Capacitor Life Warning
(WAC), Cooling Fan Life Warning (WAF), Start Contact Signal (FR), Chip Overtemperature Warning (OHF), Light Load Detection Signal (LOC), Ready for Operation (IRDY), Forward Shipment
Line (FWR), Backward Run (RVR), Fatal Failure (MJA), Window Comparator FV (WCFV), Window Comparator FI (WCFI), Window Comparator FE (WCFE), Alarm Generation
Code 0~3(AC0~AC3) | Multi-function monitor output terminal | Analog voltage output, analog current output, pulse train output (A-F, D-F {multiplied by "n", pulse output only}, A, T, V, P, etc.) | Display the monitor | Output frequency, output current, output torque, frequency conversion value, trip record, I/O terminal status, power supply, etc | Other features | V/f free setting (7), frequency cap/lower limit, frequency hopping, curve acceleration/deceleration, manual torque boost level/interrupt, energy-saving operation, analog meter tripping, start-up frequency,
Carrier frequency adjustment, electronic thermal function (freely configurable available), external start/end (frequency/rate), analog input selection, trip retry, instantaneous power interruption
Period restart, various signal outputs, reduced voltage start-up, overload limit, initialization value setting, automatic deceleration when power is off, AVR function, automatic acceleration/deceleration,
Auto-regulation (on-line/off-line), high-torque multi-click operation control (sensorless vector control of two monitors with one inverter) | Carrier frequency modification range | 5.9m/s2 (0.6G)、10~55Hz (0.4~22kW)
2.94m/s2 (0.3G)、10~55Hz (30~132kW) | Protection features | Overcurrent Protection, Overvoltage Protection, Undervoltage Protection, Electronic Thermal Protection, Temperature Error Protection, Instantaneous Power Interruption/Power Interruption Protection, Input Phase Loss Protection, Braking
Resistor overload protection, ground fault current detection at startup, USP error, external tripping, emergency shutdown tripping, CT error, communication error, option error, etc | Operating environment | Environment/Storage Temperature/Humidity | -10~+50°C/-20~+65°C/20~90%RH (no condensation) | Vibration* | 5.9m/s2(0.6G),10~55Hz
2.94m/s2(0.3G),10~55Hz | Use environment | below 1000m above sea level; Indoor (no corrosive gases, dust, etc.) | Optional | Encoder feedback option | Sensor vector control | DI board | 4-bit BCD, 16-bit binary | Other options | Braking resistors, AC reactors, DC reactors, digital operator cables, anti-interference filters, braking units, etc | Our customer-centric service concept: the pursuit of a full range of services is a high-quality, high-standard service, the pursuit of every detail of the service process. It is impossible for interests to blossom into brilliant flowers from lies. Only when every process, every action and every detail of the service is professional and careful, can we meet or even exceed the expectations of customers, so that customers can be satisfied and recognize us. Honest, professional, affordable, and fast, so you can rest assured. "Honest and professional service, affordable price, continuous improvement" is our service philosophy.
This article introduces the Omron/Omron 3G3RX advanced general-purpose inverter heat dissipation method: forced air cooling products, if you are interested in Omron inverter, please also contact our staff, we are looking forward to your call, hope our technology and service can bring you a better experience.
|