PLC-INTERFACE, incl. PLC-BPT.../21 base terminal, plug-in connection, with manually operated plug-in miniature relay with multi-layer gold-plated contacts, 1 changeover contact, 120 V AC/110 V DC input voltage
size
Width 6.2 mm
Height 80 mm
Depth 94 mm
Environmental conditions
Ambient temperature (operating) -40 °C ... 55 °C
Ambient temperature (storage / transport) -40 °C ... 85 °C
Protection class RT III (relay)
IP20 (Relay Base)
Coil side
Rated input voltage UN 120 V AC
110 V DC
Typical input current at UN 3.5 mA (at UN = 120V AC)
3 mA (at UN = 120V AC)
Typical response time is 6 ms
Typical release time is 15 ms
Protection circuit Bridge rectifier Bridge rectifier
The operating voltage is displayed with a yellow LED
Power consumption at rated conditions is 0.42 W
Contact side
Contact Type: 1 changeover contact
Switch contact type Single contact
Contact material AgSnO, hard gold plating
The maximum switching voltage is 30 V AC
36 V DC
Minimum switching voltage 100 mV at 10 mA
Minimum switching current 1 mA (24 V)
The maximum starting current is 50 mA
Limit continuous current to 50 mA
Maximum power rating (resistive load) 1.2 W (24 V DC)
Contact surface (with destructible gold plating)
Precautions If the plating is damaged, the following values can be applied
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (at 100 mA)
Limit continuous current to 6 A
Minimum switching current 10 mA at 12 V
Maximum power rating (resistive load) 140 W (24 V DC)
20 W (for 48 V DC)
18 W (can be used for 60 V DC)
23 W (for 110 V DC)
40 W (can be used for 220 V DC)
1500 VA (can be used for 250VAC)
Switching capacity 2 A (at 24 V, 13 DCs)
0.2 A (at 110 V, 13 DCs)
0.1 A (at 220 V, 13 DCs)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)
overview
Test voltage 4 kV AC (50 Hz, 1 minute, coil/contact)
Mode of operation 100% working factor
Flammability rating according to UL 94 V0 (enclosure)
Mechanical life 2x 107 switching cycles
Installation Position Any
Assembly Instructions Arrangement without spacing
Connect your data
Connection Name Coil Side
Connection: Push-in connection
Stripping length 8 mm
Rigid conductor cross-section 0.14 mm² ... 2.5 mm²
Flexible conductor cross-section 0.14 mm² ... 2.5 mm²
0.2 mm² … 2.5 mm² (single sleeve)
2x 0.5 mm² … 1 mm² (TWIN sleeve)
Attachable guide cross-section AWG 26 ... 14
Connect to data2
Connection Name Contact Side
Connection: Push-in connection
Stripping length 8 mm
Rigid conductor cross-section 0.14 mm² ... 2.5 mm²
Flexible conductor cross-section 0.14 mm² ... 2.5 mm²
0.2 mm² … 2.5 mm² (single sleeve)
2x 0.5 mm² … 1 mm² (TWIN sleeve)
Attachable guide cross-section AWG 26 ... 14
Standards and Specifications
Name Standards/Regulations
Standard/Procedure IEC 60664
IEC 60664A
DIN VDE 0110
DIN EN 50178/VDE 0160 (relevant part)
DIN EN 50178/VDE 0160
IEC 60255/DIN VDE 0435 (relevant parts)
Pollution level 3
Overvoltage category III
Conformance/Certification
Name CE
Certificate CE compliant
Name Corrosive Gas Testing
Identifire: ISA-S71.04. G3 Harsh Group
EN 60068-2-60
All suppliers of 76 Technology have been strictly audited to ensure that all sources of goods come from manufacturers or formal agents. Our self-confidence stems from our strict requirements for product quality, adhere to the original **, fake one pay ten, if there is a demand, welcome to consult the delivery date and price, we will select the best quotation for you in many channels, 76 technology multi-brand one-stop procurement, save you time, worry, money.
The above is the relay module with manual operation locking function of Germany brand Phoenix/Phoenix - PLC-RPT-120UC/21AU/MS - 2909674 products, the purpose of 76 Technology is to survive by quality, develop by reputation, and eternal by service, give us a chance and give you a surprise.
|
More on that
|